Phase monitoring relay (EMR6-AWM580-H-1)

Eaton · Control & Automation · Relays & Timers · Ireland · eaton.com
Part Number
EMR6-AWM580-H-1  ·  HS 8536.49
Phase monitoring relay (EMR6-AWM580-H-1)

Technical Specifications

Manufacturer part number (MPN)EMR6-AWM580-H-1
EAN / GTIN4015081788019
Sales unitpcs
Eaton catalogue number184765
Depth107 mm
Height85.6 mm
Width45 mm
Weight0.16 kg
CertificationsCSA; UL; GL; IEC; CCC
Ambient operating temperature - max60 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30
Air dischargeAir/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulseAccording to IEC/EN 61000-4-4, level 3
Electromagnetic compatibilityAccording to IEC/EN 60947-6-2
Immunity to line-conducted interferenceLevel 3 (according to IEC/EN 61000-4-6)
Immunity to radiationLevel 3 (according to IEC/EN 61000-4-3)
Surge ratingAccording to IEC/EN 61000-4-5 Level 4
Electric connection typeScrew connection
FeaturesAutomatic phase sequence correction (can be disabled); Imbalance threshold values adjustable 2 - 25 % of mean value of phase voltages
FunctionsMulti-functional; Phase failure detection; Under voltage detection; Over voltage detection
Monitoring functionOvervoltage; Phase imbalance monitoring; Phase sequence monitoring; Phase sequence; Undervoltage; Phase failure; Imbalance; Phase sequence (can be deactivated)
Voltage measurement - max580 V
Voltage measurement - min350 V
Degree of protectionTerminals: IP20; Enclosure: IP50
Lifespan, mechanical30,000,000 Operations
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product categoryEMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)4000 V AC
Shock resistanceClass 2
Suitable forThree-phase networks
TypePhase monitoring relay
Voltage typeAC
Hysteresis0 - 5 %
Measuring cycle100 ms
Monitoring voltage350 - 580 V AC, 50/60 Hz (per phase)
Temperature error0.06 %/°C, Measuring circuits
Duty factor100 %, Power supply
Power consumption41 VA
Rated control supply voltage (Us) at AC, 50 Hz - max580 V
Rated control supply voltage (Us) at AC, 50 Hz - min350 V
Rated control supply voltage (Us) at AC, 60 Hz - max580 V
Rated control supply voltage (Us) at AC, 60 Hz - min350 V
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Supply voltage350 - 580 V AC, 50/60 Hz
Voltage tolerance0.85 x Uc; 1.1 x Uc
Lifespan, electrical100,000 Operation (at 230 V, AC-12, 4 A)
Number of contacts (change-over contacts)2
Number of contacts (normally closed contacts)0
Number of contacts (normally open contacts)0
Rated operational current (Ie)2 A at DC-13, 24 V; 4 A at AC-12, 230 V; 4 A at DC-12, 24 V; 3 A at AC-15, 230 V
Rated operational voltage (Ue) at AC - max250 V
Short-circuit protection ratingMax. 10 A Fast/gL, Fuse, Relay output contacts
Connection typeSnap fixing, top-hat rail IEC/EN 60715
Screwdriver size5.5 x 0.8 mm, Terminal screw
Terminal capacity2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule; 1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid
Tightening torqueMin. 0.6 Nm, Screw terminals; 0.8 Nm, Screw terminals
Delay timeStart-up delay fixed Ts = 250 ms; Adjustable tripping delay Tv = 0 - 30 s
Timing cycle0.5 %, Time error within supply voltage; 0.5 % Error within supply voltage (Measuring circuits); 0.06 %/°C, Time error within temperature range
Operating voltage AC 50 Hz350–580 V
Operating voltage AC 60 Hz350–580 V
External power supply requiredNo
Supply voltage AC 50 Hz350–580 V
Supply voltage AC 60 Hz350–580 V
Rated switch current4 A
Type of electric connectionScrew connection
With detachable clampsNo
Rated control supply voltage AC 50 Hz350–580 V
Rated control supply voltage AC 60 Hz350–580 V
Voltage type for actuatingAC
Phase sequence monitoringYes
Phase failure detectionYes
Function under voltage detectionYes
Function overvoltage detectionYes
Phase imbalance monitoringYes
Voltage measuring range350–580 V
Min. adjustable delay-on energization time0.1 s
Max. permitted delay-on energization time30 s
Min. adjustable off-delay time0.1 s
Max. permitted off-delay time30 s
Number of contacts as change-over contact2
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents