cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Switch (P5-160/V/SVB/N)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
P5-160/V/SVB/N  ·  HS 8536.50
Safety Switch (P5-160/V/SVB/N)

Technical Specifications

Manufacturer part number (MPN)P5-160/V/SVB/N
EAN / GTIN4015082809300
Sales unitpcs
Eaton catalogue number280930
Depth150 mm
Height150 mm
Width130 mm
Weight1.637 kg
CompliancesCE Marked
CertificationsIEC 60947; CSA Std. C22.2 No. 14-05; EN 60947-3; UL 508; VDE; CSA Class No.: 3211-05; IEC/EN 60204; UL File No.: E36332; CSA-C22.2 No. 94; IEC/EN 60947; CSA File No.: 223805; IEC/EN 60947-3; UL Category Control No.: NLRV, NLRV7; CSA; CSA-C22.2 No. 14-05; UL; VDE 0660; CE
Catalog NotesRated Short-time Withstand Current (Icw) for a time of 1 second
Actuator colorRed
Actuator typeDoor coupling rotary drive
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Control circuit reliability1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid5 W
Heat dissipation per pole, current-dependent Pvid5 W
Rated operational current for specified heat dissipation (In)160 A
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)900 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)850 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)850 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)340 A
Rated operational current (Ie) at AC-21, 440 V160 A
Rated operational current (Ie) at AC-23A, 230 V103 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V105 A
Rated operational current (Ie) at AC-23A, 500 V106 A
Rated operational current (Ie) at AC-23A, 690 V42 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V103 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V85 A
Rated operational current (Ie) at AC-3, 500 V80 A
Rated operational current (Ie) at AC-3, 660 V, 690 V42 A
Rated operational current (Ie) at DC-23A, 120 V50 A
Rated operational current (Ie) at DC-23A, 24 V160 A
Rated operational current (Ie) at DC-23A, 48 V160 A
Rated operational current (Ie) at DC-23A, 60 V160 A
Rated operational power at AC-23A, 220/230 V, 50 Hz30 kW
Rated operational power at AC-23A, 400 V, 50 Hz55 kW
Rated operational power at AC-23A, 500 V, 50 Hz75 kW
Rated operational power at AC-23A, 690 V, 50 Hz37 kW
Rated operational power at AC-3, 380/400 V, 50 Hz45 kW
Rated operational power at AC-3, 415 V, 50 Hz45 kW
Rated operational power at AC-3, 500 V, 50 Hz55 kW
Rated operational power at AC-3, 690 V, 50 Hz37 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)160 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as emergency stop installation; Version as main switch; Version as maintenance-/service switch
Fitted withRed rotary handle and yellow locking ring
FunctionsInterlockable; Emergency switching off function
Locking facilityLockable in the 0 (Off) position
Number of poles4
AccessoriesAuxiliary contact fitted by user.
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical100,000 Operations
Mounting methodRear mounting
Mounting positionAs required
Operating frequency50 Operations/h
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch
Rated impulse withstand voltage (Uimp)8000 V AC
Safe isolation440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Suitable forBranch circuits, suitable as motor disconnect, (UL/CSA); Intermediate mounting
Assigned motor power at 115/120 V, 60 Hz, 1-phase10 HP
Assigned motor power at 115/120 V, 60 Hz, 3-phase20 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase25 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase40 HP
Assigned motor power at 277 V, 60 Hz, 1-phase25 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase60 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase60 HP
Rated conditional short-circuit current (Iq)30 kA
Rated short-time withstand current (Icw)3 kA; 3 kA, Contacts, 1 second
Short-circuit current rating (basic rating)10 kA, SCCR (UL/CSA); 400A Class RK1, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault)300 A, Class J, max. Fuse, SCCR (UL/CSA); 65 kA, SCCR (UL/CSA)
Short-circuit protection rating160 A gG/gL, Fuse, Contacts
Load rating1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
Number of contacts in series at DC-23A, 120 V3
Number of contacts in series at DC-23A, 24 V3
Number of contacts in series at DC-23A, 48 V3
Number of contacts in series at DC-23A, 60 V3
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)1050 A
Switching capacity (auxiliary contacts, general use)10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600 (UL/CSA)
Switching capacity (main contacts, general use)200 A, Rated uninterrupted current max. (UL/CSA)
Voltage per contact pair in series42 V
Screw size5 mm AF, Hexagon socket-head spanner, Terminal screw
Tightening torque125 lb-in, Screw terminals; 14 Nm, Screw terminals
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents