cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Time relay, Multi-function

Eaton · Control & Automation · Relays & Timers · Ireland · eaton.com
Part Number
ETR4-69-W  ·  HS 8536.90
Time relay, Multi-function

Eaton ETR4-69-W Time relay, 1W, 0.05s-100h, multifunction, 400VAC.

Technical Specifications

Manufacturer part number (MPN)ETR4-69-W
EAN / GTIN4015080318873
HS code8536.90
Sales unitpcs
Eaton catalogue number031887
Depth103 mm
Height83 mm
Width23 mm
Weight0.109 kg
CertificationsVDE 0435; IEC/EN 61000-4-3; Standard IEC/EN 61812; IEC/EN 61000-4-2
Ambient operating temperature - max60 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max45 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-45 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid1.4 W
Rated operational current for specified heat dissipation (In)6 A
Static heat dissipation, non-current-dependent Pvs0.5 W
Conventional thermal current Ith of auxiliary contacts (1-pole, open)6 A
Mains voltage tolerance400 V AC (at 50/60 Hz)
Nominal current3 A
Rated breaking capacity3 A at AC-15 (cos ϕ = 0.3 220 V); 3 A at AC-14 (cos ϕ = 0.3 440 V); 1.1 x Iₑ (DC-11 L/R - 40 ms)
Rated insulation voltage (Ui)600 V
Rated making capacity1.1 x Iₑ (DC-11 L/R - 40 ms); 48 A (AC-14 cos ϕ = 0.3 400 V); 50 A (AC-15 cos ϕ = 0.3 220 V)
Rated operational current (Ie)3 A at AC-14, 440 V; 3 A at AC-14, 380 V 400 V 415 V; 1.5 A at DC-11, 24 V; 3 A at AC-15, 380 V 400 V 415 V; 3 A at AC-15, 220 V 230 V 240 V; 1.2 A at DC-11, L/R max. 50 ms
Rated operational voltage (Ue) at AC - max440 V
Safe isolation250 V AC, Between coil and auxiliary contacts, According to EN 61140; 250 V AC, Between auxiliary contacts, According to EN 61140
Short-circuit protection ratingMax. 6 A gG/gL, Fuse, Short-circuit rating without welding, Contacts; Max. 6 A gG/gL, fuse, without welding, Contacts
Air discharge8 kV
Burst impulse1 kV, Signal cable; According to IEC/EN 61000-4-4; 2 kV, Supply cable
Contact discharge6 kV
Electromagnetic fields3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3); 1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3); 10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference10 V (according to IEC/EN 61000-4-6)
Radio interference classClass B (EN 55011, conducted); Class B (EN 55011, radiated)
Surge rating2 kV, symmetrical, power pulses (Surge), EMC; 4 kV, asymmetrical, power pulses (Surge), EMC; According to IEC/EN 61000-4-5, power pulses (Surge), EMC
Electric connection typeScrew connection
Degree of protectionTerminals: IP20; IP20
Lifespan, mechanical30,000,000 Operations (DC operated); 30,000,000 Operations (AC operated)
Mounting positionAs required
Number of contacts (change-over contacts)1
Overvoltage categoryIII
Pollution degree2
Product categoryETR4 timing relays
Rated impulse withstand voltage (Uimp)6000 V AC
Shock resistance4 g, Make contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forDIN rail (top hat rail) mounting
Terminal capacity2 x (0.5 - 1.5) mm², solid; 1 x (0.5 - 2.5) mm², solid; 1 x (0.5 - 2.5) mm², flexible with ferrule; 1 x (20 - 14) AWG, solid or stranded; 2 x (0.5 - 1.5) mm², flexible with ferrule
Time range - max360000 s
Time range - min0.05 s
TypeTimer relay
Voltage typeAC
Command time50 ms, AC
Contact changeover time4 ms
Duty factor100 %
Operating frequency4000 Operations/h
Pick-up voltage0.85 - 1.1 V AC x Uc
Power consumption0.5 VA at AC (Sealing power); 0.5 VA at AC (Pick-up power)
Rated control supply voltage (Us) at AC, 50 Hz - max400 V
Rated control supply voltage (Us) at AC, 50 Hz - min400 V
Rated control supply voltage (Us) at AC, 60 Hz - max400 V
Rated control supply voltage (Us) at AC, 60 Hz - min400 V
Recovery time70 ms (after 100 % time delay)
Repetition accuracy≤ 0.5 % (deviation)

Properties

MOQ1

Cross-References

Attached Documents