Danfoss SFV 25 back-pressure-dependent safety relief valve, store code 2416+302, set pressure 16 bar g (232 psig), supplied with a TÜV pressure-setting certificate. SFV 20 and SFV 25 are standard, back-pressure-dependent safety relief valves in angle-way execution, designed to protect pressure vessels and other components against excessive pressure in industrial refrigeration plant. On a rise above the set pressure the valve starts to open, is fully open before the pressure is 10% above set pressure, and is fully closed again before the pressure falls 10% below set pressure (DIN 3320 characteristic). The housing is special steel approved for low-temperature operation; the spindle and seat are stainless steel for precise operation, and the valve cone gasket is a special chloroprene (neoprene) compound. The spring housing is closed tightly to avoid refrigerant leakage. After the set pressure is adjusted at Danfoss the valve is sealed, and a metal plate records the flow diameter, set pressure, date of production, production number and type-approved code. Applicable for R717 (ammonia), HFC and HCFC (e.g. R22, R134a, R404A) and R744 (CO2), within a temperature range of -30 to +100 C (-22 to +212 F). The valves are designed for a strength test of 43 bar g (624 psig). It is recommended that the valves be installed in pairs in conjunction with the DSV double stop / change-over valve so one valve can be inspected or replaced while the other keeps the vessel protected. Approved in accordance with the Pressure Equipment Directive (PED) and CE marked; discharge capacity certified to ISO 4126-1 / EN 13136. This code is an SFV 25 (nominal valve size 25 mm (1 in), flow diameter 23 mm (0.906 in), flow area 415 mm2 (0.643 in2)) with G outside-pipe-thread connections per ISO 228/1: inlet G 1 1/4 in, outlet G 1 1/2 in. Set pressure 16 bar g (232 psig); de-rated certified coefficient of discharge Kdr 0.48; valve lift 4.5 mm. PED 2014/68/EU category IV, fluid group I, CE marked. Specifications per Danfoss store code 2416+302.
| Type | SFV 25 safety relief valve (back-pressure-dependent, angle-way) |
| Code number | 2416+302 |
| Set pressure | 16 bar g (232 psig) |
| Pressure certificate | TÜV certificate included |
| Nominal valve size | 25 mm (1 in) |
| Flow diameter | 23 mm (0.906 in) |
| Flow area A0 | 415 mm2 (0.643 in2) |
| De-rated certified coefficient of discharge Kdr | 0.48 |
| Valve lift | 4.5 mm |
| Inlet connection | G 1 1/4 in (ISO 228/1 outside pipe thread) |
| Outlet connection | G 1 1/2 in (ISO 228/1 outside pipe thread) |
| Pressure setting range (family) | 10-25 bar g (145-363 psig) |
| Strength test pressure | 43 bar g (624 psig) |
| Media temperature range | -30 to 100 C (-22 to 212 F) |
| Applicable media | R717 (ammonia), HFC, HCFC (R22, R134a, R404A), R744 (CO2) |
| Housing material | special low-temperature steel |
| Spindle and seat | stainless steel |
| Cone gasket | special chloroprene (neoprene) compound |
| Conformity assessment | PED 2014/68/EU, category IV, fluid group I, CE marked |
| Discharge capacity standard | ISO 4126-1 / EN 13136 |
| Approvals | CE, EAC |
| Net weight | 3.946 kg |
| Gross weight | 3.946 kg |
| EAN | 5702428192095 |
| Material | Special low-temperature steel housing; stainless steel spindle and seat; chloroprene (neoprene) cone gasket |
| Pressure rating | 16 bar g (232 psig) set pressure |
| Temperature range | -30 to 100 C |
| Standard size | Inlet G 1 1/4 in x outlet G 1 1/2 in (ISO 228/1) |
| Thread standard | ISO 228/1 |
| MOQ | 1 |
Danfoss SFV 25 safety relief valve. Install with the spring housing upwards for exact opening pressure. Recommended to install in pairs on a DSV double stop / change-over valve so one valve can be serviced while the other protects the vessel — SFV 25 pairs with the DSV 2 change-over valve (2 x SFV 25) and the matching 148F30xx flange + gasket spare set. Select by required set pressure (16 bar g) and certificate type.