cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety switch 3P 1NO1NC IN75A (P3-100/I5/SVB/HI11)

Eaton · Switchgear & Protection · Safety Switches · Ireland · eaton.com
Part Number
P3-100/I5/SVB/HI11  ·  HS 8536.50
Safety switch 3P 1NO1NC IN75A (P3-100/I5/SVB/HI11)

Eaton P3-100/I5/SVB/HI11 3 pole safety switch with auxiliary contact, 1NO+1NC, Iu = 100A, AC-23A.

Technical Specifications

Manufacturer part number (MPN)P3-100/I5/SVB/HI11
EAN / GTIN4015082073787
Sales unitpcs
Eaton catalogue number207378
Depth169 mm
Height180 mm
Width200 mm
Weight1.54 kg
CompliancesCE Marked
CertificationsCSA Std. C22.2 No. 14-05; UL 508; IEC 60947; EN 60947-3; VDE; IEC/EN 60204; IEC/EN 60947-3; VDE 0660; CSA; IEC/EN 60947; UL
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorRed
Actuator typeDoor coupling rotary drive
Ambient operating temperature - max40 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)1
Equipment heat dissipation, current-dependent Pvid7.5 W
Heat dissipation per pole, current-dependent Pvid7.5 W
Rated operational current for specified heat dissipation (In)100 A
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)760 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)740 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)880 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)520 A
Rated operational current (Ie) at AC-21, 440 V100 A
Rated operational current (Ie) at AC-23A, 230 V100 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V100 A
Rated operational current (Ie) at AC-23A, 500 V96 A
Rated operational current (Ie) at AC-23A, 690 V68 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V71 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V71 A
Rated operational current (Ie) at AC-3, 500 V65 A
Rated operational current (Ie) at AC-3, 660 V, 690 V23.8 A
Rated operational current (Ie) at DC-23A, 120 V25 A
Rated operational current (Ie) at DC-23A, 24 V50 A
Rated operational current (Ie) at DC-23A, 48 V50 A
Rated operational current (Ie) at DC-23A, 60 V50 A
Rated operational power at AC-23A, 220/230 V, 50 Hz30 kW
Rated operational power at AC-23A, 400 V, 50 Hz55 kW
Rated operational power at AC-23A, 500 V, 50 Hz55 kW
Rated operational power at AC-23A, 690 V, 50 Hz55 kW
Rated operational power at AC-3, 380/400 V, 50 Hz37 kW
Rated operational power at AC-3, 415 V, 50 Hz37 kW
Rated operational power at AC-3, 500 V, 50 Hz45 kW
Rated operational power at AC-3, 690 V, 50 Hz37 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)100 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as emergency stop installation; Version as maintenance-/service switch; Version as main switch; Version as safety switch
Fitted withRed rotary handle and yellow locking ring
FunctionsInterlockable; Emergency switching off function
Locking facilityLockable in the 0 (Off) position
Number of poles3
AccessoriesAuxiliary contact or neutral conductor fitted by user.
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical100,000 Operations
Mounting methodSurface mounting
Mounting positionAs required
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forGround mounting
Switching angle90 °
Assigned motor power at 115/120 V, 60 Hz, 1-phase5 HP
Assigned motor power at 200/208 V, 60 Hz, 1-phase10 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase20 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase15 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase25 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase60 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase75 HP
Rated conditional short-circuit current (Iq)4 kA (Load side); 80 kA (Supply side)
Rated short-time withstand current (Icw)2 kA
Short-circuit current rating (basic rating)10 kA, SCCR (UL/CSA); 150A, max. Fuse, SCCR (UL/CSA)
Short-circuit protection rating100 A gG/gL, Fuse, Contacts
Load rating1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor); 2 x Iₑ (with intermittent operation class 12, 25 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor)
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V1
Number of contacts in series at DC-23A, 48 V2
Number of contacts in series at DC-23A, 60 V2
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)950 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)P600 (UL/CSA); A600 (UL/CSA)
Switching capacity (main contacts, general use)100 A, If used with neutral conductor IU = max. 90 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series60 V
Screw sizeM5, Terminal screw
Terminal capacity14 - 2 AWG, solid or flexible with ferrule; 1 x (1.5 - 25) mm², flexible with ferrules to DIN 46228; 2 x (1.5 - 6) mm², flexible with ferrules to DIN 46228; 2 x (2.5 - 10) mm², solid or stranded; 1 x (2.5 - 35) mm², solid or stranded
Tightening torque26.5 lb-in, Screw terminals; 3 Nm, Screw terminals
Country of originUnited Kingdom

Properties

MOQ1

Cross-References

Attached Documents