cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

NH2 Switch-disconnector 3P400 BBE (XNH2-FCE-S400-BT)

Eaton · Switchgear & Protection · Fuse Switch-Disconnectors · Ireland · eaton.com
Part Number
XNH2-FCE-S400-BT  ·  HS 8536.90
NH2 Switch-disconnector 3P400 BBE (XNH2-FCE-S400-BT)

Technical Specifications

Manufacturer part number (MPN)XNH2-FCE-S400-BT
EAN / GTIN4015081779970
Sales unitpcs
Eaton catalogue number183070
Depth306 mm
Height190 mm
Width210 mm
Weight4.099 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947-3
FeaturesElectronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-5; Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-4; Halogen free; Standard sealable
Fitted withConnectors; Error protection
Flammability characteristics (UL)Self-extinguishing (UL 94)
Special featuresPermanent operation (rated operating mode) Current paths of electrolytic copper, silver-plated with electronic monitoring of fuse-links
Suitable forBusbar mounting; Front mounting
Actuator typeCover grip
ColorGray
Number of polesThree-pole
TypeFuse control - electronic
Ambient operating temperature detailsAmbient temperature range: -25 °C - 70 °C Operating temperature range: -5 °C - 55 °C
Equipment heat dissipation, current-dependent22 W
Heat deflection temperature125 °C
Heat dissipation at 80% without fuses22.9 W
Heat dissipation per pole, current-dependent7.3 W
Rated operational current for specified heat dissipation (In)400 A
Total heat dissipation without fuses at Ith36 W
Creepage resistanceCTI 600
Direction of incoming supplyAs required (FLEX System)
Electrical connection type of main circuitFrame clamp
Electronic fuse monitoring1 NC; 1 NO; > 1 kOhm/V; 3 LEDs (F1, F2, F3) red; 1.5 VA; Test button for relay + LEDs; NH with live handle straps; Self-supplied; 1 LED green
Frequency rating40 Hz - 60 Hz
Frequency rating (electronic fuse monitoring)50 - 60 Hz
Frequency rating of contacts40 Hz - 60 Hz
Lifespan, electrical200 operations
Operating altitude without derating - max2000 mm
Overvoltage categoryIII (230/400 V); III; II (500 V)
Permitted power loss per fuse link - max34 W
Pollution degree3
Rated conditional short-circuit rating100 kA (690 V); 120 kA (500 V)
Rated impulse withstand voltage (Uimp)8 kV
Rated insulation voltage (Ui)800 VAC
Rated operating voltage (Ue) at AC - max500 V
Rated operation current (Ie)400 A
Rated operational current400 A (DC-22B); 400 A (AC-21B); 400 A (AC-22B); 400 A (AC-23B)
Rated short-time withstand current (Icw)3 kA
Rated uninterrupted current (Iu)400 A
Switching current of electronic fuse monitoring - max1 A
Voltage inputs400 V AC - 500 V AC (+/-10%)
Voltage rating at AC400 V (AC-23B) 500 V (AC-22B) 690 V (AC-21B)
Voltage rating at AC - max250 VAC
Voltage rating at DC440 V (DC-22B)
Voltage rating at DC - max24 VDC
Voltage testYes, sliding inspection windows
Conditioned rated short-circuit current Iq120 kA
Rated conditional short-circuit current (Iq)120 kA
Activation typeDependent manual activation
Actuator positionFront side
Cable entry typeOther
Degree of protection (front side)Other
Lifespan, mechanical800 operations
Locking facilityYes, optional
MaterialPolyamide
Mounting methodBusbars of 60 mm
Mounting positionVertical or horizontal
SizeNH2 fuse
Suitable for fusesNH2
Terminal capacity (copper band)10 mm x 16 mm x 0.8 mm (10x) at box terminal
Terminal capacity (copper busbar)Max. 48 mm cable lug width at flange connection; Bolt diameter at flange connection: M10; 40 mm x 10 mm
Terminal capacity (copper strip)16 mm x 0.8 mm (6x) - 32 mm x 1 mm (10x) at box terminal
Terminal capacity (stranded cable)95 mm² - 300 mm² (1x) at box terminal; 120 mm² - 240 mm² at clamp-type terminal; 120 mm² - 150 mm² (2x) at double clamp-type terminal; 25 mm² - 240 mm² at box terminal
Connection typeBox terminal
Degree of protectionIP2XC (contact protection, XNH installed); IP10 (handle cover open, XNH installed); IP3X; IP20 (operating status, XNH installed)
Rated permanent current Iu400 A
Motor drive integratedNo
Type of electrical connection of main circuitFrame clamp
Version as emergency stop installationNo
Type of control elementCover grip
Version as main switchNo
Version as safety switchNo
Rated short-time withstand current lcw3 kA
Suitable for floor mountingNo
Suitable for front mountingYes
Suitable for busbar mountingYes
Max. rated operation voltage Ue AC500 V
With error protectionYes
Motor drive optionalNo
Position control elementFront side
Equipped with connectorsYes
Country of originGermany

Properties

MOQ1

Cross-References