Eaton Contactor 3-Pole 18.5 kW, 230 V AC (DILMT40(230V50HZ/240V60HZ))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILMT40(230V50HZ/240V60HZ)  ·  HS 8536.90
Eaton Contactor 3-Pole 18.5 kW, 230 V AC (DILMT40(230V50HZ/240V60HZ))

Eaton DILMT40(230V50HZ/240V60HZ) contactor, 3-pole, 380 V 400 V: 18.5 kW, 230 V 50 Hz, 240 V 60 Hz, AC operated, screw terminals.

Technical Specifications

Manufacturer part number (MPN)DILMT40(230V50HZ/240V60HZ)
EAN / GTIN4015081912230
HS code8536.90
Sales unitpcs
Eaton catalogue number191000
Depth108.1 mm
Height103.6 mm
Width55 mm
Weight0.776 kg
CertificationsEN 60335-1; GB14048; IEC/EN 60947
Catalog NotesNot suitable for motors with efficiency class IE3.
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Rated breaking capacity at 380/400 V320 A
Rated insulation voltage (Ui)690 V
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V60 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V40 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V40 A
Rated operational power at AC-3, 380/400 V, 50 Hz18.5 kW
Rated operational power at AC-3, 690 V, 50 Hz22 kW
Rated operational voltage (Ue) at AC - max690 V
Number of polesThree-pole
ApplicationContactors for Motors
Connection to SmartWire-DTNo
Degree of protectionIP20
Frame sizeFS3
Lifespan, mechanical5,000,000 Operations (AC operated)
Operating frequency3600 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
Rated impulse withstand voltage (Uimp)6000 V AC
Used withDILMT95-XHI11-SR and DILT-XHI01(10)
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Voltage typeAC
Pick-up voltage0.85 - 1.1 V AC x Uc
Power consumption, pick-up, 50 Hz0 VA, Dual-frequency coil in a cold state and 1.0 x Us; 220 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up, 60 Hz0 VA, Dual-frequency coil in a cold state and 1.0 x Us; 220 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing, 50 Hz22 W, Dual-frequency coil in a cold state and 1.0 x Us; 0 W, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing, 60 Hz5 W, Dual-frequency coil in a cold state and 1.0 x Us; 0 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 0 W, Dual-frequency coil in a cold state and 1.0 x Us; 20 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max230 V
Rated control supply voltage (Us) at AC, 50 Hz - min230 V
Rated control supply voltage (Us) at AC, 60 Hz - max240 V
Rated control supply voltage (Us) at AC, 60 Hz - min240 V
Screw sizeM6, Terminal screw; M3.5, Terminal screw
Screwdriver size2, Terminal screw, Pozidriv screwdriver; 2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Stripping length (control circuit cable)14 mm
Stripping length (main cable)14 mm
Terminal capacity (solid)2 x (0.75 - 2.5) mm²; 1 x (0.75 - 2.5) mm²; 1 x (2.5 - 25) mm², Main cables; 2 x (2.5 - 16) mm², Main cables
Terminal capacity (stranded)1 x (2.5 - 25) mm²; 2 x (2.5 - 16) mm²
Tightening torque1.2 Nm, Screw terminals; 2.5 Nm

Properties

MOQ1

Cross-References

Attached Documents