Danfoss interchangeable orifice assembly (ORF) no. 03 for the TE 5 thermostatic expansion valve. R134a 21 kW, R22 32 kW, R407A 32 kW, R407C 32 kW, R407F 35 kW, R404A/R507A 25 kW, R1234yf 18 kW. Compatible refrigerants: R22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf. Fits the TE 5 valve body of the TE parts program.
| Type | Orifice assembly (ORF, thermostatic expansion valve) |
| Used for | TE 5 |
| Orifice no. | 03 |
| Refrigerants | R22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf |
| Rated capacity (Range N) | R134a 21 kW, R22 32 kW, R407A 32 kW, R407C 32 kW, R407F 35 kW, R404A/R507A 25 kW, R1234yf 18 kW |
| Rating basis | te 4.4 °C, tc 38 °C, tliq 37 °C (ARI) |
| Net weight | 0.102 kg / Gross: 0.134 kg |
| EAN | 5702428320986 |
| Code number | 067B2791 |
| Product group | Expansion valves |
| Orifice size | 03 |
| Approval | EAC; LLC CDC TYSK |
| REACH candidate-list substances | Lead (CAS no. 7439-92-1) |
| Rated cap. cond. Range N [IMP] | tcond=100 °F; tevap=40 °F; tliq=98 °F |
| Rated cap. R134a | |
| Range N | 21.00 kW, 6.00 TR |
| Rated cap. R22 | |
| Range B | 21.00 kW, 5.97 TR |
| Rated cap. R22 | |
| Range N | 32.00 kW, 9.00 TR |
| Rated cap. R404A | |
| Range B | 13.60 kW, 3.87 TR |
| Rated cap. R404A | |
| Range N | 25.00 kW, 7.00 TR |
| Rated cap. R407A | |
| Range N | 32.00 kW, 9.00 TR |
| Rated cap. R407C | |
| Range N | 32.00 kW, 9.00 TR |
| Rated cap. R407F | |
| Range N | 35.00 kW, 10.00 TR |
| Rated cap. R454C | |
| Range N | 29.74 kW, 8.48 TR |
| Rated cap. R507 | |
| Range B | 13.60 kW, 3.87 TR |
| Rated cap. R507 | |
| Range N | 25.00 kW, 7.00 TR |
| Rated cap.R1234yf, Range N [kW | 18.00 kW |
| Rated cap.R1234yf, Range N [TR | 5.00 TR |
| EU RoHS compliance | Yes with exemptions |
| MOQ | 1 |