cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Switch (DMM-125/3/M4/P-R)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
DMM-125/3/M4/P-R  ·  HS 8536.50
Safety Switch (DMM-125/3/M4/P-R)

Technical Specifications

Manufacturer part number (MPN)DMM-125/3/M4/P-R
EAN / GTIN8711426320871
Sales unitpcs
Eaton catalogue number6094964
Depth155 mm
Height115 mm
Width137 mm
Weight0.9 kg
CertificationsIEC/EN 60204; IEC/EN 60947-3; EAC; IEC/EN 60947; Lloyds; VDE 0660; RoHS; KEMA; CE
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid4.9 W
Heat dissipation per pole, current-dependent Pvid4.5 W
Rated operational current for specified heat dissipation (In)125 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)1000 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)528 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)336 A
Rated insulation voltage (Ui)1000 V
Rated operational current (Ie) at AC-21, 400 V, 415 V125 A
Rated operational current (Ie) at AC-21, 500 V125 A
Rated operational current (Ie) at AC-21, 690 V125 A
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V125 A
Rated operational current (Ie) at AC-22, 500 V125 A
Rated operational current (Ie) at AC-22, 690 V125 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V63 A
Rated operational current (Ie) at AC-23A, 500 V63 A
Rated operational current (Ie) at AC-23A, 690 V45 A
Rated operational power at AC-23A, 400 V, 50 Hz30 kW
Rated operational power at AC-23A, 500 V, 50 Hz45 kW
Rated operational power at AC-23A, 690 V, 50 Hz40 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)125 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as emergency stop installation; Version as main switch; Version as maintenance-/service switch
Fitted withRed rotary handle and yellow locking ring; Metal shaft for a control panel depth of 400 mm
FunctionsEmergency switching off function; Interlockable
Number of polesThree-pole
AccessoriesAuxiliary contact fitted by user.
Actuator colorRed
Actuator typeLong turning handle
Degree of protectionNEMA Other
Degree of protection (front side)IP20
Lifespan, mechanical10,000 Operations
Mounting methodRear mounting
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch Switch-disconnector
Rated impulse withstand voltage (Uimp)6000 V
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Suitable forDistribution board installation; Ground mounting
Breaking current13.7 kA
Light-through energyMax. 134 kA²s
Rated conditional short-circuit current (Iq)50 kA; 30 kA at 415 V
Rated short-time withstand current (Icw)2.5 kA; 2,5 kA, Contacts, 1 second
Short-circuit protection rating125, Fuse, Contacts
Stripping length (main cable)21 mm
Terminal capacity6 - 70 mm², flexible with ferrules to DIN 46228
Tightening torque7 Nm, Screw terminals
Country of originNetherlands

Properties

MOQ1

Cross-References

Attached Documents