| Manufacturer | Eaton |
| Product family | xPole PLHT |
| Type designation | PLHT-OV80/3 |
| Manufacturer part number (MPN) | PLHT-OV80/3 |
| EAN / GTIN | 4015082649906 |
| Eaton / SAP material no. | 1000017926 |
| Poles | 3P |
| Release | thermomagnetic (overload + short-circuit) |
| Rated current In | 80 A |
| Rated ultimate breaking capacity Icu | 20 kA |
| Rated operational voltage Ue | 230/400 V AC |
| Mounting | DIN rail (35 mm) |
| Standard | IEC/EN 60947-2 |
| HS code | 8536.20 |
| Sales unit | pcs |
| Eaton catalogue number | 264990 |
| Depth | 90 mm |
| Height | 75 mm |
| Width | 81 mm |
| Weight | 0.64 kg |
| Compliances | RoHS conform |
| Current limiting class | 3 |
| Features | Additional equipment possible |
| Special features | Ambient temperature hint: a 1 °C increase results in a 0.35% linear reduction of current carrying capacity |
| Amperage Rating | 80 A |
| Number of poles (protected) | 3 |
| Number of poles (total) | 3 |
| Release characteristic | Other |
| Ambient operating temperature - max | 55 °C |
| Ambient operating temperature - min | -25 °C |
| Equipment heat dissipation, current-dependent | 21.3 W |
| Heat dissipation capacity | 0 W |
| Heat dissipation per pole, current-dependent | 7.1 W |
| Rated operational current for specified heat dissipation (In) | 80 A |
| Static heat dissipation, non-current-dependent | 0 W |
| Frequency rating - max | 60 Hz |
| Frequency rating - min | 50 Hz |
| Overvoltage category | III |
| Pollution degree | 2 |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated insulation voltage (Ui) | 440 V |
| Rated operational voltage (Ue) - max | 400 V |
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V | 20 kA |
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V | 20 kA |
| Voltage type | AC |
| Built-in depth | 75 mm |
| Connectable conductor cross section (multi-wired) - max | 50 mm² |
| Connectable conductor cross section (multi-wired) - min | 2.5 mm² |
| Connectable conductor cross section (solid-core) - max | 50 mm² |
| Connectable conductor cross section (solid-core) - min | 2.5 mm² |
| Degree of protection | IP20 |
| Width in number of modular spacings | 3 |