NH1 Switch-disconnector 3P250 E/B (XNH1-FCE-A250-BT)

Eaton · Switchgear & Protection · Fuse Switch-Disconnectors · Ireland · eaton.com
Part Number
XNH1-FCE-A250-BT  ·  HS 8536.90
NH1 Switch-disconnector 3P250 E/B (XNH1-FCE-A250-BT)

Technical Specifications

Manufacturer part number (MPN)XNH1-FCE-A250-BT
EAN / GTIN4015081779758
Sales unitpcs
Eaton catalogue number183048
Depth306 mm
Height148 mm
Width184 mm
Weight2.213 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947-3
FeaturesElectronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-5; Halogen free; Standard sealable; Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-4
Fitted withConnectors; Error protection
Flammability characteristics (UL)Self-extinguishing (UL 94)
Special featuresPermanent operation (rated operating mode) Current paths of electrolytic copper, silver-plated with electronic monitoring of fuse-links
Suitable forGround mounting; Front mounting
Actuator typeCover grip
ColorGray
Number of polesThree-pole
TypeFuse control - electronic
Ambient operating temperature detailsAmbient temperature range: -25 °C - 70 °C Operating temperature range: -5 °C - 55 °C
Equipment heat dissipation, current-dependent16 W
Heat deflection temperature125 °C
Heat dissipation at 80% without fuses10.2 W
Heat dissipation per pole, current-dependent5.3 W
Rated operational current for specified heat dissipation (In)250 A
Total heat dissipation without fuses at Ith16 W
Creepage resistanceCTI 600
Direction of incoming supplyAs required
Electrical connection type of main circuitFrame clamp
Electronic fuse monitoring1 NC; 1.5 VA; Test button for relay + LEDs; 1 LED green; Self-supplied; 3 LEDs (F1, F2, F3) red; NH with live handle straps; > 1 kOhm/V; 1 NO
Frequency rating40 Hz - 60 Hz
Frequency rating (electronic fuse monitoring)50 - 60 Hz
Frequency rating of contacts40 Hz - 60 Hz
Lifespan, electrical200 operations
Operating altitude without derating - max2000 mm
Overvoltage categoryIII; III (230/400 V); II (500 V)
Permitted power loss per fuse link - max23 W
Pollution degree3
Rated conditional short-circuit rating120 kA (500 V); 100 kA (690 V)
Rated impulse withstand voltage (Uimp)8 kV
Rated insulation voltage (Ui)800 VAC
Rated operating voltage (Ue) at AC - max500 V
Rated operation current (Ie)250 A
Rated operational current250 A (DC-21B); 250 A (AC-21B); 250 A (AC-23B); 250 A (AC-22B); 250 A (DC-22B)
Rated short-time withstand current (Icw)6 kA
Rated uninterrupted current (Iu)250 A
Switching current of electronic fuse monitoring - max1 A
Voltage inputs400 V AC - 500 V AC (+/-10%)
Voltage rating at AC400 V (AC-23B) 500 V (AC-22B) 690 V (AC-21B)
Voltage rating at AC - max250 VAC
Voltage rating at DC250 V (DC-22B) 440 V (DC-21B)
Voltage rating at DC - max24 VDC
Voltage testYes, sliding inspection windows
Conditioned rated short-circuit current Iq120 kA
Rated conditional short-circuit current (Iq)120 kA
Activation typeDependent manual activation
Actuator positionFront side
Cable entry typeOther
Degree of protection (front side)Other
Lifespan, mechanical1400 operations
Locking facilityYes, optional
MaterialPolyamide
Mounting methodMounting plate; DIN rail
Mounting positionVertical or horizontal
SizeNH1 fuse
Suitable for fusesNH1
Terminal capacity (copper band)6 mm x 16 mm x 0.8 mm (6x) at box terminal
Terminal capacity (copper busbar)Bolt diameter at flange connection: M10; Max. 37 mm cable lug width at flange connection; 30 mm x 10 mm
Terminal capacity (copper strip)16 mm x 0.8 mm (10x) at box terminal
Terminal capacity (stranded cable)70 mm² - 95 mm² (2x) at double clamp-type terminal; 25 mm² - 150 mm² at box terminal; 35 mm² - 150 mm² at box terminal; 10 mm² -150 mm² at clamp-type terminal
Connection typeBox terminal
Degree of protectionIP2XC (contact protection, XNH installed); IP10 (handle cover open, XNH installed); IP20 (operating status, XNH installed); IP3X
Rated permanent current Iu250 A
Motor drive integratedNo
Type of electrical connection of main circuitFrame clamp
Version as emergency stop installationNo
Type of control elementCover grip
Version as main switchNo
Version as safety switchNo
Rated short-time withstand current lcw6 kA
Suitable for floor mountingYes
Suitable for front mountingYes
Suitable for busbar mountingNo
Max. rated operation voltage Ue AC500 V
With error protectionYes
Motor drive optionalNo
Position control elementFront side
Equipped with connectorsYes
Country of originGermany

Properties