| Manufacturer part number (MPN) | T5-1-102/EA/SVB |
| EAN / GTIN | 4015080988083 |
| Sales unit | pcs |
| Eaton catalogue number | 098808 |
| Depth | 123 mm |
| Height | 88 mm |
| Width | 88 mm |
| Weight | 0.47 kg |
| Certifications | VDE 0660; IEC/EN 60947; IEC/EN 60947-3; IEC/EN 60204 |
| Catalog Notes | Rated Short-time Withstand Current (Icw) for a time of 1 second |
| Actuator color | Red |
| Actuator type | Door coupling rotary drive |
| Ambient operating temperature - max | 50 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Control circuit reliability | 1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA) |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Heat dissipation per pole, current-dependent Pvid | 7.5 W |
| Rated operational current for specified heat dissipation (In) | 100 A |
| Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3) | 760 A |
| Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) | 740 A |
| Rated breaking capacity at 500 V (cos phi to IEC 60947-3) | 590 A |
| Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3) | 420 A |
| Rated operational current (Ie) at AC-21, 440 V | 100 A |
| Rated operational current (Ie) at AC-23A, 230 V | 100 A |
| Rated operational current (Ie) at AC-23A, 400 V, 415 V | 100 A |
| Rated operational current (Ie) at AC-23A, 500 V | 55 A |
| Rated operational current (Ie) at AC-23A, 690 V | 32 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 71 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 55 A |
| Rated operational current (Ie) at AC-3, 500 V | 44 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 17 A |
| Rated operational current (Ie) star-delta at AC-3, 220/230 V | 100 A |
| Rated operational current (Ie) star-delta at AC-3, 380/400 V | 95.3 A |
| Rated operational current (Ie) star-delta at AC-3, 500 V | 76.2 A |
| Rated operational current (Ie) star-delta at AC-3, 690 V | 29.4 A |
| Rated operational power at AC-23A, 220/230 V, 50 Hz | 30 kW |
| Rated operational power at AC-23A, 400 V, 50 Hz | 55 kW |
| Rated operational power at AC-23A, 500 V, 50 Hz | 37 kW |
| Rated operational power at AC-23A, 690 V, 50 Hz | 30 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 30 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 30 kW |
| Rated operational power at AC-3, 500 V, 50 Hz | 30 kW |
| Rated operational power at AC-3, 690 V, 50 Hz | 15 kW |
| Rated operational power star-delta at 220/230 V, 50 Hz | 30 kW |
| Rated operational power star-delta at 380/400 V, 50 Hz | 45 kW |
| Rated operational power star-delta at 500 V, 50 Hz | 45 kW |
| Rated operational power star-delta at 690 V, 50 Hz | 22 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated uninterrupted current (Iu) | 100 A |
| Uninterrupted current | Rated uninterrupted current Iu is specified for max. cross-section. |
| Features | Version as main switch; Version as maintenance-/service switch; Version as emergency stop installation |
| Fitted with | Red rotary handle and yellow locking ring |
| Functions | Interlockable; Emergency switching off function |
| Locking facility | Lockable in the 0 (Off) position |
| Number of poles | 2 |
| Degree of protection | NEMA 12 |
| Degree of protection (front side) | IP65 |
| Lifespan, mechanical | 500,000 Operations |
| Mounting method | Flush mounting |
| Mounting position | As required |
| Number of contact units | 1 |
| Operating frequency | 1200 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product Category | Main switch |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Safe isolation | 440 V AC, Between the contacts, According to EN 61140 |
| Safety parameter (EN ISO 13849-1) | B10d values as per EN ISO 13849-1, table C.1 |
| Shock resistance | 15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms |
| Suitable for | Front mounting center |
| Switching angle | 90 ° |
| Rated conditional short-circuit current (Iq) | 2 kA |
| Rated short-time withstand current (Icw) | 1.7 kA; 1,7 kA, Contacts, 1 second |
| Short-circuit protection rating | 100 A gG/gL, Fuse, Contacts |
| Load rating | 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor); 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor); 2 x Iₑ (with intermittent operation class 12, 25 % duty factor) |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3) | 950 A |
| Switching capacity (main contacts, general use) | 63 A, Rated uninterrupted current max. (UL/CSA) |
| Voltage per contact pair in series | 60 V |
| Screw size | M6, Terminal screw |
| Terminal capacity | 1 x (2.5 - 35) mm², solid or stranded; 1 x (1 - 25) mm², flexible with ferrules to DIN 46228; 2 x (1.5 - 10) mm², flexible with ferrule to DIN 46228; 2 x (2.5 - 16) mm², solid or stranded |
| Tightening torque | 35.4 lb-in, Screw terminals; 4 Nm, Screw terminals |
| Country of origin | United Kingdom |