cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton FAZT-D2/2 Miniature Circuit Breaker — 2P, Type D, 2 A, 25 kA

Eaton · Electrical Components · Miniature Circuit Breakers · Ireland · eaton.com
Part Number
FAZT-D2/2  ·  HS 8536.20
Eaton FAZT-D2/2 Miniature Circuit Breaker — 2P, Type D, 2 A, 25 kA

Eaton FAZT-D2/2 miniature circuit breaker (MCB) from the xEffect FAZ-T range. 2-pole, rated current In = 2 A, Type D tripping characteristic. Rated ultimate short-circuit breaking capacity Icu = 25 kA to IEC/EN 60947-2; rated operational voltage Ue 230/400 V AC. DIN-rail (35 mm) modular device for overload and short-circuit protection of cables and equipment. Conforms to IEC/EN 60947-2. Eaton type FAZT-D2/2, EAN 4015082408657, Eaton/SAP material 1200283360, catalogue code 82253590.

Technical Specifications

ManufacturerEaton
Product familyxEffect FAZ-T
Type designationFAZT-D2/2
Manufacturer part number (MPN)FAZT-D2/2
EAN / GTIN4015082408657
Eaton / SAP material no.1200283360
Poles2P
Tripping characteristicType D
Rated current In2 A
Rated ultimate breaking capacity Icu25 kA
Rated operational voltage Ue230/400 V AC
MountingDIN rail (35 mm)
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs
Eaton catalogue number240865
Depth80 mm
Height75.5 mm
Width36 mm
Weight0.225 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947-2; EN45545-2; IEC 61373
Used withFAZ-T; Miniature circuit breaker
Amperage Rating2 A
FeaturesAdditional equipment possible
Frame45 mm
Frequency rating50 Hz / 60 Hz
Pollution degree2
Lifespan, mechanical10000 operations
Mounting MethodQuick attachment with 3 latch positions for top-hat rail IEC/EN 60715
Degree of protectionIP20
Equipment heat dissipation, current-dependent2 W
Rated impulse withstand voltage (Uimp)4 kV
Busbar material thickness0.8 mm (except N 0.5 SU)
Terminal protectionFinger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)Twin-purpose terminals
Ambient operating temperature - max75 °C
Ambient operating temperature - min-25 °C
Built-in depth70.5 mm
Connectable conductor cross section (multi-wired) - max25 mm²
Connectable conductor cross section (multi-wired) - min1 mm²
Connectable conductor cross section (solid-core) - max25 mm²
Connectable conductor cross section (solid-core) - min1 mm²
Current limiting class3
Enclosure width80 mm
Frequency rating - max60 Hz
Frequency rating - min50 Hz
Heat dissipation capacity0 W
Heat dissipation per pole, current-dependent0 W
Direction of incoming supplyAs required
Voltage rating (IEC/EN 60898-1)400 VAC
Width in number of modular spacings2
Voltage rating (IEC/EN 60947-2)240 V AC / 415 V AC
Voltage typeAC
Mounting positionAs required
Overvoltage categoryIII
Number of polesTwo-pole
Lifespan, electrical4000 operations
Release characteristicD
TypeFAZ-T Miniature circuit breaker
Special featuresAmbient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
ApplicationSwitchgear for industrial and advanced commercial applications xEffect - Switchgear for industrial and advanced commercial applications
Mounting width17.5 mm
Mounting width per pole17.5 mm
Number of poles (protected)2
Number of poles (total)2
Operational voltage (IEC/EN 60947-2) - max415 VAC
Operational voltage at DC (EC/EN 60947-2) - max60 VDC
Rated insulation voltage (Ui)440 V
Rated operational current for specified heat dissipation (In)2 A
Rated operational voltage (Ue) - max415 V
Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V15 kA
Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V15 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V25 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V25 kA
Rated switching capacity (IEC/EN 60947-2)25 kA
Static heat dissipation, non-current-dependent0 W
Terminal capacity1 mm² - 25 mm²
Tightening torqueMax. 2.4 Nm
Power loss2 W
Document NameDescription Action

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References

Attached Documents