cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

WALL-Mount Cabinet H400 B600 D200 (CS-46/200)

Eaton · Enclosures · Industrial Enclosures · Ireland · eaton.com
Part Number
CS-46/200  ·  HS 8538.10
WALL-Mount Cabinet H400 B600 D200 (CS-46/200)

Eaton CS-46/200 Enclosure with mounting plate, IP66. RAL7035. EN62217.

Technical Specifications

Manufacturer part number (MPN)CS-46/200
EAN / GTIN4015081112449
Sales unitpcs
Eaton catalogue number111685
Depth200 mm
Height400 mm
Width600 mm
Weight13.73 kg
CompliancesUL 508A; CSA-C22.2 No.14; IEC/EN 62208; CE marking; UL CSA09 (may be provided with metal sub-panel, no back mounted components are allowed between sub-panel and the back sheet metal enclosure); RoHS conform
CertificationsIEC/EN 62208; UL (Category Control Number NITW); UL (File No. E336299); UL CSA08 (request filed); In accordance with Directive 2015/863/EU of the European Parliament and Council
Catalog NotesFoamed polyurethane sealing throughout. Impact resistance category IK10 to EN 62262. Sheet steel mounting plate. Bottom plate with foamed gasket. Single door, door stop on the right, door opening angle 120°. Door hinge pins with quick chang
FeaturesWall build in; Pole fastening
Fitted withMounting plate; Including M6 threaded welded studs for earth conductor connections in the door:; Cover; Door
FunctionsFloor standing enclosure
RAL-number7035
Suitable forMetrical mounting
Used withIndustrial control panels
ColorLight gray (RAL 7035); Gray
TypeWall-mounting housing CS Wall-mounting housing with mounting plate
Ambient operating temperature details-25 °C - 40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30
Cover/door angle120° door opening angle
Cover/door profile2 door profiles
Cover/door typeStandard closure 3 mm double-ward key (door interlock); Can be converted by user; Door hinges on the right, can be converted by user; Door hinges right
Design typeCanted and seam welded, including two M6 threaded bolts for earth conductor connections inside the enclosure.
Flange plate dimensions172 mm x 432 mm
Installation siteIndoor installation
Installation typeFloor standing wall model
Load capacity (door)25 kg
Load capacity (mounting plate)500 kg payload, when brackets fitted in all four enclosure corners (vertically or horizontally) and the weights are symmetrically distributed within the enclosure.; 200 kg
MaterialSteel; Steel plate
Material qualityOther
Material thickness (body)1.2 mm
Material thickness (bottom plate)2 mm
Material thickness (door)1.2 mm
Mounting method9 mm drilling dimensions for wall mounting (Back plate); Wall fastening; Intermediate mounting
Mounting plate height370 mm
Mounting plate materialSheet steel, hot-galvanized
Mounting plate width550 mm
Number of connector holes0
Number of covers/doors1
Number of F3A flanges2
Number of hinges2
Number of locks1
Permissible load of the door(s) according to IEC 62208 - max250 N
Permissible load of the enclosure according to IEC 62208 - max2250 N
Permissible load of the mounting plate according to IEC 62208 - max2000 N
Surface finishingStructured powder spray polyester based paint finish; Semi-textured; Powder coating; Gloss
Surface treatmentStructured powder spray polyester based paint finish
Thickness of mounting plate2 mm
Weight of mounted components - max225 kg
Degree of protectionIEC: IP66, indoor; UL/CSA Types 1, 12, indoor only.; 12 (NEMA); IP66; IP23 (with ventilating plates); IK10; IK10 (impact resistance)
Heat diss. wall mount individual encl. top39 W
Heat diss. wall mount middle encl. top35 W
Heat diss. wall mount starting encl. top37 W
Thermal dissipation (Delta T = 20 K) according to IEC/TR 6089039 W
ColourGrey
With mounting plateYes
Number of doors1
Suitable for wall mountingYes
Pre-stampingNo
EMC-versionYes
With glazed doorNo
CouplableNo
Impact strengthIK09
Suitable for outdoor set-upNo
Suitable for metrical mountingYes
Mounting plate depth-adjustableYes
ConnectableYes
With ventilation doorNo
Wall fastening possibleYes
With rear doorNo
Suitable for wall built-inYes
With coverYes
With doorYes
Pitched roofNo
Pole fasteningYes
Transparent coverNo
Suitable for outdoor installationYes
Max. permitted load of the enclosure according to IEC 622082250 N
Max. permitted load of the door(s) according to IEC 62208250 N
Floor standing wall modelYes
FreestandingNo
Corner modelNo
Intermediate mountingYes
Country of originSpain

Properties

MOQ1

Cross-References

Attached Documents