Danfoss TE 55 thermostatic charge (power) element, OEM order code 067G3217. The interchangeable element carries the thermostatic charge that senses evaporator-outlet superheat and drives the TE 55 / TQ 55 expansion valve; it mounts on the valve body (067G4001-4004) and pairs with a matched orifice assembly to complete the valve. This charge is selected for R22/R407C over an evaporating temperature range of -60 to -25 °C (-75 to -15 °F) with a maximum operating pressure limit (MOP 20 psig at -20 °C (-4 °F)). Externally equalized (1/4 in flare), adjustable superheat, 5 m capillary, 28 bar (400 psig) max working pressure, brass. Supplied with bulb strap, gasket, key and O-ring. Data quoted verbatim from store.danfoss.com (code 067G3217).
| Brand | Danfoss |
| Part number | 067G3217 |
| Type | TE 55 (thermostatic expansion valve, parts program) |
| Type designation | Element (thermostatic charge / power head) |
| Used for | TE 55 / TQ 55 thermostatic expansion valves |
| Refrigerant | R22/R407C |
| Pressure equalization | Externally equalized |
| Equalization connection | Flare, 1/4 in |
| Capillary tube length | 5000 mm (197 in) |
| Superheat setting | Adjustable |
| Evaporating temperature range | -60 to -25 °C (-75 to -15 °F) |
| Maximum operating pressure (MOP) | MOP 20 psig at -20 °C (-4 °F) |
| Max working pressure (PS/MWP) | 28 bar (400 psig) |
| Body material | Brass |
| Parts included | Bulb strap, Gasket, Key, O-ring |
| Net weight | 0.69 kg |
| Gross weight | 0.84 kg |
| Packing | 9 pc per multi-pack |
| EAN | 5702428322294 |
| Approvals | EAC, LLC CDC TYSK |
| HS code | 8481.90 (valve parts) |
| Material | Brass; thermostatic charge element with capillary and bulb |
| Pressure rating | 28 bar (400 psig) max working pressure |
| Temperature range | -60 to -25 °C evaporating |
| Primary standard | EN 12284 |
| MOQ | 1 |
Fits Danfoss TE 55 / TQ 55 thermostatic expansion valve bodies. Select the element by refrigerant (R22/R407C), evaporating temperature range (-60 to -25 °C) and MOP (MOP 20), and pair with the correct orifice number for the required capacity. Verify the refrigerant and temperature application before ordering.