| Manufacturer part number (MPN) | DILM500-S/22(220-240V50/60HZ) |
| EAN / GTIN | 4015082741990 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 274199 |
| Depth | 216 mm |
| Height | 219 mm |
| Width | 160 mm |
| Weight | 8.58 kg |
| Conventional thermal current Ith (1-pole, enclosed) | 1500 A |
| Conventional thermal current Ith (3-pole, enclosed) | 600 A |
| Conventional thermal current Ith at 40°C (3-pole, open) | 800 A |
| Conventional thermal current Ith at 50°C (3-pole, open) | 715 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 682 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 650 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 1625 A |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -40 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -40 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Number of auxiliary contacts (normally closed contacts) | 2 |
| Number of auxiliary contacts (normally open contacts) | 2 |
| Number of contacts (normally closed contacts) | 2 |
| Number of contacts (normally open contacts) | 2 |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 19.33 W |
| Rated operational current for specified heat dissipation (In) | 500 A |
| Static heat dissipation, non-current-dependent Pvs | 3.3 W |
| Inrush current | Max. 30 x Ie (peak) |
| Rated breaking capacity at 1000 V | 950 A |
| Rated breaking capacity at 220/230 V | 5000 A |
| Rated breaking capacity at 380/400 V | 5000 A |
| Rated breaking capacity at 500 V | 5000 A |
| Rated breaking capacity at 660/690 V | 5000 A |
| Rated insulation voltage (Ui) | 1000 V |
| Rated making capacity (cos phi to IEC/EN 60947) | 5500 A |
| Rated operational current (Ie) | 177 A at 690 V (Individual compensation, three-phase capacitors, open); 307 A at up to 525 V (Individual compensation, three-phase capacitors, open) |
| Rated operational current (Ie) at AC-3 |
| 1000 V | 95 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V |
| 240 V | 500 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V |
| 415 V | 500 A |
| Rated operational current (Ie) at AC-3 |
| 440 V | 500 A |
| Rated operational current (Ie) at AC-3 |
| 500 V | 500 A |
| Rated operational current (Ie) at AC-3, 660 V |
| 690 V | 325 A |
| Rated operational current (Ie) at AC-4 |
| Rated operational current (Ie) at AC-4, 220 V, 230 V |
| 240 V | 360 A |
| Rated operational current (Ie) at AC-4 |
| 440 V | 360 A |
| Rated operational current (Ie) at AC-4 |
| 500 V | 360 A |
| Rated operational current (Ie) at AC-4, 660 V |
| 690 V | 260 A |
| Rated operational power at AC-3, 1000 V |
| 50 Hz | 132 kW |
| Rated operational power at AC-3, 240 V |
| 50 Hz | 170 kW |
| Rated operational power at AC-3, 380/400 V |
| 50 Hz | 250 kW |
| Rated operational power at AC-3, 415 V |
| 50 Hz | 290 kW |
| Rated operational power at AC-3, 440 V |
| 50 Hz | 315 kW |
| Rated operational power at AC-3, 500 V |
| 50 Hz | 355 kW |
| Rated operational power at AC-3, 690 V |
| 50 Hz | 300 kW |
| Rated operational power at AC-4, 1000 V |
| Rated operational power at AC-4, 220/230 V |
| 50 Hz | 112 kW |
| Rated operational power at AC-4, 240 V |
| 50 Hz | 122 kW |
| Rated operational power at AC-4, 415 V |
| 50 Hz | 216 kW |
| Rated operational power at AC-4, 440 V |
| 50 Hz | 229 kW |
| Rated operational power at AC-4, 500 V |
| Rated operational power at AC-4, 660/690 V |
| 50 Hz | 240 kW |
| Rated operational voltage (Ue) at AC - max | 1000 V |
| Safe isolation | 1000 V AC, Between coil and contacts, According to EN 61140 |
| Special purpose rating of definite purpose rating | 3900 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 635 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 3120 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 520 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Accessories | Fitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA |
| Application | Contactors for Motors |
| Connection | Screw terminals |
| Degree of protection | IP00 |
| Electromagnetic compatibility | Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression. |
| Fitted with | Suppressor circuit in actuating electronics |
| Lifespan, electrical | 100,000 Operations (at Condensor operation) |
| Lifespan, mechanical | 7,000,000 Operations (AC operated) |
| Operating frequency | 2000 mechanical Operations/h (AC operated); 200 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Resistance | 500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11) |
| Shock resistance | 8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
| Voltage type | AC |
| Drop-out voltage | AC operated: 0.2 x US max - 0.4 x US min |
| AC operated; AC operated | 0.25 x US max - 0.6 x US min, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.85 - 1.1 V AC x Us |
| Power consumption | Control transformer with uk ≤ 10% |
| Power consumption, pick-up |
| 50 Hz | 715 VA, Pull-in power, Coil in a cold state and 1.0 x Us; 645 W, Pull-in power, Coil in a cold state and 1.0 x Us |
| Power consumption, pick-up |
| 60 Hz | 715 VA, Pull-in power, Coil in a cold state and 1.0 x Us; 645 W, Pull-in power, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing |
| 50 Hz | 4 W, Coil in a cold state and 1.0 x Us; 6.8 VA, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing |
| 60 Hz | 4 W, Coil in a cold state and 1.0 x Us; 6.8 VA, Coil in a cold state and 1.0 x Us |
| Rated control supply voltage (Us) at AC |
| 50 Hz - max | 240 V |
| Rated control supply voltage (Us) at AC |
| 50 Hz - min | 220 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - max | 240 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - min | 220 V |
| Switching time (AC operated, make contacts, closing delay) - max | 55 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 50 ms |
| Assigned motor power at 200/208 V, 60 Hz |
| 3-phase | 150 HP |
| Assigned motor power at 230/240 V, 60 Hz |
| 3-phase | 200 HP |
| Assigned motor power at 460/480 V, 60 Hz |
| 3-phase | 400 HP |
| Assigned motor power at 575/600 V, 60 Hz |
| 3-phase | 500 HP |
| Short-circuit current rating (basic rating) | 600 A, max. CB, SCCR (UL/CSA); 30 kA, SCCR (UL/CSA); 800 A, max. Fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 30/100 kA, Fuse, SCCR (UL/CSA); 100 kA, CB, SCCR (UL/CSA); 800/600 A, Class J, max. Fuse, SCCR (UL/CSA); 600 A, max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 600 A, max. CB, SCCR (UL/CSA); 800/600 A, Class J, max. Fuse, SCCR (UL/CSA); 30/100 kA, Fuse, SCCR (UL/CSA); 30 kA, CB, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 1000 V | 250 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 400 V | 630 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 630 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 1000 V | 200 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 500 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 500 A gG/gL |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA); 15 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA); A600, AC operated (UL/CSA) |
| Switching capacity (main contacts, general use) | 550 A, Maximum motor rating (UL/CSA) |
| Screw size | M3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main connections |
| Screwdriver size | 2, Terminal screw, Control circuit cables, Pozidriv screwdriver |
| Terminal capacity (busbar) | 30 mm width, Main connection |
| Terminal capacity (copper band) | Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks |
| Terminal capacity (flexible with cable lug) | 50 - 240 mm² |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid) | 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) | 18 - 14, Control circuit cables; 2/0 - 500 MCM, Main cables |
| Terminal capacity (stranded with cable lug) | 70 - 240 mm² |
| Tightening torque | 1.2 Nm, Screw terminals, Control circuit cables; 24 Nm, Main cable connection screw/bolt |
| Width across flats | 16 mm |