Contactor 400V/AC3 160KW/300A (DILM300A-S/22(110-120V50/60HZ))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM300A-S/22(110-120V50/60HZ)  ·  HS 8536.90
Contactor 400V/AC3 160KW/300A (DILM300A-S/22(110-120V50/60HZ))

Eaton DILM300A-S/22(110-120V50/60HZ) DILM300A-S/22(110-120V50/60HZ).

Technical Specifications

Manufacturer part number (MPN)DILM300A-S/22(110-120V50/60HZ)
EAN / GTIN4015081363360
HS code8536.90
Sales unitpcs
Eaton catalogue number139558
Depth208 mm
Height189 mm
Width140 mm
Weight7.1 kg
Catalog NotesContacts according to EN 50012 EN 45545 - Fire protection on railway vehicles: Fire protection class of all plastics according to UL94: V-0 / plastic weight in total: 1.872 kg Conventional thermal current Ith of main contacts (1-pole, open) at 60°
Conventional thermal current Ith (1-pole, enclosed)788 A
Conventional thermal current Ith (3-pole, enclosed)315 A
Conventional thermal current Ith at 40°C (3-pole, open)490 A
Conventional thermal current Ith at 50°C (3-pole, open)438 A
Conventional thermal current Ith at 55°C (3-pole, open)418 A
Conventional thermal current Ith at 60°C (3-pole, open)400 A
Conventional thermal current Ith of main contacts (1-pole, open)1000 A
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-40 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-40 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Number of auxiliary contacts (normally closed contacts)2
Number of auxiliary contacts (normally open contacts)2
Number of contacts (normally closed contacts)2
Number of contacts (normally open contacts)2
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid7 W
Rated operational current for specified heat dissipation (In)300 A
Static heat dissipation, non-current-dependent Pvs3.3 W
Inrush currentMax. 30 x Ie (peak)
Rated breaking capacity at 1000 V950 A
Rated breaking capacity at 220/230 V3000 A
Rated breaking capacity at 380/400 V3000 A
Rated breaking capacity at 500 V3000 A
Rated breaking capacity at 660/690 V3000 A
Rated insulation voltage (Ui)1000 V
Rated making capacity (cos phi to IEC/EN 60947)3000 A
Rated operational current (Ie)307 A at up to 525 V (Individual compensation, three-phase capacitors, open); 177 A at 690 V (Individual compensation, three-phase capacitors, open)
Rated operational current (Ie) at AC-3
1000 V95 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V300 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V300 A
Rated operational current (Ie) at AC-3
440 V300 A
Rated operational current (Ie) at AC-3
500 V300 A
Rated operational current (Ie) at AC-3, 660 V
690 V185 A
Rated operational current (Ie) at AC-4
1000 V76 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V240 A
Rated operational current (Ie) at AC-4
440 V240 A
Rated operational current (Ie) at AC-4
500 V240 A
Rated operational current (Ie) at AC-4, 660 V
690 V150 A
Rated operational power at AC-3, 1000 V
50 Hz132 kW
Rated operational power at AC-3, 240 V
50 Hz100 kW
Rated operational power at AC-3, 380/400 V
50 Hz160 kW
Rated operational power at AC-3, 415 V
50 Hz175 kW
Rated operational power at AC-3, 440 V
50 Hz185 kW
Rated operational power at AC-3, 500 V
50 Hz210 kW
Rated operational power at AC-3, 690 V
50 Hz170 kW
Rated operational power at AC-4, 1000 V
50 Hz108 kW
Rated operational power at AC-4, 220/230 V
50 Hz75 kW
Rated operational power at AC-4, 240 V
50 Hz82 kW
Rated operational power at AC-4, 415 V
50 Hz142 kW
Rated operational power at AC-4, 440 V
50 Hz150 kW
Rated operational power at AC-4, 500 V
Rated operational power at AC-4, 660/690 V
50 Hz137 kW
Rated operational voltage (Ue) at AC - max1000 V
Safe isolation1000 V AC, Between coil and contacts, According to EN 61140
Special purpose rating of definite purpose rating1800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 300 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 2160 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 360 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
AccessoriesFitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Electromagnetic compatibilityDesigned for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
Fitted withSuppressor circuit in actuating electronics
Lifespan, electrical100,000 Operations (at Condensor operation)
Lifespan, mechanical10,000,000 Operations (AC operated)
Operating frequency3000 mechanical Operations/h (AC operated); 200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11)
Shock resistance10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Utilization categoryAC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Voltage typeAC
Drop-out voltageAC operated: 0.2 x US max - 0.4 x US min
AC operated; AC operated0.25 x US max - 0.6 x US min, AC operated
Duty factor100 %
Pick-up voltage0.85 - 1.1 V AC x Us
Power consumptionControl transformer with uk ≤ 10%
Power consumption, pick-up
50 Hz325 W, Pull-in power, Coil in a cold state and 1.0 x Us; 360 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, pick-up
60 Hz325 W, Pull-in power, Coil in a cold state and 1.0 x Us; 360 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, sealing
50 Hz4.2 W, Coil in a cold state and 1.0 x Us; 6.7 VA, Coil in a cold state and 1.0 x Us
Power consumption, sealing
60 Hz6.7 VA, Coil in a cold state and 1.0 x Us; 4.2 W, Coil in a cold state and 1.0 x Us
Rated control supply voltage (Us) at AC
50 Hz - max120 V
Rated control supply voltage (Us) at AC
50 Hz - min110 V
Rated control supply voltage (Us) at AC
60 Hz - max120 V
Rated control supply voltage (Us) at AC
60 Hz - min110 V
Switching time (AC operated, make contacts, closing delay) - max55 ms
Switching time (AC operated, make contacts, opening delay) - max40 ms
Assigned motor power at 200/208 V, 60 Hz
3-phase100 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase125 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase250 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase300 HP
Short-circuit current rating (basic rating)18 kA, SCCR (UL/CSA); 600 A, max. CB, SCCR (UL/CSA); 700 A, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)18 kA, Fuse, SCCR (UL/CSA); 250 A, max. CB, SCCR (UL/CSA); 700 A, Class L, max. Fuse, SCCR (UL/CSA); 65 kA, CB, SCCR (UL/CSA); 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA); 18/100 kA, Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)700 A, Class J, max. Fuse, SCCR (UL/CSA); 18 kA, Fuse, SCCR (UL/CSA); 18 kA, CB, SCCR (UL/CSA); 600 A, max. CB, SCCR (UL/CSA); 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA); 18/100 kA, Fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 1000 V200 A gG/gL
Short-circuit protection rating (type 1 coordination) at 400 V400 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V400 A gG/gL
Short-circuit protection rating (type 2 coordination) at 1000 V160 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V400 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V315 A gG/gL
Switching capacity (auxiliary contacts, general use)15 A, 600 V AC, (UL/CSA); 1 A, 250 V DC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)P300, DC operated (UL/CSA); A600, AC operated (UL/CSA)
Switching capacity (main contacts, general use)350 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main connections
Screwdriver size2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Terminal capacity (busbar)25 mm width, Main connection
Terminal capacity (copper band)Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks
Terminal capacity (flexible with cable lug)50 - 240 mm²
Terminal capacity (flexible with ferrule)2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid)1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)2/0 - 500 MCM, Main cables; 18 - 14, Control circuit cables
Terminal capacity (stranded with cable lug)70 - 240 mm²
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 24 Nm, Main cable connection screw/bolt
Width across flats16 mm