Danfoss SVA-DH 300 angleway shut-off valve, 300 mm (12 in) butt weld ASME B 36.10M Schedule 40, steel, 40 bar, with handwheel (code 148B3777)

Danfoss · HVAC & Refrigeration · Globe Valves · Denmark · danfoss.com
Part Number
148B3777  ·  HS 8481.80
Danfoss SVA-DH 300 angleway shut-off valve, 300 mm (12 in) butt weld ASME B 36.10M Schedule 40, steel, 40 bar, with handwheel (code 148B3777)

Danfoss SVA-DH 300 angleway shut-off (stop) valve for industrial refrigeration, code 148B3777. Low-temperature steel body with butt-weld connections to ASME B 36.10M Schedule 40, nominal size 300 mm (12 in). Maximum working pressure 40 bar (580 psig); media temperature range -60 to 150 C (-76 to 302 F). Flow coefficient Kv 1610 m3/h (Cv 1867.6 gal/min). Delta Pressure High (SVA-DH) is the balanced design without restriction in the opening function; it opens at all differential pressures with limited torque. Both SVA-DL and SVA-DH have internal backseating, so the spindle seal can be replaced while the valve is still under pressure; the valve dismantles in line for inspection and repair. Supplied with handwheel. For HCFC, non-flammable HFC, R717 (ammonia) and R744 (CO2) industrial refrigeration systems. PED category IV.

Technical Specifications

TypeSVA-DH 300 angleway shut-off valve
Code number148B3777
SeriesSVA-DH (Delta Pressure High)
DirectionAngleway
Connection typeButt weld
Connection standardASME B 36.10M Schedule 40
Nominal size300 mm (12 in)
Body materialSteel (reddish-brown paint finish)
Maximum working pressure40 bar (580 psig)
Media temperature range-60 to 150 C (-76 to 302 F)
Kv value1610 m3/h (Cv 1867.6 gal/min)
EquipmentHandwheel
Weightnet weight 187.67 kg, gross weight 231 kg
PED categoryIV
ApprovalsCE, EAC
EAN5702428179119
Net weight187.67 Kilogram
Product groupShut-off and regulating valves
ApprovalCE
CE markYes
China RoHS complianceYes
Colour PaintReddish brown
Connection Code(2002:S40:300)
Cv value [gal/min]1867.6 gal/min
EU RoHS complianceYes
Fluid Group1
Inlet connection size [in]12 in
Inlet connection size [mm]300 mm
Inlet connection typeButt weld
Kv value [m³/h]1610 m³/h
Max. Working Pressure [bar]40 bar
Max. Working Pressure [psig]580 psig
Outlet connection size [in]12 in
Outlet connection size [mm]300 mm
Outlet connection typeButt weld
REACH Candidate List substancesNo
RefrigerantsR113
Temperature range [°C] [max]150 °C
Temperature range [°C] [min]-60 °C
Temperature range [°F] [max]302 °F
Temperature range [°F] [min]-76 °F
Valve versionDelta Pressure High

Properties

MaterialSteel
Pressure rating40 bar
Temperature range-60 to 150 C
Primary standardASME B 36.10M Schedule 40
Standard size300 mm
MOQ1

Compatibility

Danfoss SVA-DH 300 large-size angleway stop valve for industrial refrigeration headers. Confirm line size (300 mm / 12 in), connection standard (ASME B 36.10M Schedule 40), top equipment (handwheel), and Delta-Pressure variant (SVA-DH) before ordering: SVA-DL has a restriction in the opening function for two-step pressure relief, while SVA-DH is balanced for opening at any differential pressure. SVA-DH and SVA-DL share spindle/seat servicing in line.

Approvals