cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-06
sales@cballast.com
cballast.com

Eaton PLHT-OV80/3 Miniature Circuit Breaker — 3P, OV, 80 A, 20 kA

Eaton · Electrical Components · Miniature Circuit Breakers · Ireland · eaton.com
Part Number
PLHT-OV80/3  ·  HS 8536.20
Eaton PLHT-OV80/3 Miniature Circuit Breaker — 3P, OV, 80 A, 20 kA

Eaton PLHT-OV80/3 miniature circuit breaker (MCB) from the xPole PLHT range. 3-pole, rated current In = 80 A, thermomagnetic overload and short-circuit release (Eaton 'OV' overload-protection designation). Rated ultimate short-circuit breaking capacity Icu = 20 kA to IEC/EN 60947-2; rated operational voltage Ue 230/400 V AC. DIN-rail (35 mm) modular device for overload and short-circuit protection of cables and equipment. Conforms to IEC/EN 60947-2. Eaton type PLHT-OV80/3, EAN 4015082649906, Eaton/SAP material 1000017926, catalogue code 8138362.

Technical Specifications

ManufacturerEaton
Product familyxPole PLHT
Type designationPLHT-OV80/3
Manufacturer part number (MPN)PLHT-OV80/3
EAN / GTIN4015082649906
Eaton / SAP material no.1000017926
Poles3P
Releasethermomagnetic (overload + short-circuit)
Rated current In80 A
Rated ultimate breaking capacity Icu20 kA
Rated operational voltage Ue230/400 V AC
MountingDIN rail (35 mm)
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs
Eaton catalogue number264990
Depth90 mm
Height75 mm
Width81 mm
Weight0.64 kg
CompliancesRoHS conform
Current limiting class3
FeaturesAdditional equipment possible
Special featuresAmbient temperature hint: a 1 °C increase results in a 0.35% linear reduction of current carrying capacity
Amperage Rating80 A
Number of poles (protected)3
Number of poles (total)3
Release characteristicOther
Ambient operating temperature - max55 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent21.3 W
Heat dissipation capacity0 W
Heat dissipation per pole, current-dependent7.1 W
Rated operational current for specified heat dissipation (In)80 A
Static heat dissipation, non-current-dependent0 W
Frequency rating - max60 Hz
Frequency rating - min50 Hz
Overvoltage categoryIII
Pollution degree2
Rated impulse withstand voltage (Uimp)4 kV
Rated insulation voltage (Ui)440 V
Rated operational voltage (Ue) - max400 V
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V20 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V20 kA
Voltage typeAC
Built-in depth75 mm
Connectable conductor cross section (multi-wired) - max50 mm²
Connectable conductor cross section (multi-wired) - min2.5 mm²
Connectable conductor cross section (solid-core) - max50 mm²
Connectable conductor cross section (solid-core) - min2.5 mm²
Degree of protectionIP20
Width in number of modular spacings3

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References

Attached Documents