cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

3P Cam switch

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
P1-25/E  ·  HS 8536.90
3P Cam switch

Eaton P1-25/E Recessed, front IP 65, 3-pole switch.

Technical Specifications

Manufacturer part number (MPN)P1-25/E
EAN / GTIN4015080387244
HS code8536.90
Sales unitpcs
Eaton catalogue number038724
Depth94 mm
Height70 mm
Width49 mm
Weight0.141 kg
CertificationsCSA File No.: 012528; UL 60947-4-1; CE; IEC/EN 60947; CSA Class No.: 3211-05; UL Category Control No.: NLRV; VDE 0660; IEC/EN 60204; CSA-C22.2 No. 60947-4-1-14; IEC/EN 60947-3; UL File No.: E36332; CSA-C22.2 No. 94; UL; CSA
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorBlack
Actuator typeShort thumb-grip
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid1.1 W
Rated operational current for specified heat dissipation (In)25 A
Static heat dissipation, non-current-dependent Pvs0 W
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)190 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)150 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)170 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)150 A
Rated operational current (Ie) at AC-21, 440 V25 A
Rated operational current (Ie) at AC-23A, 230 V25 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V25 A
Rated operational current (Ie) at AC-23A, 500 V17.4 A
Rated operational current (Ie) at AC-23A, 690 V12.6 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V19.6 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V15.2 A
Rated operational current (Ie) at AC-3, 500 V12.1 A
Rated operational current (Ie) at AC-3, 660 V, 690 V8.8 A
Rated operational current (Ie) at DC-23A, 120 V12 A
Rated operational current (Ie) at DC-23A, 24 V25 A
Rated operational current (Ie) at DC-23A, 48 V25 A
Rated operational current (Ie) at DC-23A, 60 V25 A
Rated operational power at AC-23A, 220/230 V, 50 Hz5.5 kW
Rated operational power at AC-23A, 400 V, 50 Hz13 kW
Rated operational power at AC-23A, 500 V, 50 Hz11 kW
Rated operational power at AC-23A, 690 V, 50 Hz11 kW
Rated operational power at AC-3, 380/400 V, 50 Hz7.5 kW
Rated operational power at AC-3, 415 V, 50 Hz7.5 kW
Rated operational power at AC-3, 690 V, 50 Hz7.5 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)25 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
Fitted withBlack thumb grip and front plate
Number of poles3
AccessoriesAuxiliary contact or neutral conductor fitted by user.
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical300,000 Operations
Mounting methodFlush mounting
Mounting positionAs required
Operating frequency1200 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryOn-Off switch
Rated impulse withstand voltage (Uimp)6000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable forBranch circuits, suitable as motor disconnect, (UL/CSA); Front mounting 4-hole
Assigned motor power at 115/120 V, 60 Hz, 1-phase1 HP
Assigned motor power at 200/208 V, 60 Hz, 1-phase2 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase3 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase3 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase5 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase10 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase15 HP
Rated conditional short-circuit current (Iq)80 kA
Rated short-time withstand current (Icw)640 A, Contacts, 1 second; 0.64 kA
Short-circuit current rating (basic rating)5 kA, SCCR (UL/CSA); 110A, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault)50 A, Class J, max. Fuse, SCCR (UL/CSA); 10 kA, SCCR (UL/CSA)
Short-circuit protection rating25 A gG/gL, Fuse, Contacts
Load rating1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 2 x Iₑ (with intermittent operation class 12, 25 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V1
Number of contacts in series at DC-23A, 48 V2
Number of contacts in series at DC-23A, 60 V2
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)240 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600 (UL/CSA); P600 (UL/CSA)
Switching capacity (main contacts, general use)20 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series60 V
Screw sizeM4, Terminal screw
Terminal capacity2 x (1 - 4) mm², flexible with ferrules to DIN 46228; 2 x (1.5 - 6) mm², solid or stranded; 1 x (1.5 - 6) mm², solid or stranded; 1 x (1 - 4) mm², flexible with ferrules to DIN 46228; 14 - 8 AWG, solid or flexible with ferrule
Tightening torque1.6 Nm, Screw terminals; 14.1 lb-in, Screw terminals

Properties

MOQ1

Cross-References

Attached Documents