cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

NETT-O-AGGR "plass B" (T5-3-8212/I5)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
T5-3-8212/I5  ·  HS 8536.50
NETT-O-AGGR "plass B" (T5-3-8212/I5)

Eaton T5-3-8212/I5 3-pole selector switch with 0-position.

Technical Specifications

Manufacturer part number (MPN)T5-3-8212/I5
EAN / GTIN7022241006378
Sales unitpcs
Eaton catalogue number207266
Depth280 mm
Height197 mm
Width200 mm
Weight2.018 kg
CertificationsIEC 60947; EN 60204; EN 60947; VDE; IEC/EN 60947; IEC/EN 60947-3; VDE 0660; IEC/EN 60204
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator functionMaintained; With 0 (Off) position
Actuator typeShort thumb-grip
Ambient operating temperature - max40 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts6
Heat dissipation per pole, current-dependent Pvid7.5 W
Rated operational current for specified heat dissipation (In)100 A
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)760 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)740 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)590 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)420 A
Rated operational current (Ie)100 A at AC-3, 230 V star-delta; 29.4 A at AC-3, 690 V star-delta; 95.3 A at AC-3, 400 V star-delta; 76.2 A at AC-3, 500 V star-delta
Rated operational current (Ie) at AC-21, 440 V100 A
Rated operational current (Ie) at AC-23A, 230 V100 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V100 A
Rated operational current (Ie) at AC-23A, 500 V55 A
Rated operational current (Ie) at AC-23A, 690 V32 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V71 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V55 A
Rated operational current (Ie) at AC-3, 500 V44 A
Rated operational current (Ie) at AC-3, 660 V, 690 V17 A
Rated operational power at AC-23A, 220/230 V, 50 Hz30 kW
Rated operational power at AC-23A, 400 V, 50 Hz55 kW
Rated operational power at AC-23A, 500 V, 50 Hz37 kW
Rated operational power at AC-23A, 690 V, 50 Hz30 kW
Rated operational power at AC-3, 380/400 V, 50 Hz30 kW
Rated operational power at AC-3, 415 V, 50 Hz30 kW
Rated operational power at AC-3, 690 V, 50 Hz15 kW
Rated operational power star-delta at 220/230 V, 50 Hz30 kW
Rated operational power star-delta at 380/400 V, 50 Hz45 kW
Rated operational power star-delta at 500 V, 50 Hz45 kW
Rated operational power star-delta at 690 V, 50 Hz22 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)100 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
Enclosure materialPlastic
FeaturesComplete device in housing
Fitted with0 (off) position; Black thumb grip and front plate
Inscription1-0-2
Number of poles3
Degree of protectionIP65
Degree of protection (front side)IP65; NEMA 12
Lifespan, mechanical500,000 Operations
ModelReverser
Mounting methodSurface mounting
Mounting positionAs required
Number of contact units3
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryControl switches
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forGround mounting; Front mounting
Switching angle60 °
TypeChangeover switch
Rated conditional short-circuit current (Iq)2 kA
Rated short-time withstand current (Icw)1,7 kA, Contacts, 1 second
Short-circuit protection rating100 A gG/gL, Fuse, Contacts
Load rating2 x Iₑ (with intermittent operation class 12, 25 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)950 A
Voltage per contact pair in series60 V
Screw sizeM6, Terminal screw
Terminal capacity (flexible with ferrule)2 x (1.5 - 10) mm², ferrule to DIN 46228; 1 x (1 - 25) mm², ferrules to DIN 46228
Terminal capacity (solid/stranded)2 x (2.5 - 16) mm²; 1 x (2.5 - 35) mm²
Tightening torque35.4 lb-in, Screw terminals; 4 Nm, Screw terminals
Rated operation power at AC-3, 400 V30 kW
Rated permanent current Iu100 A
Rated operation current Ie at AC-3, 400 V55 A
With zero (off) positionYes
Housing materialPlastic
With retraction in 0-positionNo
Degree of protection (IP), front sideIP65
Type of electrical connection of main circuitScrew connection
Type of control elementWing knob
Suitable for floor mountingYes
Suitable for front mountingNo
Suitable for distribution board installationNo
Suitable for intermediate mountingNo
Complete device in housingYes
Country of originUnited Kingdom

Properties

MOQ1

Cross-References

Attached Documents