cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILM750/22(RA110)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM750/22(RA110)  ·  HS 8536.90
Contactor DILM750/22(RA110)

Eaton DILM750/22(RA110) Contactor, 380 V 400 V 400 kW, 2 N/O, 2 NC, RA 110: 48 - 110 V 40 - 60 Hz/48 - 110 V DC.

Technical Specifications

Manufacturer part number (MPN)DILM750/22(RA110)
EAN / GTIN4015082082215
HS code8536.90
Sales unitpcs
Eaton catalogue number208221
Depth232 mm
Height296 mm
Width250 mm
Weight16.52 kg
CertificationsUL File No.: E29096; UL; CSA-C22.2 No. 60947-4-1-14; IEC/EN 60947; UL 60947-4-1; CE; VDE 0660; CSA Class No.: 3211-04; CSA File No.: 012528; IEC/EN 60947-4-1; UL Category Control No.: NLDX; CSA
Catalog NotesContacts according to EN 50012 Also tested according to AC-3e up to 690 V. Also suitable for motors with efficiency class IE3. Conventional thermal current Ith of main contacts (1-pole, open) at 60°
Conventional thermal current Ith at 40°C (3-pole, open)1102 A
Conventional thermal current Ith at 50°C (3-pole, open)986 A
Conventional thermal current Ith at 55°C (3-pole, open)940 A
Conventional thermal current Ith at 60°C (3-pole, open)900 A
Conventional thermal current Ith of main contacts (1-pole, open)2250 A
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-40 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-40 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Number of auxiliary contacts (normally closed contacts)2
Number of auxiliary contacts (normally open contacts)2
Number of contacts (normally closed contacts)2
Number of contacts (normally open contacts)2
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid18 W
Rated operational current for specified heat dissipation (In)750 A
Static heat dissipation, non-current-dependent Pvs6.5 W
Inrush currentMax. 30 x Ie (peak)
Rated breaking capacity at 1000 V5800 A
Rated breaking capacity at 220/230 V8200 A
Rated breaking capacity at 380/400 V8200 A
Rated breaking capacity at 500 V8200 A
Rated breaking capacity at 660/690 V8200 A
Rated insulation voltage (Ui)1000 V
Rated making capacity (cos phi to IEC/EN 60947)9840 A
Rated operational current (Ie)265 A at 690 V (Individual compensation, three-phase capacitors, open); 463 A at up to 525 V (Individual compensation, three-phase capacitors, open)
Rated operational current (Ie) at AC-3
1000 V580 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V750 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V750 A
Rated operational current (Ie) at AC-3
440 V750 A
Rated operational current (Ie) at AC-3
500 V750 A
Rated operational current (Ie) at AC-3, 660 V
690 V750 A
Rated operational current (Ie) at AC-4
1000 V464 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V576 A
Rated operational current (Ie) at AC-4
440 V576 A
Rated operational current (Ie) at AC-4
500 V576 A
Rated operational current (Ie) at AC-4, 660 V
690 V576 A
Rated operational power at AC-3, 1000 V
50 Hz800 kW
Rated operational power at AC-3, 240 V
50 Hz260 kW
Rated operational power at AC-3, 380/400 V
50 Hz400 kW
Rated operational power at AC-3, 415 V
50 Hz455 kW
Rated operational power at AC-3, 440 V
50 Hz480 kW
Rated operational power at AC-3, 500 V
50 Hz550 kW
Rated operational power at AC-3, 690 V
50 Hz720 kW
Rated operational power at AC-4, 1000 V
50 Hz678 kW
Rated operational power at AC-4, 220/230 V
50 Hz181 kW
Rated operational power at AC-4, 240 V
50 Hz200 kW
Rated operational power at AC-4, 415 V
50 Hz346 kW
Rated operational power at AC-4, 440 V
50 Hz367 kW
Rated operational power at AC-4, 500 V
50 Hz417 kW
Rated operational power at AC-4, 660/690 V
50 Hz556 kW
Rated operational voltage (Ue) at AC - max1000 V
Safe isolation1000 V AC, Between coil and contacts, According to EN 61140
Special purpose rating of definite purpose rating4800 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 800 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 4800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 800 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
AccessoriesFitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Electromagnetic compatibilityDesigned for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
Fitted withSuppressor circuit in actuating electronics
Lifespan, electrical100,000 Operations (at Condensor operation)
Lifespan, mechanical5,000,000 Operations (DC operated); 5,000,000 Operations (AC operated)
Operating frequency200 Operations/h; 1000 mechanical Operations/h (AC operated); 1000 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11)
Shock resistance10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Signal level5 V - 15 V, PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2), Magnet systems
Utilization categoryAC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage typeAC/DC
Drop-out voltage0.2 x US max - 0.6 x US min
DC operated; AC operated0.2 x US max - 0.6 x US min, AC operated
Duty factor100 %
Pick-up voltage0.7 - 1.15 V AC x Us; 0.7 - 1.15 V DC x Us
Power consumptionControl transformer with uk ≤ 7%
Power consumption, pick-up
50 Hz1100 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, pick-up
60 Hz1100 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, sealing
50 Hz26.4 VA, Coil in a cold state and 1.0 x Us; 10.3 W, Coil in a cold state and 1.0 x Us
Power consumption, sealing
60 Hz26.4 VA, Coil in a cold state and 1.0 x Us; 10.3 W, Coil in a cold state and 1.0 x Us
Rated control supply voltage (Us) at AC
50 Hz - max110 V
Rated control supply voltage (Us) at AC
50 Hz - min48 V
Rated control supply voltage (Us) at AC
60 Hz - max110 V
Rated control supply voltage (Us) at AC
60 Hz - min48 V
Rated control supply voltage (Us) at DC - max110 V
Rated control supply voltage (Us) at DC - min48 V
Switching time (AC operated, make contacts, closing delay) - max70 ms
Switching time (AC operated, make contacts, opening delay) - max110 ms
Assigned motor power at 200/208 V, 60 Hz
3-phase250 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase300 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase600 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase700 HP
Short-circuit current rating (basic rating)42 kA, SCCR (UL/CSA); 2000 A, max. Fuse, SCCR (UL/CSA); 1200 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)85 kA, CB, SCCR (UL/CSA); 2000 A, max. Fuse, SCCR (UL/CSA); 1200 A, max. CB, SCCR (UL/CSA); 85 kA, Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)85 kA, Fuse, SCCR (UL/CSA); 2000 A, max. Fuse, SCCR (UL/CSA); 1200 A, max. CB, SCCR (UL/CSA); 85 kA, CB, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 1000 V800 A gG/gL
Short-circuit protection rating (type 1 coordination) at 400 V1200 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V1200 A gG/gL
Short-circuit protection rating (type 2 coordination) at 1000 V630 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V630 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V630 A gG/gL
Switching capacity (auxiliary contacts, general use)1 A, 250 V DC, (UL/CSA); 15 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600, AC operated (UL/CSA); P300, DC operated (UL/CSA)
Switching capacity (main contacts, general use)1102 A, Maximum motor rating (UL/CSA)
Screw sizeM12, Terminal screw, Main connections; M3.5, Terminal screw, Control circuit cables
Screwdriver size2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Terminal capacity (busbar)60 mm width, Main connection
Terminal capacity (copper band)Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks
Terminal capacity (flexible with cable lug)50 - 240 mm²
Terminal capacity (flexible with ferrule)1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid)1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)18 - 14, Control circuit cables; 2/0 - 500 MCM, Main cables
Terminal capacity (stranded with cable lug)70 - 240 mm²
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 35 Nm, Main cable connection screw/bolt
Width across flats18 mm

Properties

MOQ1

Cross-References

Attached Documents