cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor 7A AC-3 230V/240V AC (DILM7-10(230V50HZ,240V60HZ))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM7-10(230V50HZ,240V60HZ)  ·  HS 8536.90
Contactor 7A AC-3 230V/240V AC (DILM7-10(230V50HZ,240V60HZ))

Eaton DILM7-10(230V50HZ,240V60HZ) DILM7 - Contactor 230-240 VAC incl. 1NO.

Technical Specifications

Manufacturer part number (MPN)DILM7-10(230V50HZ,240V60HZ)
EAN / GTIN4015082765507
HS code8536.90
Sales unitpcs
Eaton catalogue number276550
Depth75 mm
Height68 mm
Width45 mm
Weight0.24 kg
CertificationsCSA-C22.2 No. 60947-4-1-14; CSA Class No.: 2411-03, 3211-04; IEC/EN 60947; UL 60947-4-1; UL Category Control No.: NLDX; CSA; CE; VDE 0660; UL; CSA File No.: 012528; IEC/EN 60947-4-1; UL File No.: E29096
Catalog NotesContacts according to EN 50012
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally open contacts)1
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)45 A
Conventional thermal current Ith (3-pole, enclosed)18 A
Conventional thermal current Ith at 55°C (3-pole, open)21 A
Conventional thermal current Ith at 60°C (3-pole, open)20 A
Conventional thermal current Ith of main contacts (1-pole, open)50 A
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid0.1 W
Rated operational current for specified heat dissipation (In)7 A
Static heat dissipation, non-current-dependent Pvs1.4 W
Rated breaking capacity at 220/230 V70 A
Rated breaking capacity at 380/400 V70 A
Rated breaking capacity at 500 V50 A
Rated breaking capacity at 660/690 V40 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)112 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V22 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V7 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V7 A
Rated operational current (Ie) at AC-3, 440 V7 A
Rated operational current (Ie) at AC-3, 500 V5 A
Rated operational current (Ie) at AC-3, 660 V, 690 V4 A
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V5 A
Rated operational current (Ie) at AC-4, 440 V5 A
Rated operational current (Ie) at AC-4, 500 V4.5 A
Rated operational current (Ie) at AC-4, 660 V, 690 V4 A
Rated operational current (Ie) at DC-1, 110 V20 A
Rated operational current (Ie) at DC-1, 220 V15 A
Rated operational current (Ie) at DC-1, 60 V20 A
Rated operational power at AC-3, 240 V, 50 Hz2.2 kW
Rated operational power at AC-3, 380/400 V, 50 Hz3 kW
Rated operational power at AC-3, 415 V, 50 Hz4 kW
Rated operational power at AC-3, 440 V, 50 Hz4.5 kW
Rated operational power at AC-3, 500 V, 50 Hz3.5 kW
Rated operational power at AC-3, 690 V, 50 Hz3.5 kW
Rated operational power at AC-4, 220/230 V, 50 Hz1 kW
Rated operational power at AC-4, 240 V, 50 Hz1.5 kW
Rated operational power at AC-4, 415 V, 50 Hz2.3 kW
Rated operational power at AC-4, 440 V, 50 Hz2.4 kW
Rated operational power at AC-4, 500 V, 50 Hz2.5 kW
Rated operational power at AC-4, 660/690 V, 50 Hz2.9 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP20
Lifespan, mechanical10,000,000 Operations (AC operated)
Operating frequency9000 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance per pole2.5 mΩ
Suitable forAlso motors with efficiency class IE3
Utilization categoryAC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeAC
Frame sizeFS1
Arcing time10 ms
Drop-out voltageAC operated: 0.6 - 0.3 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.1 V AC x Uc
Power consumption, pick-up, 50 Hz24 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, pick-up, 60 Hz30 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing, 50 Hz3.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz; 1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 4.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max230 V
Rated control supply voltage (Us) at AC, 50 Hz - min230 V
Rated control supply voltage (Us) at AC, 60 Hz - max240 V
Rated control supply voltage (Us) at AC, 60 Hz - min240 V
Switching time (AC operated, make contacts, closing delay) - max21 ms
Switching time (AC operated, make contacts, closing delay) - min15 ms
Switching time (AC operated, make contacts, opening delay) - max18 ms
Switching time (AC operated, make contacts, opening delay) - min9 ms
Assigned motor power at 115/120 V, 60 Hz, 1-phase0.25 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase1.5 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase1 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase2 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase3 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase5 HP
Safe isolation400 V AC, Between the contacts, According to EN 61140; 400 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)5 kA, 25 A max. fuse, SCCR (UL/CSA); 5 kA, 25 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 20 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA); 65 kA, 16 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 20 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V35 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V20 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V20 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V16 A gG/gL
Special purpose rating of definite purpose rating7 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 42 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Special purpose rating of elevator control3.7 A, 200 V 60 Hz 3-ph, (UL/CSA); 6 A, 240 V 60 Hz 3-ph, (UL/CSA); 3.4 A, 480 V 60 Hz 3-ph, (UL/CSA); 0.75 HP, 200 V 60 Hz 3-ph, (UL/CSA); 2 HP, 480 V 60 Hz 3-ph, (UL/CSA); 3.9 A, 600 V 60 Hz 3-ph, (UL/CSA); 1.5 HP, 240 V 60 Hz 3-ph, (UL/CSA); 3 HP, 600 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)60 A, LRA 600 V 60 Hz 3phase; (CSA); 60 A, LRA 480 V 60 Hz 3phase; (CSA); 10 A, FLA 480 V 60 Hz 3phase; (CSA); 10 A, FLA 600 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating12 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 12 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps12 A (600V 60Hz 3phase, 347V 60Hz 1phase); 12 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Switching capacity (auxiliary contacts, general use)1 A, 250 V DC, (UL/CSA); 10 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)P300, DC operated (UL/CSA); A600, AC operated (UL/CSA)
Switching capacity (main contacts, general use)20 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)10 mm
Terminal capacity (solid)1 x (0.75 - 4) mm²; 2 x (0.75 - 2.5) mm²
Tightening torque1.2 Nm, Screw terminals
Terminal capacity (flexible with ferrule)2 x (0.75 - 2.5) mm²; 2 x (0.75 - 2,5) mm²; 1 x (0.75 - 2.5) mm²
Terminal capacity (solid/stranded AWG)Single 18 - 10, double 18 - 14

Properties

MOQ1

Cross-References

Attached Documents