Danfoss interchangeable orifice assembly (ORF) no. 04 for the TE 5 thermostatic expansion valve. R134a 28 kW, R22 42 kW, R404A/R507A 35 kW, R407A 42 kW, R407C 46 kW, R407F 46 kW, R1234yf 25 kW. Compatible refrigerants: R22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf. Fits the TE 5 valve body of the TE parts program.
| Type | Orifice assembly (ORF, thermostatic expansion valve) |
| Used for | TE 5 |
| Orifice no. | 04 |
| Refrigerants | R22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf |
| Rated capacity (Range N) | R134a 28 kW, R22 42 kW, R404A/R507A 35 kW, R407A 42 kW, R407C 46 kW, R407F 46 kW, R1234yf 25 kW |
| Rating basis | te 4.4 °C, tc 38 °C, tliq 37 °C (ARI) |
| Net weight | 0.102 kg / Gross: 0.136 kg |
| EAN | 5702428320993 |
| Code number | 067B2792 |
| Product group | Expansion valves |
| Orifice size | 04 |
| Approval | EAC; LLC CDC TYSK |
| REACH candidate-list substances | Lead (CAS no. 7439-92-1) |
| Rated cap. cond. Range N [IMP] | tcond=100 °F; tevap=40 °F; tliq=98 °F |
| Rated cap. R134a | |
| Range N | 28.00 kW, 8.00 TR |
| Rated cap. R22 | |
| Range B | 28.20 kW, 8.02 TR |
| Rated cap. R22 | |
| Range N | 42.00 kW, 12.00 TR |
| Rated cap. R404A | |
| Range B | 18.30 kW, 5.21 TR |
| Rated cap. R404A | |
| Range N | 35.00 kW, 10.00 TR |
| Rated cap. R407A | |
| Range N | 42.00 kW, 12.00 TR |
| Rated cap. R407C | |
| Range N | 46.00 kW, 13.00 TR |
| Rated cap. R407F | |
| Range N | 46.00 kW, 13.00 TR |
| Rated cap. R454C | |
| Range N | 40.74 kW, 11.61 TR |
| Rated cap. R507 | |
| Range B | 18.30 kW, 5.21 TR |
| Rated cap. R507 | |
| Range N | 35.00 kW, 10.00 TR |
| Rated cap.R1234yf, Range N [kW | 25.00 kW |
| Rated cap.R1234yf, Range N [TR | 7.00 TR |
| EU RoHS compliance | Yes with exemptions |
| MOQ | 1 |
For the Danfoss TE 5 / TE 12 / TE 20 thermostatic expansion valve parts program. Match refrigerant, orifice/element and body to the same valve size. Verify against your system specification.