Contactor DILMP45-01(RDC24)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILMP45-01(RDC24)  ·  HS 8536.90
Contactor DILMP45-01(RDC24)

Eaton DILMP45-01(RDC24) Contactor, 4-pole, 45 A, 1 NC, 24 V DC, DC operated.

Technical Specifications

Manufacturer part number (MPN)DILMP45-01(RDC24)
EAN / GTIN4015081170432
HS code8536.90
Sales unitpcs
Eaton catalogue number118916
Depth97 mm
Height85 mm
Width58 mm
Weight0.596 kg
CertificationsCSA Class No.: 2411-03
3211-04; IEC/EN 60947-4-1; UL File No.E29096; CSA File No.: 012528; CE; IEC/EN 60947; VDE 0660; CSA; UL Category Control No.: NLDX; CSA-C22.2 No. 60947-4-1-14; UL; UL 60947-4-1
Catalog NotesAlso tested according to AC-3e.
Shock resistance5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-3
Connection to SmartWire-DTIn conjunction with DIL-SWD SmartWire DT contactor module; Yes
Number of main contacts (normally open contact)4
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed contacts)1
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)105 A
Conventional thermal current Ith (3-pole, enclosed)36 A
Conventional thermal current Ith at 55°C (3-pole, open)40 A
Conventional thermal current Ith at 60°C (3-pole, open)39 A
Conventional thermal current Ith of main contacts (1-pole, open)117 A
Equipment heat dissipation, current-dependent Pvid13.2 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid4.4 W
Rated operational current for specified heat dissipation (In)45 A
Static heat dissipation, non-current-dependent Pvs0.9 W
Rated breaking capacity at 220/230 V250 A
Rated breaking capacity at 380/400 V250 A
Rated breaking capacity at 500 V250 A
Rated breaking capacity at 660/690 V144 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)350 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V45 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V25 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V25 A
Rated operational current (Ie) at AC-3
440 V25 A
Rated operational current (Ie) at AC-3
500 V25 A
Rated operational current (Ie) at AC-3, 660 V
690 V15 A
Rated operational current (Ie) at DC-1
110 V45 A
Rated operational current (Ie) at DC-1
220 V45 A
Rated operational current (Ie) at DC-1
60 V45 A
Rated operational power at AC-1, 220/230 V
50 Hz16 kW
Rated operational power at AC-1, 240 V
50 Hz18 kW
Rated operational power at AC-1, 380/400 V
50 Hz28 kW
Rated operational power at AC-1, 415 V
50 Hz31 kW
Rated operational power at AC-1, 440 V
50 Hz33 kW
Rated operational power at AC-1, 500 V
50 Hz37 kW
Rated operational power at AC-1, 690 V
50 Hz49 kW
Rated operational power at AC-3, 240 V
50 Hz8.5 kW
Rated operational power at AC-3, 380/400 V
50 Hz11 kW
Rated operational power at AC-3, 415 V
50 Hz14.5 kW
Rated operational power at AC-3, 440 V
50 Hz15.5 kW
Rated operational power at AC-3, 500 V
50 Hz17.5 kW
Rated operational power at AC-3, 690 V
50 Hz14 kW
Rated operational voltage (Ue) at AC - max690 V
Interference immunityAccording to EN 60947-1
Fitted withMirror contact; Suppressor circuit in actuating electronics
Number of polesFour-pole
ApplicationContactors for 4 pole electric consumers
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (AC operated); 10,000,000 Operations (DC operated)
Operating frequency5000 mechanical Operations/h (DC operated); 5000 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Residual current1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Resistance per pole2.7 mΩ
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeDC
Arcing time10 ms
Drop-out voltage0.2 - 0.6 x UC, DC operated
Duty factor100 %
Pick-up voltage0.7 - 1.2 V DC x Uc; 0.85 - 1.1 V AC/DC x Us
Power consumption (pick-up) at DC12 W
Power consumption (sealing) at DC0.9 W
Rated control supply voltage (Us) at DC - max27 V
Rated control supply voltage (Us) at DC - min24 V
Switching time (DC operated, make contacts, closing delay) - max47 ms
Switching time (DC operated, make contacts, opening delay) - max30 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase2 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase7.5 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase5 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase10 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase15 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase20 HP
Safe isolation440 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)5 kA, SCCR (UL/CSA); 125 A, max. Fuse, SCCR (UL/CSA); 125 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)50/32 A, max. CB, SCCR (UL/CSA); 10/100 kA, Fuse, SCCR (UL/CSA); 125/70 A, Class J, max. Fuse, SCCR (UL/CSA); 10/65 kA, CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)10/100 kA, Fuse, SCCR (UL/CSA); 125/100 A, Class J, max. Fuse, SCCR (UL/CSA); 10/22 kA, CB, SCCR (UL/CSA); 50/32 A, max. CB, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V100 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V50 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V35 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V35 A gG/gL
Special purpose rating of definite purpose rating25 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 150 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Special purpose rating of elevator control15 HP, 600 V 60 Hz 3-ph, (UL/CSA); 3 HP, 200 V 60 Hz 3-ph, (UL/CSA); 17 A, 600 V 60 Hz 3-ph, (UL/CSA); 5 HP, 240 V 60 Hz 3-ph, (UL/CSA); 10 HP, 480 V 60 Hz 3-ph, (UL/CSA); 11 A, 200 V 60 Hz 3-ph, (UL/CSA); 15.2 A, 240 V 60 Hz 3-ph, (UL/CSA); 14 A, 480 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)240 A, LRA 480 V 60 Hz 3phase; (CSA); 30 A, FLA 600 V 60 Hz 3phase; (CSA); 40 A, FLA 480 V 60 Hz 3phase; (CSA); 180 A, LRA 600 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps40 A (480V 60Hz 3phase, 277V 60Hz 1phase); 40 A (600V 60Hz 3phase, 347V 60Hz 1phase)
Switching capacity (auxiliary contacts, general use)1 A, 250 V DC, (UL/CSA); 10 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)P300, DC operated (UL/CSA); A600, AC operated (UL/CSA)
Switching capacity (main contacts, general use)40 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M5, Terminal screw, Main cables
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)10 mm
Terminal capacity (flexible)1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm²
Terminal capacity (solid)1 x (0.75 - 16) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 4) mm², Control circuit cables; 2 x (0.75 - 10) mm², Main cables; 1 x (0.75 - 2.5) mm²
Terminal capacity (stranded)1 x 16 mm², Main cables
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 3 Nm, Screw terminals, Main cables
Terminal capacity (flexible with ferrule)1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm²
Terminal capacity (solid/stranded AWG)18 - 6, Main cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References