cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Cam switch, On/Off (P3-100/IVS)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
P3-100/IVS  ·  HS 8536.90
Cam switch, On/Off (P3-100/IVS)

Eaton P3-100/IVS Switch, bottom-mounted module, front IP 30.

Technical Specifications

Manufacturer part number (MPN)P3-100/IVS
EAN / GTIN4015080814399
HS code8536.90
Sales unitpcs
Eaton catalogue number081439
Depth90 mm
Height90 mm
Width90 mm
Weight0.288 kg
CertificationsUL File No.: E36332; CE; UL 60947-4-1; UL Category Control No.: NLRV; IEC/EN 60204; CSA Class No.: 3211-05; IEC/EN 60947; IEC/EN 60947-3; CSA File No.: 012528; CSA-C22.2 No. 94; VDE 0660; CSA-C22.2 No. 60947-4-1-14; CSA; UL
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorBlack
Actuator typeShort thumb-grip
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid7.5 W
Rated operational current for specified heat dissipation (In)100 A
Static heat dissipation, non-current-dependent Pvs0 W
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)760 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)740 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)880 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)520 A
Rated operational current (Ie) at AC-21, 440 V100 A
Rated operational current (Ie) at AC-23A, 230 V100 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V100 A
Rated operational current (Ie) at AC-23A, 500 V96 A
Rated operational current (Ie) at AC-23A, 690 V68 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V71 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V71 A
Rated operational current (Ie) at AC-3, 500 V65 A
Rated operational current (Ie) at AC-3, 660 V, 690 V23.8 A
Rated operational current (Ie) at DC-23A, 120 V25 A
Rated operational current (Ie) at DC-23A, 24 V50 A
Rated operational current (Ie) at DC-23A, 48 V50 A
Rated operational current (Ie) at DC-23A, 60 V50 A
Rated operational power at AC-23A, 220/230 V, 50 Hz30 kW
Rated operational power at AC-23A, 400 V, 50 Hz55 kW
Rated operational power at AC-23A, 500 V, 50 Hz55 kW
Rated operational power at AC-23A, 690 V, 50 Hz55 kW
Rated operational power at AC-3, 380/400 V, 50 Hz37 kW
Rated operational power at AC-3, 415 V, 50 Hz37 kW
Rated operational power at AC-3, 500 V, 50 Hz45 kW
Rated operational power at AC-3, 690 V, 50 Hz37 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)100 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
Fitted withBlack thumb grip and front plate
Locking facilityLockable in the 0 (Off) position
Number of poles3
AccessoriesAuxiliary contact or neutral conductor fitted by user.
Degree of protectionNEMA Other
Degree of protection (front side)IP30
Lifespan, mechanical100,000 Operations
Mounting methodService distribution board mounting
Mounting positionAs required
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryOn-Off switch
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forDistribution board installation; Branch circuits, suitable as motor disconnect, (UL/CSA)
Assigned motor power at 115/120 V, 60 Hz, 1-phase5 HP
Assigned motor power at 200/208 V, 60 Hz, 1-phase10 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase20 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase15 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase25 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase60 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase75 HP
Rated conditional short-circuit current (Iq)4 kA (Load side); 80 kA (Supply side)
Rated short-time withstand current (Icw)2 kA
Short-circuit current rating (basic rating)10 kA, SCCR (UL/CSA); 150A, max. Fuse, SCCR (UL/CSA)
Short-circuit protection rating100 A gG/gL, Fuse, Contacts
Load rating2 x Iₑ (with intermittent operation class 12, 25 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V1
Number of contacts in series at DC-23A, 48 V2
Number of contacts in series at DC-23A, 60 V2
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)950 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600 (UL/CSA); P600 (UL/CSA)
Switching capacity (main contacts, general use)100 A, If used with neutral conductor IU = max. 90 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series60 V
Screw sizeM5, Terminal screw
Terminal capacity1 x (2.5 - 35) mm², solid or stranded; 1 x (1.5 - 25) mm², flexible with ferrules to DIN 46228; 2 x (2.5 - 10) mm², solid or stranded; 14 - 2 AWG, solid or flexible with ferrule; 2 x (1.5 - 6) mm², flexible with ferrules to DIN 46228
Tightening torque3 Nm, Screw terminals; 26.5 lb-in, Screw terminals

Properties

MOQ1

Cross-References

Attached Documents