Danfoss orifice assembly no. 03 for TE 5 thermostatic expansion valve (code 067B2791)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
067B2791  ·  HS 8481.90
Danfoss orifice assembly no. 03 for TE 5 thermostatic expansion valve (code 067B2791)

Danfoss interchangeable orifice assembly (ORF) no. 03 for the TE 5 thermostatic expansion valve. R134a 21 kW, R22 32 kW, R407A 32 kW, R407C 32 kW, R407F 35 kW, R404A/R507A 25 kW, R1234yf 18 kW. Compatible refrigerants: R22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf. Fits the TE 5 valve body of the TE parts program.

Technical Specifications

TypeOrifice assembly (ORF, thermostatic expansion valve)
Used forTE 5
Orifice no.03
RefrigerantsR22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf
Rated capacity (Range N)R134a 21 kW, R22 32 kW, R407A 32 kW, R407C 32 kW, R407F 35 kW, R404A/R507A 25 kW, R1234yf 18 kW
Rating basiste 4.4 °C, tc 38 °C, tliq 37 °C (ARI)
Net weight0.102 kg / Gross: 0.134 kg
EAN5702428320986
Code number067B2791
Product groupExpansion valves
Orifice size03
ApprovalEAC; LLC CDC TYSK
REACH candidate-list substancesLead (CAS no. 7439-92-1)
Rated cap. cond. Range N [IMP]tcond=100 °F; tevap=40 °F; tliq=98 °F
Rated cap. R134a
Range N21.00 kW, 6.00 TR
Rated cap. R22
Range B21.00 kW, 5.97 TR
Rated cap. R22
Range N32.00 kW, 9.00 TR
Rated cap. R404A
Range B13.60 kW, 3.87 TR
Rated cap. R404A
Range N25.00 kW, 7.00 TR
Rated cap. R407A
Range N32.00 kW, 9.00 TR
Rated cap. R407C
Range N32.00 kW, 9.00 TR
Rated cap. R407F
Range N35.00 kW, 10.00 TR
Rated cap. R454C
Range N29.74 kW, 8.48 TR
Rated cap. R507
Range B13.60 kW, 3.87 TR
Rated cap. R507
Range N25.00 kW, 7.00 TR
Rated cap.R1234yf, Range N [kW18.00 kW
Rated cap.R1234yf, Range N [TR5.00 TR
EU RoHS complianceYes with exemptions

Properties

MOQ1

Compatibility

For the Danfoss TE 5 / TE 12 / TE 20 thermostatic expansion valve parts program. Match refrigerant, orifice/element and body to the same valve size. Verify against your system specification.

Standards

Approvals