| Manufacturer part number (MPN) | EMR6-N100-N-1 EAN / GTIN: 4015081787944 Sales unit: pcs Eaton catalogue number: 184758 Depth: 103.7 mm Height: 85.6 mm Width: 22.5 mm Weight: 0.153 kg Certifications: CSA; RMRS; EN 61557; RCM; IEC/EN 60255-6; UL; GL; DNV; EAC Ambient operating temperature - max: 60 °C Ambient storage temperature - max: 85 °C Ambient operating temperature - min: -25 °C Climatic proofing: Damp heat, cyclic, to IEC 60068-2-30 Air discharge: Air/contact discharge, according to IEC/EN 61000-4-2, level 3 Burst impulse: According to IEC/EN 61000-4-4, level 3 Electromagnetic compatibility: According to IEC/EN 60947-6-2 Immunity to line-conducted interference: Level 3 (according to IEC/EN 61000-4-6) Immunity to radiation: Level 3 (according to IEC/EN 61000-4-3) Surge rating: According to IEC/EN 61000-4-5 Level 4 Electric connection type: Screw connection Functions: Response value sensitivity adjustable Monitoring function: Mixture ratio of conductive liquids; Fill level of conductive liquids Degree of protection: Terminals: IP20; Enclosure: IP50 Lifespan, mechanical: 10,000,000 Operations Mounting position: As required Overvoltage category: III Pollution degree: 3 Product category: EMR Measuring and monitoring relays Rated impulse withstand voltage (Uimp): 4000 V AC Shock resistance: Class 2 Type: Level monitoring relay Voltage type: AC Connection: minimum level, MIN, Sensor inputs, Measuring circuits; Maximum level, MAX, Sensor inputs, Measuring circuits; Earth reference sensor, C, Sensor inputs |
| Measuring circuits Sensor voltage | 6 VAC Duty factor: 100 % |
| Power supply Power consumption | 2.6 VA Rated control supply voltage (Us) at AC, 50 Hz - max: 240 V Rated control supply voltage (Us) at AC, 50 Hz - min: 110 V Rated control supply voltage (Us) at AC, 60 Hz - max: 240 V Rated control supply voltage (Us) at AC, 60 Hz - min: 110 V Rated frequency - max: 60 Hz Rated frequency - min: 50 Hz Supply voltage: 110 - 130 V AC, 50/60 Hz; 220 - 240 V AC, 50/60 Hz Voltage tolerance: 1.1 x Uc; 0.85 x Uc Lifespan, electrical: 100,000 Operation (at 230 V, AC-12, 4 A) Number of contacts (change-over contacts): 1 Number of contacts (normally closed contacts): 0 Number of contacts (normally open contacts): 0 Rated operational current (Ie): 5 A at AC-12, 230 V; 3 A at AC-15, 230 V Rated operational voltage (Ue) at AC - max: 300 V Short-circuit protection rating: Max. 10 A Fast/gL, Fuse, Relay output contacts Connection type: Snap fixing, top-hat rail IEC/EN 60715 Screwdriver size: 5.5 x 0.8 mm |
| Terminal screw Terminal capacity | 1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid; 2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule Tightening torque: Min. 0.5 Nm, Screw terminals; 0.8 Nm |
| Screw terminals Adjustment range | 5 - 100 kΩ, Sensitivity Operating voltage AC 50 Hz: 110–240 V Operating voltage AC 60 Hz: 110–240 V Supply voltage AC 50 Hz: 110–240 V Supply voltage AC 60 Hz: 110–240 V Supply voltage DC: 110–240 V Rated switch current: 4 A Type of electric connection: Screw connection Rated control supply voltage AC 50 Hz: 110–240 V Rated control supply voltage AC 60 Hz: 110–240 V Voltage type for actuating: AC With detachable clamps: No Number of inputs for electrodes: 3 Response value sensitivity adjustable: Yes Number of contacts as change-over contact: 1 Physical measurement principle: Conductive Cascadable: No Country of origin: Germany Min. adjustable operate delay time: 0 s Min. adjustable off-delay time: 0 s |