Variable-frequency drive 690V 200 kW (SPX200A1-5A4N1)

Eaton · Drives & Controllers · Variable Frequency Drives · Ireland · eaton.com
Part Number
SPX200A1-5A4N1  ·  HS 8504.40
Variable-frequency drive 690V 200 kW (SPX200A1-5A4N1)

Technical Specifications

Manufacturer part number (MPN)SPX200A1-5A4N1
EAN / GTIN4015081230020
HS code8504.40
Sales unitpcs
Eaton catalogue number125396
Depth602 mm
Height2018 mm
Width595 mm
Weight275 kg
AltitudeMax. 3000 m; Max. 1000 m; Above 1000 m with 1 % performance reduction per 100 m
Ambient operating temperature - max50 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-10 °C
Ambient operating temperature at 150% overload - max50 °C
Ambient operating temperature at 150% overload - min-10 °C
Ambient storage temperature - min-40 °C
Climatic proofing< 95 % relative humidity, no condensation, no corrosion, no dripping water
Communication interfacePROFIBUS-DP; LonWorks, optional; Modbus-TCP, optional; BACnet/IP, optional; CANopen®, optional; DeviceNet, optional; BACnet MS/TP, optional; EtherCAT, optional; Ethernet IP, optional; Modbus-RTU, optional; PROFINET, optional
Connection to SmartWire-DTNo
ProtocolTCP/IP; PROFIBUS; Other bus systems; DeviceNet; Data-Highway; CAN; LON
Number of inputs (analog)2
Number of inputs (digital)6
Number of outputs (analog)1
Number of outputs (digital)1
Number of relay outputs2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
Rated control voltage (Uc)24 V DC (external, max. 250 mA)
Equipment heat dissipation, current-dependent Pvid5000 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid0 W
Rated operational current for specified heat dissipation (In)208 A
Static heat dissipation, non-current-dependent Pvs0 W
Degree of protectionNEMA 1; IP21
Electromagnetic compatibility1st and 2nd environments (according to EN 61800-3)
Fitted withOLED display; IGBT inverter; Radio interference suppression filter; Control unit; DC link choke; Internal DC link; PC connection
Frame sizeFR10
Functions4-quadrant operation possible
Mounting positionVertical
Product CategoryVariable frequency drives
ProtectionFinger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Radio interference classC2
C3depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Suitable forBranch circuits, (UL/CSA)
Mains voltage - max690 V
Mains voltage - min525 V
Operating modeSensorless vector control (SLV); U/f control; Optional: Vector control with feedback (CLV)
Output frequency - max320 Hz
Output frequency - min0 Hz
Output voltage (U2)600 V AC, 3-phase; 690 V AC, 3-phase
Rated control supply voltage10 V DC (Us, max. 10 mA)
Rated frequency - max66 Hz
Rated frequency - min45 Hz
Rated operational current (Ie) at 110% overload261 A
Rated operational current (Ie) at 150% overload208 A
Rated operational power at 690 V, 50 Hz
3-phase200 kW
Rated operational power at 690 V, 50 Hz, 3-phase
110% overload250 kW
Rated operational voltage690 V AC, 3-phase; 600 V AC, 3-phase
Resolution0.01 Hz (Frequency resolution, setpoint value)
Supply frequency50/60 Hz
Switching frequency1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
System configuration typeAC supply systems with earthed center point
Voltage rating - max690 VAC
Assigned motor current IM at 690 V, 50 Hz
110% overload253 A
Assigned motor current IM at 690 V, 50 Hz
150% overload202 A
Assigned motor current IM at 690 V, 60 Hz
110% overload251 A
Assigned motor current IM at 690 V, 60 Hz
150% overload167 A
Assigned motor power at 690 V, 60 Hz
3-phase200 HP
Assigned motor power at 690 V, 60 Hz, 3-phase
110 % overload300 HP

Properties

MOQ1

Cross-References