| Manufacturer part number (MPN) | MSC-D-2,5-M7(230V50HZ)-PI |
| EAN / GTIN | 4015081982677 |
| Sales unit | pcs |
| Eaton catalogue number | 199566 |
| Depth | 95 mm |
| Height | 197 mm |
| Width | 45 mm |
| Weight | 0.608 kg |
| Certifications | VDE 0660; IEC/EN 60947-4-1 |
| Catalog Notes | Also suitable for motors with efficiency class IE3. |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient operating temperature - min | -25 °C |
| Rated operational current (Ie) | 1.9 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 2.5 A |
| Rated operational power at AC-3, 220/230 V, 50 Hz | 0.37 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 0.75 kW |
| Rated operational voltage | 230 - 415 V AC |
| Fitted with | Short-circuit release |
| Functions | Temperature compensated overload protection |
| Class | CLASS 10 A |
| Connection | Push in terminals |
| Connection to SmartWire-DT | No |
| Coordination type | 2 |
| Degree of protection | IP20; NEMA Other |
| Model | IEC/UL starter |
| Mounting method | DIN rail |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 1 |
| Overload release current setting - max | 2.5 A |
| Overload release current setting - min | 1.6 A |
| Overvoltage category | III |
| Pollution degree | 3 |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Suitable for | Also motors with efficiency class IE3 |
| Type | Starter with Bi-Metal release |
| Voltage type | AC |
| Power consumption, sealing, 50 Hz | 1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 230 V |
| Short-circuit release (Irm) - max | 38.8 A |
| With transformer | No |
| Power consumption | 1.4 W |
| Rated operation power at AC-3, 400 V | 0.75 kW |
| Number of auxiliary contacts as normally open contact | 1 |
| Suitable for emergency stop | No |
| Rated operation current Ie | 1.9 A |
| Overload release current setting | 1.6–2.5 A |
| Supporting protocol for LON | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for ASI | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for other bus systems | No |
| External reset possible | No |
| Suitable for rail mounting | Yes |
| Rated control supply voltage AC 50 Hz | 230 V |
| Supporting protocol for SERCOS | No |
| Supporting protocol for INTERBUS-Safety | No |
| Release class | CLASS 10 A |
| With short-circuit release | Yes |
| With fuse | No |
| Type of electrical connection of main circuit | Spring clamp connection |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Voltage type for actuating | AC |
| Type of motor starter | Direct online starter (DOL) |
| Rated operation power at AC-3, 230 V, 3-phase | 0.37 kW |
| Rated operation current at AC-3, 400 V | 2.5 A |
| Ambient temperature, upper operating limit | 55 °C |
| Temperature compensated overload protection | Yes |
| Rated conditional short-circuit current, type 2, 400 V | 50 A |
| Rated conditional short-circuit current, type 2, 230 V | 50 A |
| Coordination class according to IEC 60947-4-3 | Class 2 |
| Country of origin | Germany |