Eaton FUSE Switch Disconnector (XNH00-S160)

Eaton · Switchgear & Protection · Fuse Switch-Disconnectors · Ireland · eaton.com
Part Number
XNH00-S160  ·  HS 8536.90
Eaton FUSE Switch Disconnector (XNH00-S160)

Eaton XNH00-S160 NH fuse-switch 3p flange connection M8 max. 95 mm², busbar 60 mm, NH000 & NH00.

Technical Specifications

Manufacturer part number (MPN)XNH00-S160
EAN / GTIN4015081779604
HS code8536.90
Sales unitpcs
Eaton catalogue number183033
Depth204 mm
Height137 mm
Width106 mm
Weight0.788 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947-3
FeaturesStandard sealable; Halogen free
Flammability characteristics (UL)Self-extinguishing (UL 94)
Special featuresPermanent operation (rated operating mode) Current paths of electrolytic copper, silver-plated Cable connection optionally at the top or bottom
Suitable forBusbar mounting; Front mounting
Actuator typeCover grip
ColorGray
Number of polesThree-pole
TypeBasic device
Ambient operating temperature detailsAmbient temperature range: -25 °C - 70 °C
Equipment heat dissipation, current-dependent14 W
Heat deflection temperature125 °C
Heat dissipation at 80% without fuses9 W
Heat dissipation per pole, current-dependent4.7 W
Rated operational current for specified heat dissipation (In)160 A
Total heat dissipation without fuses at Ith14 W
Creepage resistanceCTI 600
Direction of incoming supplyAs required (FLEX System)
Electrical connection type of main circuitScrew connection
Frequency rating40 Hz - 60 Hz
Frequency rating of contacts40 Hz - 60 Hz
Lifespan, electrical300 operations
Operating altitude without derating - max2000 mm
Overvoltage categoryIII
Permitted power loss per fuse link - max12 W
Pollution degree3
Power rating at AC-23, 400 V0 kW
Rated conditional short-circuit rating120 kA (500 V); 100 kA (690 V)
Rated impulse withstand voltage (Uimp)8 kV
Rated insulation voltage (Ui)800 VAC
Rated operating voltage (Ue) at AC - max690 V
Rated operation current (Ie)160 A
Rated operational current160 A (AC-22B); 160 A; 160 A (AC-23B); 160 A (AC-21B)
Rated short-time withstand current (Icw)7 kA
Rated uninterrupted current (Iu)160 A
Voltage rating at AC400 V (AC-23B) 500 V (AC-22B) 690 V (AC-21B)
Voltage rating at DC250 V DC at DC-22B 440 V DC at DC-21B
Voltage testYes, sliding inspection windows
Conditioned rated short-circuit current Iq120 kA
Rated conditional short-circuit current (Iq)120 kA
Activation typeDependent manual activation
Actuator positionFront side
Cable entry typeOther
Degree of protection (front side)Other
Lifespan, mechanical1400 operations
Locking facilityYes, optional
MaterialPolyamide
Mounting methodBusbars of 60 mm
Mounting positionVertical or horizontal
SizeNH000 / NH00 fuse
Suitable for fusesNH00
Terminal capacity (copper band)9 mm x 0.8 mm (6x) at box terminal
Terminal capacity (copper busbar)Max. 25 mm cable lug width at flange connection; 20 mm x 10 mm; Bolt diameter at flange connection: M8
Terminal capacity (copper strip)9 mm x 0.8 mm (9x) at box terminal
Terminal capacity (stranded cable)1.5 mm² - 95 mm² at box terminal; 1.5 mm² - 50 mm² at box terminal; 10 mm² - 70 mm² at clamp-type terminal
Connection typeFlat connection
Degree of protectionIP20 (operating status, XNH installed); IP2XC (contact protection, XNH installed); IP10 (handle cover open, XNH installed)

Properties

MOQ1

Cross-References

Attached Documents