cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Switch 3P Recessed (P3-63/EA/Svb)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
P3-63/EA/SVB  ·  HS 8536.50
Safety Switch 3P Recessed (P3-63/EA/Svb)

Eaton P3-63/EA/SVB Recessed mounting - Iu=63A, 230V/18,5kW 400V/37kW.

Technical Specifications

Manufacturer part number (MPN)P3-63/EA/SVB
EAN / GTIN4015080316077
Sales unitpcs
Eaton catalogue number031607
Depth128 mm
Height102 mm
Width87 mm
Weight0.426 kg
CertificationsUL; UL Category Control No.: NLRV; IEC/EN 60947; CSA Class No.: 3211-05; CSA-C22.2 No. 60947-4-1-14; CSA File No.: 012528; UL 60947-4-1; CE; UL File No.: E36332; VDE 0660; IEC/EN 60204; CSA-C22.2 No. 94; CSA; IEC/EN 60947-3
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorRed
Actuator typeDoor coupling rotary drive
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Heat dissipation per pole, current-dependent Pvid4.5 W
Rated operational current for specified heat dissipation (In)63 A
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)640 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)600 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)590 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)340 A
Rated operational current (Ie) at AC-21, 440 V63 A
Rated operational current (Ie) at AC-23A, 230 V63 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V63 A
Rated operational current (Ie) at AC-23A, 500 V63 A
Rated operational current (Ie) at AC-23A, 690 V63 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V51 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V55 A
Rated operational current (Ie) at AC-3, 500 V44 A
Rated operational current (Ie) at AC-3, 660 V, 690 V22.1 A
Rated operational current (Ie) at DC-23A, 120 V25 A
Rated operational current (Ie) at DC-23A, 24 V50 A
Rated operational current (Ie) at DC-23A, 48 V50 A
Rated operational current (Ie) at DC-23A, 60 V50 A
Rated operational power at AC-23A, 220/230 V, 50 Hz18.5 kW
Rated operational power at AC-23A, 400 V, 50 Hz30 kW
Rated operational power at AC-23A, 500 V, 50 Hz45 kW
Rated operational power at AC-23A, 690 V, 50 Hz55 kW
Rated operational power at AC-3, 380/400 V, 50 Hz30 kW
Rated operational power at AC-3, 415 V, 50 Hz30 kW
Rated operational power at AC-3, 500 V, 50 Hz30 kW
Rated operational power at AC-3, 690 V, 50 Hz30 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)63 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as emergency stop installation; Version as maintenance-/service switch; Version as main switch
Fitted withRed rotary handle and yellow locking ring
FunctionsEmergency switching off function; Interlockable
Locking facilityLockable in the 0 (Off) position
Number of poles3
AccessoriesAuxiliary contact or neutral conductor fitted by user.
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical100,000 Operations
Mounting methodFlush mounting
Mounting positionAs required
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forBranch circuits, suitable as motor disconnect, (UL/CSA); Front mounting 4-hole
Assigned motor power at 115/120 V, 60 Hz, 1-phase3 HP
Assigned motor power at 200/208 V, 60 Hz, 1-phase7.5 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase15 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase10 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase15 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase40 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase50 HP
Rated conditional short-circuit current (Iq)4 kA (Load side); 100 kA (Supply side)
Rated short-time withstand current (Icw)1.26 kA
Short-circuit current rating (basic rating)10 kA, SCCR (UL/CSA); 150A, max. Fuse, SCCR (UL/CSA)
Short-circuit protection rating80 A gG/gL, Fuse, Contacts
Load rating2 x Iₑ (with intermittent operation class 12, 25 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor)
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V1
Number of contacts in series at DC-23A, 48 V2
Number of contacts in series at DC-23A, 60 V2
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)800 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600 (UL/CSA); P600 (UL/CSA)
Switching capacity (main contacts, general use)60 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series60 V
Screw sizeM5, Terminal screw
Terminal capacity1 x (2.5 - 35) mm², solid or stranded; 2 x (2.5 - 10) mm², solid or stranded; 14 - 2 AWG, solid or flexible with ferrule; 1 x (1.5 - 25) mm², flexible with ferrules to DIN 46228; 2 x (1.5 - 6) mm², flexible with ferrules to DIN 46228
Tightening torque3 Nm, Screw terminals; 26.5 lb-in, Screw terminals
Country of originUnited Kingdom

Properties

MOQ1

Cross-References

Attached Documents