Danfoss SVA-HL 150 straightway shut-off valve, 150 mm (6 in) butt weld, steel, 65 bar (code 148B6281)

Danfoss · HVAC & Refrigeration · Globe Valves · Denmark · danfoss.com
Part Number
148B6281  ·  HS 8481.80
Image not available for this product

Danfoss SVA-HL 150 straightway shut-off (stop) valve for industrial refrigeration, code 148B6281. SVA-HL is the SVA valve fitted with the HL packing gland, recommended for applications running with high, constant media temperatures. Low-temperature steel body with butt weld "F" connection (ANSI / ASME B36.10M), nominal size 150 mm (6 in), wall 3 mm, pipe OD 170.3 mm. Maximum working pressure 65 bar (943 psig); media temperature range -60 to 150 C (-76 to 302 F). Flow coefficient Kv 597 m3/h (Cv 693 gal/min) in the straightway direction; can accept flow in both directions. Renewable seat and cone close tightly and withstand high system pulsation and vibration, and can be dismantled and repaired in line. Supplied with cap. For HCFC, non-flammable HFC, R717 (ammonia) and R744 (CO2) systems.

Technical Specifications

TypeSVA-HL 150 shut-off valve (SVL Flexline)
Code number148B6281
SeriesSVA-HL (HL high-temperature packing gland)
DirectionStraightway
Connection typeButt weld ("F")
Connection standardANSI (ASME B36.10M)
Nominal size150 mm (6 in)
Pipe OD170.3 mm; weld wall thickness 3 mm
Body materialSteel (low-temperature carbon steel)
Maximum working pressure65 bar (943 psig)
Media temperature range-60 to 150 C (-76 to 302 F)
Kv value597 m3/h (Cv 693 gal/min), straightway
Flow directionBi-flow
EquipmentCap
PED 2014/68/EU compliant; CE marked above the Article 4.3 threshold.
EAN5715162505564

Properties

MaterialSteel
Pressure rating65 bar
Temperature range-60 to 150 C
Primary standardANSI (ASME B36.10M)
Standard size150 mm
MOQ1

Compatibility

Danfoss SVL Flexline SVA-HL stop valve. This code is the straightway SVA-HL 150 with butt weld "F" ends (ANSI / ASME B36.10M) and a cap. Confirm line size (150 mm (6 in)), connection type/standard, direction (straightway) and refrigerant before ordering. SVA-HL, SVA-S and SVA-L share the same internal parts; SVA-HL adds the HL high-temperature packing gland.