| Manufacturer part number (MPN) | DILM115-22(RDC24) |
| EAN / GTIN | 4015082395810 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 239581 |
| Depth | 175 mm |
| Height | 170 mm |
| Width | 90 mm |
| Weight | 2.31 kg |
| Certifications | UL Category Control No.: NLDX; UL; CE; IEC/EN 60947; IEC/EN 60947-4-1; VDE 0660; UL File No.: E29096; CSA-C22.2 No. 60947-4-1-14; UL 60947-4-1; CSA File No.: 012528; CSA Class No.: 2411-03, 3211-04; CSA |
| Catalog Notes | Contacts according to EN 50012 |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Number of main contacts (normally open contact) | 3 |
| Number of auxiliary contacts (normally closed contacts) | 2 |
| Number of auxiliary contacts (normally open contacts) | 2 |
| Number of contacts (normally closed contacts) | 2 |
| Number of contacts (normally open contacts) | 2 |
| Number of contacts (normally closed) as main contact | 0 |
| Conventional thermal current Ith (1-pole, enclosed) | 285 A |
| Conventional thermal current Ith (3-pole, enclosed) | 115 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 135 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 130 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 325 A |
| Equipment heat dissipation, current-dependent Pvid | 18.9 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 6.3 W |
| Rated operational current for specified heat dissipation (In) | 115 A |
| Static heat dissipation, non-current-dependent Pvs | 1.9 W |
| Rated breaking capacity at 220/230 V | 1150 A |
| Rated breaking capacity at 380/400 V | 1150 A |
| Rated breaking capacity at 500 V | 1150 A |
| Rated breaking capacity at 660/690 V | 1100 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 1610 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 160 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 115 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 115 A |
| Rated operational current (Ie) at AC-3, 440 V | 115 A |
| Rated operational current (Ie) at AC-3, 500 V | 115 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 93 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 55 A |
| Rated operational current (Ie) at AC-4, 440 V | 55 A |
| Rated operational current (Ie) at AC-4, 500 V | 55 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 45 A |
| Rated operational current (Ie) at DC-1, 110 V | 160 A |
| Rated operational current (Ie) at DC-1, 220 V | 90 A |
| Rated operational current (Ie) at DC-1, 60 V | 160 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 40 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 55 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 70 kW |
| Rated operational power at AC-3, 440 V, 50 Hz | 75 kW |
| Rated operational power at AC-3, 500 V, 50 Hz | 85 kW |
| Rated operational power at AC-3, 690 V, 50 Hz | 90 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 17 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 19 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 33 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 35 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 40 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 43 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
| Fitted with | Suppressor circuit in actuating electronics; Mirror contact |
| Number of poles | Three-pole |
| Application | Contactors for Motors |
| Connection | Screw terminals |
| Degree of protection | IP00 |
| Lifespan, mechanical | 10,000,000 Operations (DC operated); 7,000,000 Operations (Coil 50/60 Hz) |
| Operating frequency | 3600 mechanical Operations/h (DC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Residual current | 1 mA (with actuation of A1 - A2 by the electronics with "0" signal) |
| Resistance per pole | 0.6 mΩ |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running; AC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
| Voltage type | DC |
| Arcing time | 15 ms |
| Drop-out voltage | At least smoothed two-phase bridge rectifier or three-phase rectifier; 0.6 - 0.15 x UC, DC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.7 - 1.2 V DC x Uc; 24 - 27 V DC (RDC 24) |
| Power consumption (pick-up) at DC | 149 W |
| Power consumption (sealing) at DC | 1.9 W |
| Rated control supply voltage (Us) at DC - max | 27 V |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Switching time (DC operated, make contacts, closing delay) - max | 35 ms |
| Switching time (DC operated, make contacts, opening delay) - max | 30 ms |
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 10 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 40 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 25 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 50 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 100 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 100 HP |
| Safe isolation | 690 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140 |
| Short-circuit current rating (basic rating) | 10 kA, 600 A max. fuse, SCCR (UL/CSA); 10 kA, 600 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA); 65 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V | 250 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 250 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 250 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 250 A gG/gL |
| Special purpose rating of definite purpose rating | 115 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 690 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Special purpose rating of elevator control | 92 A, 200 V 60 Hz 3-ph, (UL/CSA); 40 HP, 240 V 60 Hz 3-ph, (UL/CSA); 75 HP, 480 V 60 Hz 3-ph, (UL/CSA); 96 A, 480 V 60 Hz 3-ph, (UL/CSA); 30 HP, 200 V 60 Hz 3-ph, (UL/CSA); 99 A, 600 V 60 Hz 3-ph, (UL/CSA); 104 A, 240 V 60 Hz 3-ph, (UL/CSA); 100 HP, 600 V 60 Hz 3-ph, (UL/CSA) |
| Special purpose rating of refrigeration control (CSA only) | 84 A, FLA 600 V 60 Hz 3phase; (CSA); 540 A, LRA 600 V 60 Hz 3phase; (CSA); 84 A, FLA 480 V 60 Hz 3phase; (CSA); 540 A, LRA 480 V 60 Hz 3phase; (CSA) |
| Special purpose rating of resistance air heating | 160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of tungsten incandescent lamps | 160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of ballast electrical discharge lamps | 160 A (600V 60Hz 3phase, 347V 60Hz 1phase); 160 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA); 15 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA); A600, AC operated (UL/CSA) |
| Switching capacity (main contacts, general use) | 180 A, Maximum motor rating (UL/CSA) |
| Screw size | 5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables; M3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main cables |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver; 2, Terminal screw, Control circuit cables, Pozidriv screwdriver |
| Stripping length (control circuit cable) | 10 mm |
| Stripping length (main cable) | 24 mm |
| Terminal capacity (copper band) | 2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (stranded) | 2 x (16 - 70) mm², Main cables; 1 x (16 - 95) mm², Main cables |
| Tightening torque | 14 Nm, Screw terminals, Main cables; 1.2 Nm, Screw terminals, Control circuit cables |
| Terminal capacity (flexible with ferrule) | 1 x (10 - 95) mm², Main cables; 1 x (0.75 - 4) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 2 x (10 - 70) mm², Main cables |
| Terminal capacity (solid/stranded AWG) | 18 - 14, Control circuit cables; Single 8…3/0, double 8…2/0, Main cables |