cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Switch 3P+N Recessed (T0-2-8900/E)

Eaton · Switchgear & Protection · Safety Switches · Ireland · eaton.com
Part Number
T0-2-8900/E  ·  HS 8536.90
Switch 3P+N Recessed (T0-2-8900/E)

Eaton T0-2-8900/E Recessed, front IP 65, 3-pole + N switch.

Technical Specifications

Manufacturer part number (MPN)T0-2-8900/E
EAN / GTIN4015082073985
HS code8536.90
Sales unitpcs
Eaton catalogue number207398
Depth86 mm
Height48 mm
Width48 mm
Weight0.108 kg
CertificationsCE; CSA-C22.2 No. 94; IEC/EN 60204; UL; VDE 0660; UL File No.: E36332; IEC/EN 60947; CSA; CSA Class No.: 3211-05; UL Category Control No.: NLRV; CSA File No.: 012528; CSA-C22.2 No. 60947-4-1-14; IEC/EN 60947-3; UL 60947-4-1
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorBlack
Actuator functionMaintained
Actuator typeShort thumb-grip
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid0.6 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid0.6 W
Rated operational current for specified heat dissipation (In)20 A
Static heat dissipation, non-current-dependent Pvs0 W
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)100 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)110 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)80 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)60 A
Rated operational current (Ie) at AC-21, 440 V20 A
Rated operational current (Ie) at AC-23A, 230 V13.3 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V13.3 A
Rated operational current (Ie) at AC-23A, 500 V13.3 A
Rated operational current (Ie) at AC-23A, 690 V7.6 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V11.5 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V11.5 A
Rated operational current (Ie) at AC-3, 500 V9 A
Rated operational current (Ie) at AC-3, 660 V, 690 V4.9 A
Rated operational current (Ie) at DC-13, control switches L/R = 50 ms10 A
Rated operational current (Ie) at DC-21, 240 V1 A
Rated operational current (Ie) at DC-23A, 120 V5 A
Rated operational current (Ie) at DC-23A, 24 V10 A
Rated operational current (Ie) at DC-23A, 240 V5 A
Rated operational current (Ie) at DC-23A, 48 V10 A
Rated operational current (Ie) at DC-23A, 60 V10 A
Rated operational current (Ie) star-delta at AC-3, 220/230 V20 A
Rated operational current (Ie) star-delta at AC-3, 380/400 V20 A
Rated operational current (Ie) star-delta at AC-3, 500 V15.6 A
Rated operational current (Ie) star-delta at AC-3, 690 V8.5 A
Rated operational power at AC-23A, 220/230 V, 50 Hz3 kW
Rated operational power at AC-23A, 400 V, 50 Hz5.5 kW
Rated operational power at AC-23A, 500 V, 50 Hz7.5 kW
Rated operational power at AC-23A, 690 V, 50 Hz5.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz5.5 kW
Rated operational power at AC-3, 415 V, 50 Hz5.5 kW
Rated operational power at AC-3, 500 V, 50 Hz5.5 kW
Rated operational power at AC-3, 690 V, 50 Hz4 kW
Rated operational power star-delta at 220/230 V, 50 Hz5.5 kW
Rated operational power star-delta at 380/400 V, 50 Hz7.5 kW
Rated operational power star-delta at 500 V, 50 Hz7.5 kW
Rated operational power star-delta at 690 V, 50 Hz5.5 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)20 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
Fitted withBlack thumb grip and front plate
Inscription0-1
Number of poles4
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical400,000 Operations
Mounting methodFlush mounting
Mounting positionAs required
Number of contact units2
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryOn-Off switch
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forFront mounting 4-hole; Branch circuits, suitable as motor disconnect, (UL/CSA)
Switching angle90 °
Assigned motor power at 115/120 V, 60 Hz, 1-phase0.5 HP
Assigned motor power at 200/208 V, 60 Hz, 1-phase1 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase3 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase1.5 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase3 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase7.5 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase7.5 HP
Rated conditional short-circuit current (Iq)6 kA
Rated short-time withstand current (Icw)0.32 kA; 320 A, Contacts, 1 second
Short-circuit current rating (basic rating)5 kA, SCCR (UL/CSA); 50A, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault)20 A, Class J, max. Fuse, SCCR (UL/CSA); 10 kA, SCCR (UL/CSA)
Short-circuit protection rating20 A gG/gL, Fuse, Contacts
Load rating2 x Iₑ (with intermittent operation class 12, 25 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
Number of contacts in series at DC-21A, 240 V1
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V1
Number of contacts in series at DC-23A, 240 V5
Number of contacts in series at DC-23A, 48 V2
Number of contacts in series at DC-23A, 60 V3
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)130 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)P300 (UL/CSA); A600 (UL/CSA)
Switching capacity (main contacts, general use)16 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series60 V
Screw sizeM3.5, Terminal screw
Terminal capacity18 - 14 AWG, solid or flexible with ferrule; 2 x (1 - 2.5) mm², solid or stranded; 1 x (1 - 2.5) mm², solid or stranded; 2 x (0.75 - 2.5) mm², flexible with ferrules to DIN 46228; 1 x (0.75 - 2.5) mm², flexible with ferrules to DIN 46228
Tightening torque8.8 lb-in, Screw terminals; 1 Nm, Screw terminals

Properties

MOQ1

Cross-References