cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Switch (P5-315/V/SVB)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
P5-315/V/SVB  ·  HS 8536.50
Safety Switch (P5-315/V/SVB)

Technical Specifications

Manufacturer part number (MPN)P5-315/V/SVB
EAN / GTIN4015082809560
Sales unitpcs
Eaton catalogue number280956
Depth150 mm
Height150 mm
Width130 mm
Weight2.168 kg
CertificationsCE; CSA-C22.2 No. 14-05; IEC/EN 60204; CSA; CSA File No.: 223805; UL Category Control No.: NLRV
NLRV7; UL 508; CSA-C22.2 No. 94; UL; UL File No.E36332; CSA Class No.: 3211-05; IEC/EN 60947-3; IEC/EN 60947; VDE 0660
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorRed
Actuator typeDoor coupling rotary drive
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid12.7 W
Heat dissipation per pole, current-dependent Pvid12.7 W
Rated operational current for specified heat dissipation (In)315 A
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)1800 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)1650 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)1550 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)400 A
Rated operational current (Ie) at AC-21
440 V315 A
Rated operational current (Ie) at AC-23A
230 V182 A
Rated operational current (Ie) at AC-23A, 400 V
415 V205 A
Rated operational current (Ie) at AC-23A
500 V184 A
Rated operational current (Ie) at AC-23A
690 V50 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V147 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V138 A
Rated operational current (Ie) at AC-3
500 V135 A
Rated operational current (Ie) at AC-3, 660 V
Rated operational current (Ie) at DC-23A
120 V100 A
Rated operational current (Ie) at DC-23A
24 V315 A
Rated operational current (Ie) at DC-23A
48 V315 A
Rated operational current (Ie) at DC-23A
60 V315 A
Rated operational power at AC-23A, 220/230 V
50 Hz55 kW
Rated operational power at AC-23A, 400 V
50 Hz110 kW
Rated operational power at AC-23A, 500 V
50 Hz132 kW
Rated operational power at AC-23A, 690 V
50 Hz45 kW
Rated operational power at AC-3, 380/400 V
50 Hz75 kW
Rated operational power at AC-3, 415 V
Rated operational power at AC-3, 500 V
50 Hz90 kW
Rated operational power at AC-3, 690 V
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)315 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as emergency stop installation; Version as main switch; Version as maintenance-/service switch
Fitted withRed rotary handle and yellow locking ring
FunctionsInterlockable; Emergency switching off function
Locking facilityLockable in the 0 (Off) position
Number of poles3
AccessoriesAuxiliary contact or neutral conductor fitted by user.
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical80,000 Operations
Mounting methodRear mounting
Mounting positionAs required
Operating frequency50 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch
Rated impulse withstand voltage (Uimp)8000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Suitable forBranch circuits, suitable as motor disconnect, (UL/CSA); Intermediate mounting
Assigned motor power at 115/120 V, 60 Hz
1-phase20 HP
Assigned motor power at 115/120 V, 60 Hz
3-phase40 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase35 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase75 HP
Assigned motor power at 277 V, 60 Hz
Assigned motor power at 460/480 V, 60 Hz
3-phase100 HP
Assigned motor power at 575/600 V, 60 Hz
Rated conditional short-circuit current (Iq)15 kA
Rated short-time withstand current (Icw)5.8 kA; 5,8 kA, Contacts, 1 second
Short-circuit current rating (basic rating)800A Class RK1, max. Fuse, SCCR (UL/CSA); 10 kA, SCCR (UL/CSA)
Short-circuit current rating (high fault)400 A, Class J, max. Fuse, SCCR (UL/CSA); 65 kA, SCCR (UL/CSA)
Short-circuit protection rating315 A gG/gL, Fuse, Contacts
Load rating1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor); 2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
Number of contacts in series at DC-23A
120 V3
Number of contacts in series at DC-23A
24 V3
Number of contacts in series at DC-23A
48 V3
Number of contacts in series at DC-23A
60 V3
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)2050 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600 (UL/CSA)
Switching capacity (main contacts, general use)300 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series42 V
Screw size6 mm AF, Hexagon socket-head spanner, Terminal screw
Tightening torque140 lb-in, Screw terminals; 16 Nm, Screw terminals
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents