cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILM250/22(RDC48)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM250/22(RDC48)  ·  HS 8536.90
Contactor DILM250/22(RDC48)

Eaton DILM250/22(RDC48) Contactor, 380 V 400 V 132 kW, 2 N/O, 2 NC, RDC 48: 24 - 48 V DC, DC operated, Screw connection.

Technical Specifications

Manufacturer part number (MPN)DILM250/22(RDC48)
EAN / GTIN4015082081997
HS code8536.90
Sales unitpcs
Eaton catalogue number208199
Depth208 mm
Height189 mm
Width140 mm
Weight7.226 kg
Conventional thermal current Ith (1-pole, enclosed)750 A
Conventional thermal current Ith (3-pole, enclosed)300 A
Conventional thermal current Ith at 40°C (3-pole, open)430 A
Conventional thermal current Ith at 50°C (3-pole, open)380 A
Conventional thermal current Ith at 55°C (3-pole, open)365 A
Conventional thermal current Ith at 60°C (3-pole, open)350 A
Conventional thermal current Ith of main contacts (1-pole, open)875 A
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-40 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-40 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Number of auxiliary contacts (normally closed contacts)2
Number of auxiliary contacts (normally open contacts)2
Number of contacts (normally closed contacts)2
Number of contacts (normally open contacts)2
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid9.33 W
Rated operational current for specified heat dissipation (In)250 A
Static heat dissipation, non-current-dependent Pvs4.6 W
Inrush currentMax. 30 x Ie (peak)
Rated breaking capacity at 1000 V760 A
Rated breaking capacity at 220/230 V2500 A
Rated breaking capacity at 380/400 V2500 A
Rated breaking capacity at 500 V2500 A
Rated breaking capacity at 660/690 V2500 A
Rated insulation voltage (Ui)1000 V
Rated making capacity (cos phi to IEC/EN 60947)3000 A
Rated operational current (Ie)220 A at up to 525 V (Individual compensation, three-phase capacitors, open); 133 A at 690 V (Individual compensation, three-phase capacitors, open)
Rated operational current (Ie) at AC-3
1000 V76 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V250 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V250 A
Rated operational current (Ie) at AC-3
440 V250 A
Rated operational current (Ie) at AC-3
500 V250 A
Rated operational current (Ie) at AC-3, 660 V
690 V185 A
Rated operational current (Ie) at AC-4
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V200 A
Rated operational current (Ie) at AC-4
440 V200 A
Rated operational current (Ie) at AC-4
500 V200 A
Rated operational current (Ie) at AC-4, 660 V
690 V150 A
Rated operational power at AC-3, 1000 V
50 Hz108 kW
Rated operational power at AC-3, 240 V
50 Hz85 kW
Rated operational power at AC-3, 380/400 V
50 Hz132 kW
Rated operational power at AC-3, 415 V
50 Hz143 kW
Rated operational power at AC-3, 440 V
50 Hz152 kW
Rated operational power at AC-3, 500 V
50 Hz173 kW
Rated operational power at AC-3, 690 V
50 Hz170 kW
Rated operational power at AC-4, 1000 V
Rated operational power at AC-4, 220/230 V
50 Hz62 kW
Rated operational power at AC-4, 240 V
50 Hz68 kW
Rated operational power at AC-4, 415 V
50 Hz117 kW
Rated operational power at AC-4, 440 V
50 Hz125 kW
Rated operational power at AC-4, 500 V
50 Hz138 kW
Rated operational power at AC-4, 660/690 V
50 Hz137 kW
Rated operational voltage (Ue) at AC - max1000 V
Safe isolation500 V AC, Between coil and contacts, According to EN 61140; 500 V AC, Between the contacts, According to EN 61140
Special purpose rating of definite purpose rating250 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 2050 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 300 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 1800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
AccessoriesFitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Electromagnetic compatibilityDesigned for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
Fitted withSuppressor circuit in actuating electronics
Lifespan, electrical100,000 Operations (at Condensor operation)
Lifespan, mechanical10,000,000 Operations (DC operated)
Operating frequency3000 mechanical Operations/h (DC operated); 200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11)
Shock resistance8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Signal level5 V - 15 V, PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2), Magnet systems
Utilization categoryAC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeDC
Drop-out voltageDC operated: 0.2 x US max - 0.6 US min
DC operated; DC operated0.15 x US min - 0.6 US max, DC operated
Duty factor100 %
Pick-up voltage0.7 - 1.15 V DC x Us
Power consumptionControl transformer with uk ≤ 6%
Power consumption (pick-up) at DC380 VA
Power consumption (sealing) at DC4.6 W
Power consumption, pick-up
50 Hz240 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, pick-up
60 Hz240 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, sealing
50 Hz4.6 W, Coil in a cold state and 1.0 x Us
Power consumption, sealing
60 Hz4.6 W, Coil in a cold state and 1.0 x Us
Rated control supply voltage (Us) at DC - max48 V
Rated control supply voltage (Us) at DC - min24 V
Switching time (AC operated, make contacts, closing delay) - max100 ms
Switching time (AC operated, make contacts, opening delay) - max110 ms
Assigned motor power at 200/208 V, 60 Hz
3-phase75 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase100 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase200 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase250 HP
Short-circuit current rating (basic rating)700 A, max. Fuse, SCCR (UL/CSA); 600 A, max. CB, SCCR (UL/CSA); 18 kA, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)18 kA, Fuse, SCCR (UL/CSA); 65 kA, CB, SCCR (UL/CSA); 250 A, max. CB, SCCR (UL/CSA); 700 A, Class L, max. Fuse, SCCR (UL/CSA); 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA); 18/100 kA, Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)18 kA, CB, SCCR (UL/CSA); 600 A, max. CB, SCCR (UL/CSA); 18 kA, Fuse, SCCR (UL/CSA); 700 A, Class J, max. Fuse, SCCR (UL/CSA); 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA); 18/100 kA, Fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 1000 V200 A gG/gL
Short-circuit protection rating (type 1 coordination) at 400 V400 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V400 A gG/gL
Short-circuit protection rating (type 2 coordination) at 1000 V160 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V315 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V315 A gG/gL
Switching capacity (auxiliary contacts, general use)1 A, 250 V DC, (UL/CSA); 15 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600, AC operated (UL/CSA); P300, DC operated (UL/CSA)
Switching capacity (main contacts, general use)350 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main connections
Screwdriver size2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Terminal capacity (busbar)25 mm width, Main connection
Terminal capacity (copper band)Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks
Terminal capacity (flexible with cable lug)50 - 240 mm²
Terminal capacity (flexible with ferrule)1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid)1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)2/0 - 500 MCM, Main cables; 18 - 14, Control circuit cables
Terminal capacity (stranded with cable lug)70 - 240 mm²
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 24 Nm, Main cable connection screw/bolt
Width across flats16 mm

Properties

MOQ1

Cross-References

Attached Documents