cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Direct-on-line starter,MSC-D-16-M17(24VDC)-PI (199612)

Eaton · Drives & Controllers · Motor Starters · Ireland · eaton.com
Part Number
199612  ·  HS 8536.50
Direct-on-line starter,MSC-D-16-M17(24VDC)-PI (199612)

Eaton 199612 Direct-on-line starter, 380 V 400 V 415 V: 7.5 kW, Ir= 10 - 16 A, 24 V DC, DC.

Technical Specifications

Manufacturer part number (MPN)199612
EAN / GTIN4015081983131
Sales unitpcs
Eaton catalogue number199612
Depth115 mm
Height214 mm
Width45 mm
Weight0.949 kg
CertificationsIEC/EN 60947-4-1; VDE 0660
Catalog NotesAlso suitable for motors with efficiency class IE3.
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient operating temperature - min-25 °C
Rated operational current (Ie)15.2 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V16 A
Rated operational power at AC-3, 220/230 V, 50 Hz4 kW
Rated operational power at AC-3, 380/400 V, 50 Hz7.5 kW
Rated operational voltage230 - 415 V AC
Fitted withShort-circuit release
FunctionsTemperature compensated overload protection
ClassCLASS 10 A
ConnectionPush in terminals
Connection to SmartWire-DTNo
Coordination type2
Degree of protectionIP20; NEMA Other
ModelIEC starter
Mounting methodDIN rail
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)1
Overload release current setting - max16 A
Overload release current setting - min10 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp)6000 V AC
Suitable forAlso motors with efficiency class IE3
TypeStarter with Bi-Metal release
Voltage typeDC
Power consumption (sealing) at DC0.86 W
Rated control supply voltage (Us) at DC - max24 V
Rated control supply voltage (Us) at DC - min24 V
Short-circuit release (Irm) - max248 A
With transformerNo
Power consumption0.9 W
Rated operation power at AC-3, 400 V7.5 kW
Number of auxiliary contacts as normally open contact1
Suitable for emergency stopNo
Rated operation current Ie15.2 A
Overload release current setting10–16 A
Supporting protocol for LONNo
Supporting protocol for TCP/IPNo
Supporting protocol for ASINo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for other bus systemsNo
External reset possibleNo
Suitable for rail mountingYes
Rated control supply voltage DC24 V
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Release classCLASS 10 A
With short-circuit releaseYes
With fuseNo
Type of electrical connection of main circuitSpring clamp connection
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for PROFINET CBANo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Voltage type for actuatingDC
Type of motor starterDirect online starter (DOL)
Rated operation power at AC-3, 230 V, 3-phase4 kW
Rated operation current at AC-3, 400 V16 A
Ambient temperature, upper operating limit55 °C
Temperature compensated overload protectionYes
Rated conditional short-circuit current, type 2, 400 V50 A
Rated conditional short-circuit current, type 2, 230 V50 A
Coordination class according to IEC 60947-4-3Class 2
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents