| Manufacturer part number (MPN) | 197910 |
| EAN / GTIN | 4015081954292 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 197910 |
| Depth | 216 mm |
| Height | 237 mm |
| Width | 160 mm |
| Weight | 8.85 kg |
| Conventional thermal current Ith (3-pole, enclosed) | 800 A |
| Conventional thermal current Ith at 40°C (3-pole, open) | 1050 A |
| Conventional thermal current Ith at 50°C (3-pole, open) | 940 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 895 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 855 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 2138 A |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 70 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -40 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -40 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Number of auxiliary contacts (normally closed contacts) | 2 |
| Number of auxiliary contacts (normally open contacts) | 2 |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Rated operational current for specified heat dissipation (In) | 800 A |
| Static heat dissipation, non-current-dependent Pvs | 6.4 W |
| Rated breaking capacity at 1000 V | 1575 A |
| Rated breaking capacity at 220/230 V | 4800 A |
| Rated breaking capacity at 380/400 V | 4800 A |
| Rated breaking capacity at 500 V | 4800 A |
| Rated breaking capacity at 660/690 V | 2000 A |
| Rated insulation voltage (Ui) | 1000 V |
| Rated making capacity up to 440 V (cos phi to IEC/EN 60947) | 6000 A |
| Rated operational voltage (Ue) at AC - max | 1000 V |
| Safe isolation | 1000 V AC, Between coil and contacts, According to EN 61140 |
| Accessories | Fitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA |
| Application | Mains contactors for resistive loads from 1000 A |
| Connection | Screw terminals |
| Degree of protection | IP00 |
| Electromagnetic compatibility | Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression. |
| Fitted with | Suppressor circuit in actuating electronics |
| Lifespan, mechanical | 3,000,000 Operations (AC operated); 3,000,000 Operations (DC operated) |
| Operating frequency | 1000 mechanical Operations/h (DC operated); 1000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Rated impulse withstand voltage (Uimp) | 12000 V |
| Resistance | 500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11) |
| Shock resistance | 8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Signal level | 5 V - 15 V, PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2), Magnet systems |
| Utilization category | AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
| Voltage type | DC |
| Duty factor | 100 % |
| Pick-up voltage | 0.7 - 1.15 V DC x Us |
| Power consumption | Control transformer with uk ≤ 7% |
| Power consumption (pick-up) at DC | 450 VA |
| Power consumption (sealing) at DC | 6.4 W |
| Power consumption, pick-up, 50 Hz | 495 VA, Pull-in power, Coil in a cold state and 1.0 x Us |
| Power consumption, pick-up, 60 Hz | 495 VA, Pull-in power, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 50 Hz | 6.4 W, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 60 Hz | 6.4 W, Coil in a cold state and 1.0 x Us |
| Rated control supply voltage (Us) at DC - max | 48 V |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Switching time (AC operated, make contacts, closing delay) - max | 80 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 110 ms |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA); 10 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | A600, AC operated (UL/CSA); P300, DC operated (UL/CSA) |
| Switching capacity (main contacts, general use) | 830 A, Maximum motor rating (UL/CSA) |
| Screw size | M10, Terminal screw; M3.5, Terminal screw |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver |
| Stripping length (control circuit cable) | 10 mm |
| Terminal capacity (busbar) | 50 mm width, Main connection |
| Terminal capacity (flexible with cable lug) | 50 - 240 mm² |
| Terminal capacity (flexible with ferrule) | 2 x (0.75 - 2.5) mm²; 1 x (0.75 - 2.5) mm² |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 14 |
| Terminal capacity (stranded with cable lug) | 70 - 240 mm² |
| Tightening torque | 1.2 Nm, Screw terminals; 24 Nm, Main cable connection screw/bolt |
| Width across flats | 16 mm |