| Manufacturer part number (MPN) | 167889 |
| EAN / GTIN | 4015081644629 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 30 pcs |
| Eaton catalogue number | 167889 |
| Depth | 76 mm |
| Height | 80 mm |
| Width | 70 mm |
| Weight | 0.32 kg |
| Compliances | RoHS conform |
| Certifications | VDE 0664-400; EN45545-2; IEC 61373; IEC/EN 61008; IEC/EN 62423 |
| Features | Additional equipment possible; Selective protection; Residual current circuit-breakers, digital |
| Fitted with | Interlocking device |
| Used with | Residual current circuit-breakers, digital; FRCdM; Type S/B+ |
| Amperage Rating | 40 A |
| Application | xEffect - Switchgear for industrial and advanced commercial applications |
| Fault current rating | 300 mA |
| Impulse withstand current | 5 kA (8/20 μs) surge-proof |
| Number of poles | Four-pole |
| Rated short-circuit strength | 10 kA |
| Sensitivity type | All current sensitive |
| Tripping time | 40 ms delayed - selective switch off; Selective switch off |
| Type | FRCdM Residual current circuit-breakers, digital Type S/B+ |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature - min | -25 °C |
| Equipment heat dissipation, current-dependent | 6.2 W |
| Heat dissipation capacity | 6.2 W |
| Heat dissipation per pole, current-dependent | 0 W |
| Rated operational current for specified heat dissipation (In) | 40 A |
| Static heat dissipation, non-current-dependent | 0 W |
| Admissible back-up fuse | 63 A gG/gL |
| Admissible back-up fuse overload - max | 40 A gG/gL |
| Frequency rating | 50 Hz |
| Leakage current type | B+ |
| Lifespan, electrical | 4000 operations |
| Pollution degree | 2 |
| Rated fault current - max | 0.3 A |
| Rated fault current - min | 0.3 A |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated insulation voltage (Ui) | 440 V |
| Rated operational voltage (Ue) - max | 415 V |
| Rated residual making and breaking capacity | 500 A |
| Rated short-time withstand current (Icw) | 10 kA |
| Short-circuit rating | 63 A (max. admissible back-up fuse) |
| Surge current capacity | 5 kA |
| Test circuit range | 196 V AC - 456 V AC |
| Voltage rating - max | 456 VAC |
| Voltage rating - min | 50 VAC |
| Voltage rating (IEC/EN 60947-2) | 240 V AC / 415 V AC |
| Switching capacity of auxiliary contact - min | 10 μA, 10 mV DC |
| Switching current of auxiliary contact - max | 2 A |
| Switching duty with resistive load of auxiliary contact - max | 60 W |
| Switching voltage at AC of auxiliary contact - max | 240 V |
| Switching voltage at DC of auxiliary contact - max | 220 V |
| Terminal capacity of auxiliary contact | 0.25 mm² - 1.5 mm² |
| Built-in depth | 70.5 mm |
| Built-in width (number of units) | 70 mm (4 SU) |
| Busbar material thickness | 0.8 mm - 2 mm |
| Climatic proofing | 25-55 °C / 90-95% relative humidity according to IEC 60068-2 |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Connectable conductor cross section (multi-wired) - min | 1.5 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Contact position indicator color | Red / green |
| Degree of protection | IP20; IP20, IP40 with suitable enclosure |
| Frame | 45 mm |
| Lifespan, mechanical | 20000 operations |
| Mounting Method | Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715; DIN rail |
| Mounting position | As required |
| Permitted storage and transport temperature - max | 60 °C |
| Permitted storage and transport temperature - min | -35 °C |
| Status indication | White / blue |
| Terminal capacity (cable) | M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2) |
| Terminal capacity (solid wire) | 1.5 mm² - 35 mm² |
| Terminal capacity (stranded cable) | 16 mm² (2x) |
| Terminal protection | Finger and hand touch safe, DGUV VS3, EN 50274 |
| Terminals (top and bottom) | Twin-purpose terminals |
| Tightening torque | 2 Nm - 2.4 Nm |
| Width in number of modular spacings | 4 |
| Product family | Eaton Moeller series xEffect FRCdM RCCB |
| Device type | Residual current circuit breaker (RCCB), no integral overcurrent protection |
| Residual current type | Type B+ |
| Rated residual current (IΔn) | 300 mA |
| Rated current | 40 A |
| Tripping characteristic | Selective (S) |
| Selection note | Fire protection variant — trip limited to 420 mA up to 20 kHz |
| Protection purpose | Protection against earth-fault fire / equipment protection |