cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton Contactor 3-Pole 37 kW 24 V 50/60 Hz (DILMT80(24V50/60HZ))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILMT80(24V50/60HZ)  ·  HS 8536.90
Eaton Contactor 3-Pole 37 kW 24 V 50/60 Hz (DILMT80(24V50/60HZ))

Eaton DILMT80(24V50/60HZ) contactor, 3-pole, 380 V / 400 V: 37 kW, 24 V 50/60 Hz, AC operated, screw terminals.

Technical Specifications

Manufacturer part number (MPN)DILMT80(24V50/60HZ)
EAN / GTIN4015081945016
HS code8536.90
Sales unitpcs
Eaton catalogue number197622
Depth124.5 mm
Height111.5 mm
Width72 mm
Weight1.26 kg
CertificationsEN 60335-1; GB14048; IEC/EN 60947
Catalog NotesNot suitable for motors with efficiency class IE3.
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Rated breaking capacity at 380/400 V640 A
Rated insulation voltage (Ui)690 V
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V110 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V80 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V80 A
Rated operational power at AC-3, 380/400 V, 50 Hz37 kW
Rated operational power at AC-3, 690 V, 50 Hz37 kW
Rated operational voltage (Ue) at AC - max690 V
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionScrew terminals
Connection to SmartWire-DTNo
Degree of protectionIP20
Frame sizeFS4
Lifespan, electrical900,000 Operations (at 400V, AC-3)
Lifespan, mechanical5,000,000 Operations (AC operated)
Operating frequency3600 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
Rated impulse withstand voltage (Uimp)6000 V AC
Used withDILMT95-XHI11-SR and DILT-XHI01(10)
Utilization categoryAC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage typeAC
Pick-up voltage0.85 - 1.1 V AC x Uc
Power consumption, pick-up, 50 Hz0 VA, Dual-frequency coil in a cold state and 1.0 x Us; 350 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up, 60 Hz0 VA, Dual-frequency coil in a cold state and 1.0 x Us; 350 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing, 50 Hz8 W, Dual-frequency coil in a cold state and 1.0 x Us; 0 W, Dual-frequency coil in a cold state and 1.0 x Us; 9 VA, Coil in a cold state and 1.0 x Us
Power consumption, sealing, 60 Hz0 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 8 W, Dual-frequency coil in a cold state and 1.0 x Us; 26 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 0 W, Dual-frequency coil in a cold state and 1.0 x Us
Rated control supply voltage (Us) at AC, 50 Hz - max24 V
Rated control supply voltage (Us) at AC, 50 Hz - min24 V
Rated control supply voltage (Us) at AC, 60 Hz - max24 V
Rated control supply voltage (Us) at AC, 60 Hz - min24 V
Screw sizeM3.5, Terminal screw; M8, Terminal screw; 4 mm AF, Hexagon socket-head spanner, Terminal screw
Screwdriver size2, Terminal screw, Pozidriv screwdriver
Stripping length (main cable)16 mm
Terminal capacity (solid)1 x (6 - 50) mm², Main cables; 2 x (0.75 - 2.5) mm²; 2 x (6 - 25) mm², Main cables; 1 x (0.75 - 2.5) mm²
Terminal capacity (stranded)1 x (6 - 50) mm²; 2 x (6 - 25) mm², Main cables
Tightening torque6 Nm, Screw terminals; 1.2 Nm, Screw terminals

Properties

MOQ1

Cross-References

Attached Documents