| Manufacturer part number (MPN) | EMR6-F500-G-1 |
| EAN / GTIN | 4015081788255 |
| Sales unit | pcs |
| Eaton catalogue number | 184789 |
| Depth | 103.7 mm |
| Height | 85.6 mm |
| Width | 22.5 mm |
| Weight | 0.16 kg |
| Certifications | IEC/EN 60255-6 |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 85 °C |
| Ambient operating temperature - min | -20 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30 |
| Air discharge | Air/contact discharge, according to IEC/EN 61000-4-2, level 3 |
| Burst impulse | According to IEC/EN 61000-4-4, level 3 |
| Electromagnetic compatibility | According to IEC/EN 60947-6-2 |
| Immunity to line-conducted interference | Level 3 (according to IEC/EN 61000-4-6) |
| Immunity to radiation | Level 3 (according to IEC/EN 61000-4-3) |
| Surge rating | According to IEC/EN 61000-4-5 Level 4 |
| Electric connection type | Screw connection |
| Features | Fixed response delay |
| Functions | Phase failure detection; Monitoring of three-phase networks |
| Monitoring function | Phase failure; Phase sequence monitoring; Phase sequence |
| Voltage measurement - max | 500 V |
| Voltage measurement - min | 200 V |
| Degree of protection | Enclosure: IP50; Terminals: IP20 |
| LED indicator | Status indication of energized output relay: Yellow LED; Status indication of Phase failure: Red, solid light; Status indication of Phase sequence fault: Red, flashing light |
| Lifespan, mechanical | 30,000,000 Operations |
| Mounting position | As required |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | EMR Measuring and monitoring relays |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Shock resistance | Class 2 |
| Type | Phase sequence relay |
| Voltage type | AC |
| Measuring cycle | 500 ms |
| Monitoring voltage | 200 - 500 V AC, 50/60 Hz (per phase); 200 - 500 V AC |
| Temperature error | 0.06 %/°C, Measuring circuits |
| Duty factor | 100 %, Power supply |
| Power consumption | 11 VA |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 500 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 200 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 500 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 200 V |
| Rated frequency - max | 60 Hz |
| Rated frequency - min | 50 Hz |
| Supply voltage | 200 - 500 V AC, 50/60 Hz |
| Voltage tolerance | 0.85 x Uc; 1.1 x Uc |
| Lifespan, electrical | 300,000 Operation (at 230 V, AC-12, 4 A) |
| Number of contacts (change-over contacts) | 2 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 0 |
| Rated operational current (Ie) | 2 A at DC-13, 24 V; 4 A at AC-12, 230 V; 4 A at DC-12, 24 V; 3 A at AC-15, 230 V |
| Rated operational voltage (Ue) at AC - max | 250 V |
| Short-circuit protection rating | Max. 10 A Fast/gL, Fuse, Relay output contacts |
| Connection type | Snap fixing, top-hat rail IEC/EN 60715 |
| Screwdriver size | 5.5 x 0.8 mm, Terminal screw |
| Terminal capacity | 2 x 2.5 mm², solid; 2 x 2.5 mm², (2 x 14 AWG), flexible with ferrule |
| Tightening torque | Min. 0.5 Nm, Screw terminals; 0.8 Nm, Screw terminals |
| Timing cycle | 0.5 % Error within supply voltage (Measuring circuits) |
| Operating voltage AC 50 Hz | 200–500 V |
| Operating voltage AC 60 Hz | 200–500 V |
| External power supply required | No |
| Supply voltage AC 50 Hz | 200–500 V |
| Supply voltage AC 60 Hz | 200–500 V |
| Rated switch current | 4 A |
| Type of electric connection | Screw connection |
| With detachable clamps | No |
| Rated control supply voltage AC 50 Hz | 200–500 V |
| Rated control supply voltage AC 60 Hz | 200–500 V |
| Voltage type for actuating | AC |
| Phase sequence monitoring | Yes |
| Phase failure detection | Yes |
| Function under voltage detection | No |
| Function overvoltage detection | No |
| Phase imbalance monitoring | No |
| Voltage measuring range | 200–500 V |
| Number of contacts as change-over contact | 2 |
| Country of origin | Germany |
| Min. adjustable delay-on energization time | 0 s |
| Min. adjustable off-delay time | 0 s |