Danfoss TWA-L electrothermal actuator, 230 V AC, normally closed (088H3132)

Danfoss · HVAC & Refrigeration · Valve Actuators · Denmark · danfoss.com
Part Number
088H3132  ·  HS 8481.90
Danfoss TWA-L electrothermal actuator, 230 V AC, normally closed (088H3132)

Danfoss TWA-L electrothermal (thermal-wax) valve actuator, OEM order code 088H3132. The TWA-L converts a switching signal from a room thermostat or controller into valve movement on hydronic floor-heating manifolds and radiator/zone valves — no auxiliary air or hydraulics. Normally closed (NC) — the valve is closed when de-energised and opens when the actuator is powered. Supply voltage 230 V AC (50/60 Hz), power consumption 2 W. RAVL connection; fits Danfoss RAVL valve bodies. 0.95 m connecting cable. Enclosure rating IP41. Net weight 138 Gram. Genuine Danfoss part; technical data quoted verbatim from store.danfoss.com (code 088H3132). OEM P/N 088H3132, EAN 5702420049502.

Technical Specifications

BrandDanfoss
Part number088H3132
TypeTWA-L
Product groupThermal actuators
DescriptionTWA-L NC 230V
Actuator principleElectrothermal (thermal wax element)
Valve functionNC
End-switchNo
Supply voltage230 V AC
Frequency range50 Hz – 60 Hz
Power consumption2 W
ConnectionRAVL
Connection typeRAVL
Cable length0.95 m
IP protection classIP41
REACH candidate-list substancesLead (CAS no. 7439-92-1)
Net weight138 Gram
Gross weight139.777 Gram
EAN5702420049502
HS code8481.90 (parts of taps, cocks, valves and similar appliances)

Properties

MaterialPolyamide housing
IP ratingIP41
MOQ1

Compatibility

Electrothermal actuator for Danfoss RAVL valve bodies. Signalled by a 24 V or 230 V AC room-thermostat/controller output — match the supply voltage (230 V AC) and valve function (normally closed) to the control system. Confirm the valve connection (RAVL) against the manifold or valve body before ordering.