| Manufacturer part number (MPN) | DILA-40(24V50HZ) |
| EAN / GTIN | 4015082763169 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 276316 |
| Depth | 75 mm |
| Height | 68 mm |
| Width | 45 mm |
| Weight | 0.24 kg |
| Compliances | CE Marked |
| Certifications | UL 508; CSA Std. C22.2 No. 14-05; EN 60947-4-1; IEC 60947-4-1; VDE; EN 60947-5-1; UL Category Control No.: NKCR; CSA; CSA File No.: 012528; CE; VDE 0660; CSA-C22.2 No. 14-05; IEC/EN 60947; UL File No.: E29184; CSA Class No.: 3211-03; IEC/EN 60947-4-1; UL |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | 25 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Connection to SmartWire-DT | No |
| Code number | 40D |
| Control circuit reliability | λ < 5 x 10-7 (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA); λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 4 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 4 |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.5 W |
| Rated operational current for specified heat dissipation (In) | 15.5 A |
| Static heat dissipation, non-current-dependent Pvs | 1.4 W |
| Conventional thermal current Ith at 60°C (3-pole, open) | 16 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 4 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 4 A |
| Rated operational current (Ie) at AC-15, 500 V | 1.5 A |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Safe isolation | 400 V AC, Between coil and auxiliary contacts, According to EN 61140; 400 V AC, Between auxiliary contacts, According to EN 61140 |
| Short-circuit protection rating without welding | 10 A gG/gL, 500 V, Max. Fuse, Contacts |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA); 15 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA); A600, AC operated (UL/CSA) |
| Features | Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module |
| Fitted with | Positive operation contacts |
| Application | Contactor relays |
| Connection | Screw terminals |
| Degree of protection | IP20 |
| Lifespan, mechanical | 20,000,000 Operations (AC operated) |
| Mounting method | DIN rail |
| Operating frequency | 9000 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | DILA relays |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Voltage type | AC |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V AC x Uc (voltage tolerance - single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz) |
| Power consumption, pick-up, 50 Hz | 24 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Power consumption, pick-up, 60 Hz | 24 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Power consumption, sealing, 50 Hz | 3.4 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz; 1.4 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Power consumption, sealing, 60 Hz | 1.4 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 24 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 24 V |
| Switching time (AC operated, make contacts, closing delay) - max | 21 ms |
| Switching time (AC operated, make contacts, closing delay) - min | 15 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 18 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 9 ms |
| Screw size | M3.5, Terminal screw |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver |
| Stripping length (main cable) | 10 mm |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm², Screw terminals; 2 x (0.75 - 2.5) mm², Screw terminals |
| Terminal capacity (solid) | 1 x (0.75 - 4) mm², Screw terminals; 2 x (0.75 - 2.5) mm², Screw terminals |
| Terminal capacity (solid/stranded AWG) | 18 - 14, Screw terminals |
| Tightening torque | 1.2 Nm, Screw terminals |