Danfoss SVA-140B 80 function module, code 148B6928 — the complete top part with cap that converts an SVL-140B 80 valve body into a manual shut-off (stop) valve for 140 bar (2030 psig) industrial R744 (CO2) service. Features a balanced piston design for smooth, low-torque opening at high differential pressure and internal metal back-seating. The top part exchanges on an installed body without welding, so a strainer body can be re-tasked as a shut-off valve (and back) simply by swapping the module. Used for products SVL-140B 80. Supplied with 1 gasket. Cap-type spindle prepared for seal-wire against unauthorised operation.
| Type | SVA-140B 80 function module (complete top part) |
| Code number | 148B6928 |
| Series | SVL-140B Flexline (140 bar CO2) |
| Product group | Shut-off and regulating valves |
| Function | Converts SVL-140B body to shut-off (stop) valve |
| Equipment / spindle | Cap |
| Design | Balanced piston, internal metal back seating |
| Parts included | 1 gasket; complete top part |
| Used for products | SVL-140B 80 |
| Maximum working pressure | 140 bar (2030 psig) |
| Maximum differential pressure | 110 bar (1595 psig) |
| Media temperature range | -40 to 150 C (-40 to 302 F) |
| Applicable media | R744 (CO2), sub- and trans-critical |
| CE mark | Yes |
| Approvals | C UL US LISTED, CE, CRN |
| Net weight | 6.95 kg |
| Gross weight | 9.55 kg |
| EAN | 5715162692660 |
| Compatible with | 140 bar CO2 shut-off valve |
| Approval | C UL US LISTED |
| China RoHS compliance | Yes |
| Equipment | Cap |
| EU RoHS compliance | Yes |
| Max. Working Pressure [bar] | 140 bar |
| Max. Working Pressure [psig] | 2030 psig |
| Neck | Standard |
| REACH Candidate List substances | No |
| Refrigerants | R744 |
| Temperature range [°C] [max] | 150 °C |
| Temperature range [°C] [min] | -40 °C |
| Temperature range [°F] [max] | 302 °F |
| Temperature range [°F] [min] | -40 °F |
| Type designation | Top Complete |
| UL mark | Yes |
| Used for product | SVL-140B 80 |
| Material | Low-temperature steel |
| Pressure rating | 140 bar |
| Temperature range | -40 to 150 C |
| MOQ | 1 |
Danfoss SVA-140B shut-off function module (spare top part) for the 140 bar CO2 SVL Flexline. Fits the SVL-140B 80 valve body (SVL-140B 80); the module exchanges on an installed body without welding. Order the matching SVL-140B body separately if not already installed. The FIA-140B strainer module fits the same body for filter duty. Not interchangeable with the 52/65 bar SVL family.