cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILEEM-01-G(24VDC)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILEEM-01-G(24VDC)  ·  HS 8536.90
Contactor DILEEM-01-G(24VDC)

Eaton DILEEM-01-G(24VDC) Contactor, 24 V DC, 3 poles, 400V, 3 kW, Contacts N/C = Normally closed= 1 NC.

Technical Specifications

Manufacturer part number (MPN)DILEEM-01-G(24VDC)
EAN / GTIN4015080516507
HS code8536.90
Sales unitpcs
Package quantity5 pcs
Eaton catalogue number051650
Depth54 mm
Height58 mm
Width45 mm
Weight0.206 kg
CertificationsUL; VDE 0660; UL 508; CSA File No.: 012528; CSA-C22.2 No. 14-05; UL Category Control No.: NLDX; CSA Class No.: 3211-04; IEC/EN 60947; CE; IEC/EN 60947-4-1; UL File No.: E29096; CSA
Catalog NotesAlso tested according to AC-3e.
Ambient operating temperature - max50 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Control circuit reliability< 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)0
Conventional thermal current Ith (1-pole, enclosed)40 A
Conventional thermal current Ith (3-pole, enclosed)16 A
Conventional thermal current Ith at 55°C (3-pole, open)19 A
Conventional thermal current Ith of auxiliary contacts (1-pole, open)10 A
Conventional thermal current Ith of main contacts (1-pole, open)50 A
Equipment heat dissipation, current-dependent Pvid0.6 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid0.2 W
Rated operational current for specified heat dissipation (In)6.6 A
Static heat dissipation, non-current-dependent Pvs2.3 W
Rated breaking capacity at 220/230 V90 A
Rated breaking capacity at 380/400 V90 A
Rated breaking capacity at 500 V64 A
Rated breaking capacity at 660/690 V42 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 440 V (cos phi to IEC/EN 60947)110 A
Rated operational current (Ie)2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series); 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series); 2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series); 1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V22 A
Rated operational current (Ie) at AC-15, 220 V, 230 V
240 V6 A
Rated operational current (Ie) at AC-15, 380 V, 400 V
415 V3 A
Rated operational current (Ie) at AC-15
500 V1.5 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V6.6 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V6.6 A
Rated operational current (Ie) at AC-3
440 V6.6 A
Rated operational current (Ie) at AC-3
500 V5 A
Rated operational current (Ie) at AC-3, 660 V
690 V3.5 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V5 A
Rated operational current (Ie) at AC-4
440 V5 A
Rated operational current (Ie) at AC-4
500 V3.7 A
Rated operational current (Ie) at AC-4, 660 V
690 V2.9 A
Rated operational current (Ie) at DC-1
110 V20 A
Rated operational current (Ie) at DC-1
12 V20 A
Rated operational current (Ie) at DC-1
220 V20 A
Rated operational current (Ie) at DC-1
24 V20 A
Rated operational current (Ie) at DC-1
60 V20 A
Rated operational power at AC-3, 240 V
50 Hz1.8 kW
Rated operational power at AC-3, 380/400 V
50 Hz3 kW
Rated operational power at AC-3, 415 V
50 Hz3.1 kW
Rated operational power at AC-4, 220/230 V
50 Hz1.1 kW
Rated operational power at AC-4, 240 V
50 Hz1.3 kW
Rated operational power at AC-4, 415 V
50 Hz2.3 kW
Rated operational power at AC-4, 440 V
50 Hz2.4 kW
Rated operational power at AC-4, 500 V
50 Hz2.2 kW
Rated operational power at AC-4, 660/690 V
Rated operational voltage (Ue) at AC - max690 V
Safe isolation300 V AC, Between the contacts, According to EN 61140; 300 V AC, Between coil and auxiliary contacts, According to EN 61140; 300 V AC, Between auxiliary contacts, According to EN 61140; 300 V AC, Between coil and contacts, According to EN 61140
FeaturesPositive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module
Fitted withAuxiliary contact
Number of polesThree-pole
ApplicationMini Contactors for Motors and Resistive Loads
Degree of protectionIP20
Lifespan, mechanical20,000,000 Operations; 150,000 Operations (at 240 V, DC
L/R = 50 ms2 contacts in series 0.5 A); 200,000 Operations (at 240 V, AC-15)
Mounting positionAs required (except vertical with terminals A1/A2 at the bottom)
Operating frequency9000 mechanical Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Suitable forAlso motors with efficiency class IE3
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeDC
Arcing time12 ms at 690 V AC
Changeover time40 - 50 ms
Duty factor100 %
Pick-up voltage0.8 - 1.1 V DC x Uc
Power consumption2.3 VA/W at DC (Pick-up/Sealing power); Smoothed DC voltage or three-phase bridge rectifier
Rated control supply voltage (Us) at DC - max24 V
Rated control supply voltage (Us) at DC - min24 V
Switching time (DC operated, make contacts, closing delay) - max35 ms
Switching time (DC operated, make contacts, closing delay) - min26 ms
Switching time (DC operated, make contacts, opening delay) - max25 ms
Switching time (DC operated, make contacts, opening delay) - min15 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase0.25 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase1.5 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase1 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase2 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase3 HP
Assigned motor power at 575/600 V, 60 Hz
Short-circuit current rating (basic rating)5 kA, SCCR (UL/CSA); 45 A, max. Fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 500 V20 A gG/gL
Short-circuit protection rating (type 2 coordination) at 500 V10 A gG/gL
Switching capacity (auxiliary contacts, general use)10 A, 600 V AC, (UL/CSA); 0.5 A, 250 V DC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600, AC operated (UL/CSA); P300, DC operated (UL/CSA)
Switching capacity (main contacts, general use)15 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Stripping length (main cable)8 mm
Terminal capacity (flexible with ferrule)1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm²
Terminal capacity (solid)2 x (0.75 - 2.5) mm²; 1 x (0.75 - 2.5) mm²
Terminal capacity (solid/stranded AWG)18 - 14
Tightening torque1.2 Nm, Screw terminals

Properties

MOQ1

Cross-References

Attached Documents