Unit breaker 10 A 2P C DC (FAZ-C10/2-DC)

Eaton · Ireland · eaton.com
Part Number
FAZ-C10/2-DC  ·  HS 8536.90
Unit breaker 10 A 2P C DC (FAZ-C10/2-DC)

Eaton FAZ-C10/2-DC Miniature circuit breaker (MCB), 10 A, 2p, characteristic: C, DC.

Technical Specifications

Manufacturer part number (MPN)FAZ-C10/2-DC
EAN / GTIN4015082791384
HS code8536.90
Sales unitpcs
Package quantity60 pcs
Eaton catalogue number279138
Depth80 mm
Height75.5 mm
Width36 mm
Weight0.222 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947-2; EN45545-2; IEC 61373
Current limiting class3
FeaturesAdditional equipment possible
Special featuresAmbient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Used withMiniature circuit breaker; FAZ-DC
Amperage Rating10 A
ApplicationSwitchgear for DC applications
Number of polesTwo-pole
Number of poles (protected)2
Number of poles (total)2
Release characteristicC
Tripping characteristicC
TypeFAZ-DC Miniature circuit breaker
Ambient operating temperature - max75 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent3 W
Heat dissipation capacity0 W
Heat dissipation per pole, current-dependent0 W
Rated operational current for specified heat dissipation (In)10 A
Static heat dissipation, non-current-dependent0 W
Admissible back-up fuse - max100 A gL/gG
Direction of incoming supplyPolarity dependent
Lifespan, electrical10000 operations
Overvoltage categoryIII
Pollution degree2
Rated impulse withstand voltage (Uimp)4 kV
Rated insulation voltage (Ui)440 V
Rated operational voltage (Ue) - max250 V
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V10 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V10 kA
Rated switching capacity (IEC/EN 60947-2)10 kA
Selectivity class3
Voltage rating at DC250 V DC (per pole)
Voltage typeDC
Built-in depth70.5 mm
Busbar material thickness0.8 mm - 2 mm
Connectable conductor cross section (multi-wired) - max25 mm²
Connectable conductor cross section (multi-wired) - min1 mm²
Connectable conductor cross section (solid-core) - max25 mm²
Connectable conductor cross section (solid-core) - min1 mm²
Degree of protectionIP20; IP40 (when fitted)
Enclosure width80 mm
Frame45 mm
Mounting MethodTop-hat rail IEC/EN 60715
Mounting positionAs required
Mounting width17.5 mm
Mounting width per pole17.5 mm
Terminal capacity (control cable)25 mm² (1x)
Terminal capacity of screw terminals for main cable10 mm² (2x)
Terminal protectionFinger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)Twin-purpose terminals
Width in number of modular spacings2

Properties