cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Residual current circuit breaker 40A 4P 300MA S/A (235468)

Eaton · Electrical Components · RCDs & RCBOs · Ireland · eaton.com
Part Number
235468  ·  HS 8536.90
Residual current circuit breaker 40A 4P 300MA S/A (235468)

Eaton 235468 Residual current circuit breaker, 40A, Selective A-Type.

Technical Specifications

Manufacturer part number (MPN)235468
EAN / GTIN4015082354688
HS code8536.90
Sales unitpcs
Package quantity3 pcs
Eaton catalogue number235468
Depth76 mm
Height80 mm
Width70 mm
Weight0.336 kg
CompliancesRoHS conform
CertificationsIEC/EN 61008
Accessories requiredZ-HK 248432
FeaturesAdditional equipment possible; Residual current circuit breaker; Selective protection
Fitted withInterlocking device
Special featuresMaximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C Tripping signal contact for subsequent installation Z-NHK 248434
Amperage Rating40 A
ApplicationResidual current circuit breaker for residential and commercial applications xPole - Switchgear for residential and commercial applications
Fault current rating300 mA
Impulse withstand currentSurge-proof 5 kA
Number of polesFour-pole
Rated short-circuit strength10 kA
Sensitivity typePulse-current sensitive
Tripping timeSelective switch off
TypePFIM Residual current circuit breakers Type S/A
Ambient operating temperature - max60 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent8.4 W
Heat dissipation capacity0 W
Heat dissipation per pole, current-dependent0 W
Rated operational current for specified heat dissipation (In)40 A
Static heat dissipation, non-current-dependent0 W
Admissible back-up fuse overload - max25 A gG/gL
Frequency rating50 Hz
Leakage current typeA
Lifespan, electrical4000 operations
Pollution degree2
Rated fault current - max0.3 A
Rated fault current - min0.3 A
Rated impulse withstand voltage (Uimp)4 kV
Rated insulation voltage (Ui)440 V
Rated operational voltage (Ue) - max400 V
Rated residual making and breaking capacity500 A
Rated short-time withstand current (Icw)10 kA
Short-circuit rating63 A (max. admissible back-up fuse)
Surge current capacity5 kA
Test circuit range196 V AC - 456 V AC
Voltage rating230 V AC / 400 V AC
Built-in depth70.5 mm
Built-in width (number of units)70 mm (4 SU)
Busbar material thickness0.8 mm - 2 mm
Climatic proofing25-55 °C / 90-95% relative humidity according to IEC 60068-2
Connectable conductor cross section (multi-wired) - max16 mm²
Connectable conductor cross section (multi-wired) - min1.5 mm²
Connectable conductor cross section (solid-core) - max35 mm²
Connectable conductor cross section (solid-core) - min1.5 mm²
Degree of protectionIP20, IP40 with suitable enclosure; IP20
Frame45 mm
Lifespan, mechanical20000 operations
Mounting MethodDIN rail; Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Permitted storage and transport temperature - max60 °C
Permitted storage and transport temperature - min-35 °C
Terminal capacity (solid wire)1.5 mm² - 35 mm²
Terminal capacity (stranded cable)16 mm² (2x)
Terminal protectionFinger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)Open mouthed/lift terminals
Width in number of modular spacings4

Properties

MOQ1

Cross-References

Attached Documents