cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Contactor DILMP200(RAC120)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILMP200(RAC120)  ·  HS 8536.90
Contactor DILMP200(RAC120)

Eaton DILMP200(RAC120) Contactor, 4-pole, 200 A, RAC 120: 100 - 120 V 50/60 Hz, AC operated.

Technical Specifications

Manufacturer part number (MPN)DILMP200(RAC120)
EAN / GTIN4015081094899
HS code8536.90
Sales unitpcs
Eaton catalogue number109923
Depth160 mm
Height170 mm
Width122 mm
Weight2.73 kg
CertificationsCSA; UL; CE; CSA Class No.: 2411-03
3211-04; UL Category Control No.NLDX; UL File No.: E29096; CSA File No.: 012528; IEC/EN 60947; UL 60947-4-1; VDE 0660; CSA-C22.2 No. 60947-4-1-14; IEC/EN 60947-4-1
Catalog NotesContacts according to EN 50012
Shock resistance5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-3; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)4
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)464 A
Conventional thermal current Ith (3-pole, enclosed)160 A
Conventional thermal current Ith at 55°C (3-pole, open)180 A
Conventional thermal current Ith at 60°C (3-pole, open)172 A
Conventional thermal current Ith of main contacts (1-pole, open)516 A
Equipment heat dissipation, current-dependent Pvid57 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid19 W
Rated operational current for specified heat dissipation (In)200 A
Static heat dissipation, non-current-dependent Pvs2.3 W
Rated breaking capacity at 220/230 V1150 A
Rated breaking capacity at 380/400 V1150 A
Rated breaking capacity at 500 V1150 A
Rated breaking capacity at 660/690 V800 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)1800 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V200 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V115 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V115 A
Rated operational current (Ie) at AC-3
440 V115 A
Rated operational current (Ie) at AC-3
500 V115 A
Rated operational current (Ie) at AC-3, 660 V
690 V93 A
Rated operational current (Ie) at DC-1
110 V200 A
Rated operational current (Ie) at DC-1
220 V200 A
Rated operational current (Ie) at DC-1
60 V200 A
Rated operational power at AC-1, 220/230 V
50 Hz72 kW
Rated operational power at AC-1, 240 V
50 Hz79 kW
Rated operational power at AC-1, 380/400 V
50 Hz125 kW
Rated operational power at AC-1, 415 V
50 Hz137 kW
Rated operational power at AC-1, 440 V
50 Hz145 kW
Rated operational power at AC-1, 500 V
50 Hz165 kW
Rated operational power at AC-1, 690 V
50 Hz217 kW
Rated operational power at AC-3, 240 V
50 Hz40 kW
Rated operational power at AC-3, 380/400 V
50 Hz55 kW
Rated operational power at AC-3, 415 V
50 Hz70 kW
Rated operational power at AC-3, 440 V
50 Hz75 kW
Rated operational power at AC-3, 500 V
50 Hz85 kW
Rated operational power at AC-3, 690 V
50 Hz90 kW
Rated operational voltage (Ue) at AC - max690 V
Interference immunityAccording to EN 60947-1
Fitted withSuppressor circuit in actuating electronics
Number of polesFour-pole
ApplicationContactors for 4 pole electric consumers
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (DC operated); 10,000,000 Operations (AC operated)
Operating frequency3600 mechanical Operations/h (AC operated); 3600 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Residual current1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Resistance per pole0.6 mΩ
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeAC
Drop-out voltageAC operated: 0.6 - 0.25 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.15 V AC/DC x Us; 0.8 - 1.15 V AC x Uc
Power consumption, pick-up
50 Hz180 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up
60 Hz150 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 180 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing
50 Hz2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing
60 Hz2.3 W, Dual-frequency coil in a cold state and 1.0 x Us; 3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC
50 Hz - max120 V
Rated control supply voltage (Us) at AC
50 Hz - min100 V
Rated control supply voltage (Us) at AC
60 Hz - max120 V
Rated control supply voltage (Us) at AC
60 Hz - min100 V
Switching time (AC operated, make contacts, closing delay) - max33 ms
Switching time (AC operated, make contacts, closing delay) - min28 ms
Switching time (AC operated, make contacts, opening delay) - max41 ms
Switching time (AC operated, make contacts, opening delay) - min35 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase10 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase40 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase30 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase60 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase125 HP
Assigned motor power at 575/600 V, 60 Hz
Safe isolation440 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)10 kA, 600 A max. fuse, SCCR (UL/CSA); 10 kA, 600 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA); 65 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V200 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V200 A gG/gL
Special purpose rating of elevator control30 HP, 200 V 60 Hz 3-ph, (UL/CSA); 92 A, 200 V 60 Hz 3-ph, (UL/CSA); 99 A, 600 V 60 Hz 3-ph, (UL/CSA); 104 A, 240 V 60 Hz 3-ph, (UL/CSA); 96 A, 480 V 60 Hz 3-ph, (UL/CSA); 40 HP, 240 V 60 Hz 3-ph, (UL/CSA); 75 HP, 480 V 60 Hz 3-ph, (UL/CSA); 100 HP, 600 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)90 A, FLA 480 V 60 Hz 3phase; (CSA); 540 A, LRA 480 V 60 Hz 3phase; (CSA); 540 A, LRA 600 V 60 Hz 3phase; (CSA); 90 A, FLA 600 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps160 A (600V 60Hz 3phase, 347V 60Hz 1phase); 160 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Switching capacity (main contacts, general use)180 A, Maximum motor rating (UL/CSA)
Screw sizeM10, Terminal screw, Main cables; M3.5, Terminal screw, Control circuit cables; 5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
Screwdriver size2, Terminal screw, Control circuit cables, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)15 mm
Terminal capacity (copper band)2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (flexible)1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm²
Terminal capacity (solid)2 x (0.75 - 4) mm², Control circuit cables; 1 x (0.75 - 4) mm², Control circuit cables; 1 x (0.75 - 2.5) mm²
Terminal capacity (stranded)1 x (16 - 120) mm², Main cables; 2 x (16 - 95) mm², Main cables
Tightening torque14 Nm, Screw terminals, Main cables; 1.2 Nm, Screw terminals, Control circuit cables
Terminal capacity (flexible with ferrule)1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm²
Terminal capacity (solid/stranded AWG)8 - 3/0, Main cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References

Attached Documents