Earth-fault RCD. 16A 2P/C A-type (PKPM2-16/2/C/003-A)

Eaton · Electrical Components · RCDs & RCBOs · Ireland · eaton.com
Part Number
PKPM2-16/2/C/003-A  ·  HS 8536.90
Earth-fault RCD. 16A 2P/C A-type (PKPM2-16/2/C/003-A)

Eaton PKPM2-16/2/C/003-A RCBO, C - characteristic, A-type 2-pole (IT/TT/TN - network) - 16 A - 30mA 10kA, grey.

Technical Specifications

Manufacturer part number (MPN)PKPM2-16/2/C/003-A
EAN / GTIN4015081077656
HS code8536.90
Sales unitpcs
Package quantity6 pcs
Eaton catalogue number108111
Depth86 mm
Height75 mm
Width37 mm
Weight0.25 kg
CompliancesCE Marked; RoHS conform
CertificationsCE
Voltage rating230 V
Surge current capacity0.25 kA
Voltage typeAC
Width in number of modular spacings2
Operating ambient temperature - max40 °C
Operating ambient temperature - min-25 °C
Product applicationSwitchgear for industrial and advanced commercial applications
Product rangePKPM2
Rated current16 A
Rated operational current for specified heat dissipation (In)16 A
Rated switching capacity (IEC/EN 61009)10 kA
Static heat dissipation, non-current-dependent0 W
Tripping characteristicC
Built-in depth70 mm
Current limiting class3
Rated short-circuit breaking capacity (EN 60947-2)0 kA
Ambient operating temperature - max40 °C
Ambient operating temperature - min-25 °C
Fault current rating0.03 A
Heat dissipation capacity0 W
Heat dissipation per pole, current-dependent0 W
Number of poles (protected)2
Number of poles (total)2
Rated operational voltage (Ue) - max230 V
Rated switching capacity10 kA
Basic functionCombined RCD/MCB devices
Mounting MethodDIN rail
Equipment heat dissipation, current-dependent5 W
Rated impulse withstand voltage (Uimp)4 kV
Degree of protectionIP20
TrippingNon-delayed
Overvoltage categoryIII
Pollution degree2
Impulse withstand currentPartly surge-proof, 250 A
Leakage current typeA
Release characteristicC
Sensitivity typeType A, pulse-current sensitive
Frequency rating50 Hz
Rated insulation voltage (Ui)250 V
Connectable conductor cross section (solid-core) - min1 mm²
Connectable conductor cross section (solid-core) - max25 mm²
Connectable conductor cross section (multi-wired) - min1 mm²
Connectable conductor cross section (multi-wired) - max25 mm²
Rated short-circuit breaking capacity (EN 61009)10 kA
Rated short-circuit breaking capacity (EN 61009-1)10 kA
Number of polesTwo-pole
Disconnection characteristicUndelayed
TypeRCBO
ApplicationSwitchgear for residential and commercial applications

Properties

MOQ1

Cross-References

Attached Documents