cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety switch 3P 1NO1NC IN12A (T0-3-15159/I1/SVB)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
T0-3-15159/I1/SVB  ·  HS 8536.50
Safety switch 3P 1NO1NC IN12A (T0-3-15159/I1/SVB)

Eaton T0-3-15159/I1/SVB 3 pole safety switch with auxiliary contact 1NO+1NC, Iu = 20A, AC-23A.

Technical Specifications

Manufacturer part number (MPN)T0-3-15159/I1/SVB
EAN / GTIN4015082226466
Sales unitpcs
Eaton catalogue number222646
Depth137 mm
Height130 mm
Width80 mm
Weight0.324 kg
CertificationsEN 60947; EN 60204; IEC 60947; VDE; IEC/EN 60947-3; IEC/EN 60204; VDE 0660; IEC/EN 60947
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorRed
Actuator typeDoor coupling rotary drive
Ambient operating temperature - max40 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)3
Equipment heat dissipation, current-dependent Pvid0.6 W
Heat dissipation per pole, current-dependent Pvid0.6 W
Rated operational current for specified heat dissipation (In)20 A
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)100 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)110 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)80 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)60 A
Rated operational current (Ie) at AC-21, 440 V20 A
Rated operational current (Ie) at AC-23A, 230 V13.3 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V13.3 A
Rated operational current (Ie) at AC-23A, 500 V13.3 A
Rated operational current (Ie) at AC-23A, 690 V7.6 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V11.5 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V11.5 A
Rated operational current (Ie) at AC-3, 500 V9 A
Rated operational current (Ie) at AC-3, 660 V, 690 V4.9 A
Rated operational current (Ie) at DC-13, control switches L/R = 50 ms10 A
Rated operational current (Ie) at DC-21, 240 V1 A
Rated operational current (Ie) at DC-23A, 120 V5 A
Rated operational current (Ie) at DC-23A, 24 V10 A
Rated operational current (Ie) at DC-23A, 240 V5 A
Rated operational current (Ie) at DC-23A, 48 V10 A
Rated operational current (Ie) at DC-23A, 60 V10 A
Rated operational current (Ie) star-delta at AC-3, 220/230 V20 A
Rated operational current (Ie) star-delta at AC-3, 380/400 V20 A
Rated operational current (Ie) star-delta at AC-3, 500 V15.6 A
Rated operational current (Ie) star-delta at AC-3, 690 V8.5 A
Rated operational power at AC-23A, 220/230 V, 50 Hz3 kW
Rated operational power at AC-23A, 400 V, 50 Hz5.5 kW
Rated operational power at AC-23A, 500 V, 50 Hz7.5 kW
Rated operational power at AC-23A, 690 V, 50 Hz5.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz5.5 kW
Rated operational power at AC-3, 415 V, 50 Hz5.5 kW
Rated operational power at AC-3, 500 V, 50 Hz5.5 kW
Rated operational power at AC-3, 690 V, 50 Hz4 kW
Rated operational power star-delta at 220/230 V, 50 Hz5.5 kW
Rated operational power star-delta at 380/400 V, 50 Hz7.5 kW
Rated operational power star-delta at 500 V, 50 Hz7.5 kW
Rated operational power star-delta at 690 V, 50 Hz5.5 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)20 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as emergency stop installation; Version as main switch; Version as maintenance-/service switch
Fitted withRed rotary handle and yellow locking ring
FunctionsInterlockable; Emergency switching off function
Number of poles3
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical400,000 Operations
Mounting methodSurface mounting
Mounting positionAs required
Number of contact units3
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forGround mounting
Switching angle90 °
Rated conditional short-circuit current (Iq)6 kA
Rated short-time withstand current (Icw)320 A, Contacts, 1 second; 0.32 kA
Short-circuit protection rating20 A gG/gL, Fuse, Contacts
Load rating1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor); 2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
Number of contacts in series at DC-21A, 240 V1
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V1
Number of contacts in series at DC-23A, 240 V5
Number of contacts in series at DC-23A, 48 V2
Number of contacts in series at DC-23A, 60 V3
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)130 A
Voltage per contact pair in series60 V
Screw sizeM3.5, Terminal screw
Terminal capacity1 x (1 - 2.5) mm², solid or stranded; 1 x (0.75 - 2.5) mm², flexible with ferrules to DIN 46228; 2 x (0.75 - 2.5) mm², flexible with ferrules to DIN 46228; 2 x (1 - 2.5) mm², solid or stranded
Tightening torque1 Nm, Screw terminals
Country of originUnited Kingdom

Properties

MOQ1

Cross-References