cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Residual current circuit breaker with overcurrent 32A 2P B 100MAA (PKP62-32/2/B/01-A)

Eaton · Electrical Components · RCDs & RCBOs · Ireland · eaton.com
Part Number
PKP62-32/2/B/01-A  ·  HS 8536.90
Residual current circuit breaker with overcurrent 32A 2P B 100MAA (PKP62-32/2/B/01-A)

Eaton PKP62-32/2/B/01-A B - characteristic A-type 2p (IT/TT/TN - network) - 32 A - violet residual current circuit breaker with overcurrent - 100mA 6kA.

Technical Specifications

Manufacturer part number (MPN)PKP62-32/2/B/01-A
EAN / GTIN4015081134564
HS code8536.90
Sales unitpcs
Package quantity6 pcs
Eaton catalogue number113946
Depth86 mm
Height75 mm
Width37 mm
Weight0.25 kg
CompliancesCE Marked; RoHS conform
CertificationsCE
Voltage rating230 V
Surge current capacity0.25 kA
Voltage typeAC
Width in number of modular spacings2
Operating ambient temperature - max40 °C
Operating ambient temperature - min-25 °C
Product applicationSwitchgear for industrial and advanced commercial applications
Product rangePKP62
Rated current32 A
Rated operational current for specified heat dissipation (In)32 A
Rated switching capacity (IEC/EN 61009)6 kA
Static heat dissipation, non-current-dependent0 W
Tripping characteristicB
Built-in depth70 mm
Current limiting class3
Rated short-circuit breaking capacity (EN 60947-2)0 kA
Ambient operating temperature - max40 °C
Ambient operating temperature - min-25 °C
Fault current rating0.1 A
Heat dissipation capacity0 W
Heat dissipation per pole, current-dependent0 W
Number of poles (protected)2
Number of poles (total)2
Rated operational voltage (Ue) - max230 V
Rated switching capacity6 kA
Basic functionCombined RCD/MCB devices
Mounting MethodDIN rail
Equipment heat dissipation, current-dependent5.5 W
Rated impulse withstand voltage (Uimp)4 kV
Degree of protectionIP20
TrippingNon-delayed
Overvoltage categoryIII
Pollution degree2
Impulse withstand currentPartly surge-proof, 250 A
Leakage current typeA
Release characteristicB
Sensitivity typeType A, pulse-current sensitive
Frequency rating50 Hz
Rated insulation voltage (Ui)250 V
Connectable conductor cross section (solid-core) - min1 mm²
Connectable conductor cross section (solid-core) - max25 mm²
Connectable conductor cross section (multi-wired) - min1 mm²
Connectable conductor cross section (multi-wired) - max25 mm²
Rated short-circuit breaking capacity (EN 61009)6 kA
Rated short-circuit breaking capacity (EN 61009-1)6 kA
Number of polesTwo-pole
Disconnection characteristicUndelayed
TypeRCBO
ApplicationSwitchgear for residential and commercial applications

Properties

MOQ1

Cross-References

Attached Documents